2006-02-08 00:00:00 | ********* UNSAT *********** |
| |
| 1)NOTE: PLEASE SEE DESIGN AND PLANS MAKE |
| REFERENCE TO THE 2001 FBC. PLEASE SEE |
| BLDG COMMENTS AS THE 2004 FBC WAS |
| ADOPTED OCT 1ST, 2005 |
| |
| 2)NOTE: PLEASE SEE PLANS WERE REQUIRED |
| TO BE SUBMITTED FOR PERMIT BEFORE THE |
| JAN 12TH, 2006 DEADLINE FOR PALM BEACH |
| COUNTY IMPACT FEE INCREASE. PLEASE SEE |
| BLDG REVIEW COMMENTS AS PLANS WERE NOT |
| SUBMITTED FOR PERMIT UNTIL 2/6/06 AND |
| MAY REQUIRE ADDITIONAL FEES BY PBC. |
| |
| 3)NOTE: PLEASE ALSO SEE BLDG REVIEW |
| COMMENTS AS VALUE FOR THIS TWO-STORY |
| DWELLING SEEMS LOW FOR SCOPE OF WORK. |
| PLEASE SEE FBC 108.3 , VALUATION IS |
| BASED ON ALL LABOR AND MATERIALS. |
| VALUE TO BE ADJUSTED. |
| |
| 4)NOTE: PLEASE CORRELATE PANEL SCHEDULE, |
| WITH RISER AND PLANS. ONE SHOWS 200A AND |
| THE OTHER LOCATIONS INDICATE PANEL AS |
| 150A'S? |
| 215.5 |
| |
| 5)NOTE: PLEASE INCLUDE ALL FEEDERS FROM |
| MAIN DISCONNECT TO SUB PANEL. |
| PLEASESHOW EQUIPMENT GROUNDING |
| CONDUCTOR. |
| 310.16,240.4, 310.15B6, 250.110, 250.122 |
| ETC |
| |
| 6)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52. REDLINED ON ONE SET. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT THE NEW REVISED SHEETS |
| INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| SHEETS FOR REFERENCE ONLY. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |