Plan Review Notes
Plan Review Notes For Permit 06010507
Permit Number 06010507
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-08 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE DESIGN AND PLANS MAKE
 REFERENCE TO THE 2001 FBC. PLEASE SEE
 BLDG COMMENTS AS THE 2004 FBC WAS
 ADOPTED OCT 1ST, 2005
  
 2)NOTE: PLEASE SEE PLANS WERE REQUIRED
 TO BE SUBMITTED FOR PERMIT BEFORE THE
 JAN 12TH, 2006 DEADLINE FOR PALM BEACH
 COUNTY IMPACT FEE INCREASE. PLEASE SEE
 BLDG REVIEW COMMENTS AS PLANS WERE NOT
 SUBMITTED FOR PERMIT UNTIL 2/6/06 AND
 MAY REQUIRE ADDITIONAL FEES BY PBC.
  
 3)NOTE: PLEASE ALSO SEE BLDG REVIEW
 COMMENTS AS VALUE FOR THIS TWO-STORY
 DWELLING SEEMS LOW FOR SCOPE OF WORK.
 PLEASE SEE FBC 108.3 , VALUATION IS
 BASED ON ALL LABOR AND MATERIALS.
 VALUE TO BE ADJUSTED.
  
 4)NOTE: PLEASE CORRELATE PANEL SCHEDULE,
 WITH RISER AND PLANS. ONE SHOWS 200A AND
 THE OTHER LOCATIONS INDICATE PANEL AS
 150A'S?
 215.5
  
 5)NOTE: PLEASE INCLUDE ALL FEEDERS FROM
 MAIN DISCONNECT TO SUB PANEL.
 PLEASESHOW EQUIPMENT GROUNDING
 CONDUCTOR.
 310.16,240.4, 310.15B6, 250.110, 250.122
 ETC
  
 6)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. REDLINED ON ONE SET.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT THE NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  