2006-03-13 00:00:00 | |
| |
| |
| DENIED |
| |
| |
| |
| 1) PERMIT VALUATION IS LOW, VALUATION |
| HAS BEEN ADJUSTED TO THE AVERAGE |
| CONSTRUCTION COSTS AS SET OUT BY ICC PER |
| 108.3 FBC* |
| |
| 2) CORRECT THE FOLLOWING INFORMATION ON |
| DRAWINGS, |
| A) UPDATEWIND DESIGN CRITERIA TO |
| NEW STANDARD |
| B) BUILDING TYPE |
| C) CONCRETE STRENGTH ON FOUNDATION |
| NOTES AND GENERAL NOTES DIFFER |
| D) FASTENERS DIFFER ON GARAGE DOOR BUCK |
| DETAIL AND FASTENER SCHEDULE |
| E) DETAIL B/1 ON FOUNDATION PLAN |
| F) MEAN ROOF HEIGHT AND OVERALL |
| BUILDING HEIGHT ON A/4 |
| G) ADDRESS ON SITE PLAN A/4 IS LAKE |
| WORTH |
| |
| 3) SHOW DRAINAGE ON SITE PLANS PER |
| R401.3 FBC |
| |
| 4) PROVIDE SOIL REPORT PER R401.4 FBC |
| AND ARCHITECTS GENERAL NOTES #7 |
| |
| 5) FOUNDATION #3 SHALL BE A MINIMUM OF |
| 12" BELOW GRADE PER R403.1.4 FBC SHOW ON |
| DETAIL H/2 |
| |
| 6) BEDROOM WINDOWS DO NOT MEET |
| EMERGENCY EGRESS REQUIREMENTS PER R310.1 |
| - R310.1.4 FBC SHOW COMPLIANCE |
| |
| 7) DOORS, WALLS, AND CEILING BETWEEN |
| GARAGE AND DWELLING SHALL MEET THE |
| REQUIREMENTS OF SECTION R309 FBC |
| |
| 8) SPECIFY BEAM/LINTEL LENGTH AND THAT |
| THEY COMPLY WITH 2104.1.5 FBC |
| |
| 9) INSULATION IS REQUIRED BETWEEN |
| GARAGE AND DWELLING (WALLS AND CEILING) |
| PROVIDE DETAIL OR NOTES |
| |
| 10) SUBMIT TRUSS DRAWINGS FOR ROOF AND |
| 2ND FLOOR PER106.1.1.2 FBC* AND |
| R802.10.1 |
| |
| 11) THOSE PRODUCTS WHICH ARE REGULATED |
| BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| |
| 12) PROVIDE CERTIFICATION LETTER FROM |
| ATRIUM WINDOWS THAT WIND LOADS WILL BE |
| MET FOR SH WINDOWS |
| |
| 13) PRODUCT APPROVAL FOR SIMONTON SGD |
| HAS A MAXIMUM WIDTH OF 72" |
| |
| 14) PROVIDE A KEY PLAN AND INSTALLATION |
| SCHEDULE SIMILAR TO ATTACHED SAMPLE ALSO |
| SHOW ATTACHMENT TYPE, ETC. ON PRODUCT |
| APPROVALS |
| |
| 15) RADON FEES SHALL BE COLLECTED FOR |
| THE STATE OF FLORIDA PER CHAPTER 10D-91 |
| FAC |
| |
| 16) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO A |
| PERMIT BEING ISSUED |
| |
| NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| FBC* = WEST PALM BEACH |
| ADMINISTATIVE AMMENDMENTS TO FBC |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| |
| |
| BLDG PLAN REVIEW |