Plan Review Notes
Plan Review Notes For Permit 06010452
Permit Number 06010452
Review Stop E
Sequence Number 7
Notes
Date Text
2006-12-08 19:08:10***UNSAT ***
  
  
 1) NOTE:PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE
 OF WORK ON THIS PROJECT NEEDS TO BE UPDATED. PLEASE
 KNOW EVEN WITH THE PREVIOUS APPLIED VALUE UNDER 433
 AVON WHICH WAS $114K AND THE VALUE ON THIS PERMIT AT
 $85K, THE VALUE FOR ALL WORK IN ACTUAL SCOPE IS
 EXTREMELY LOW. PLEASE KNOW THE ELECTRICAL ALONE IN THIS
 BUILDING IS HIGHER THAN THE APPLIED VALUE FOR THIS
 PERMIT. PLEASE KNOW THE VALUE SHALL INCLUDE ALL LABOR
 AND MATERIALS.
 PLEASE KNOW IF A VALUE IS NOT ADJUSTED FOR ALL WORK AND
 MATERIALS AS SHOWN, ONE WILL BE APPLIED BASED ON THE
 TABLES FROM THE FBC OR MARSHALL'S AND SWIFT GUIDE.
 FBC 108.3
  
 2) NOTE: PLEASE SEE PANEL P5 IS BEING SHOWN AT 600A'S
 WITH A 225A FEED. PLEASE VERIFY.
 FBC 106.1.2
  
 3) NOTE: PLEASE KNOW AS THE SCOPE INVOLVED EXCEEDS THAT
 OF 30%, PLEASE SEE FBC CHAPTER 13 WILL APPLY TO THE
 EXISTING OFFICES. THIS WAS GONE OVER IN PREVIOUS
 MEETINGS WITH THE ENGINEER AND DESIGN TEAM AND THIS
 INFORMATION WAS TO BE UPDATED AND APPLIED TO PLANS.
 PLEASE SEE LIGHTING CONTROLS, LIGHTING DENSITIES, ETC.
 PLEASE SEE OTHER ROOM(S) ON PLANS WHICH DO NOT SEEM TO
 INDICATE A SEPARATE SPACE CONTROL.
 PLEASE SEE NEW OUTSIDE LIGHTS REQUIRED TO BE PART OF
 THE EXTERIOR LIGHTING POWER ALLOWANCES.
 FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 13-415.2.
  
 4) NOTE: PLEASE VERIFY SUB SECTIONS FOR PANELS, 4, AND
 2 NOT ON RISER.
  
 5) NOTE: PLEASE PROVIDE A COMPLETE LOAD SUMMARY FOR THE
 GENERATOR AS WELL AS THE LOADS ON EACH OF THE EDP AND
 THE EDPA.
 220, 702.5
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  