Plan Review Notes
Plan Review Notes For Permit 06010506
Permit Number 06010506
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-06 00:00:00 
  
 PROVISO
  
 WHEN RESUBMITTING FOR MECHANICAL
 COMMENTS, PROVIDE THE FOLLOWING ON THE
 ELECTRICAL SHEET.
  
 PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 AN EQUIPMENT GROUND FROM THE DISCONNECT
 TO THE PANEL MUST BE INDICATED ON THE
 RISER PER 250.122.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  