Plan Review Notes For Permit 06010462 |
Permit Number |
06010462 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-30 00:00:00 | | | | | | | | | PROVISO | | REFERENCE FBC-2004 PLUMBING | | | | 608.16.5 CONNECTIONS TO LAWN IRRIGATION | | SYSTEMS: THE POTABLE WATER SUPPLY TO | | IRRIGATION SYSTEMS SHALL BE PROTECTED | | AGAINST BACKFLOW BY AN ATMOSPHERIC-TYPE | | VACUUM BREAKER, A PRESSURE-TYPE VACUUM | | BREAKER OR A REDUCED PRESSURE PRINCIPLE | | BACKFLOW PREVENTER. A VALVE SHALL NOT BE | | INSTALLED DOWNSTREAM FROM AN ATMOSPHERIC | | VACUUM BEEAKER. WHERE CHEMICALS ARE | | INTRODUCED INTO THE SYSTEM, THE POTABLE | | WATER SHALL BE PROTECTED AGAINST | | BACKFLOW BY A REDUCED PRESSURE PRINCIPLE | | BACKFLOW PREVENTER. SEC. 106.3.5.1.3 | | BACKFLOW TO BE INSTALLED BY PLUMBING | | CONTRACTOR |
|