Plan Review Notes For Permit 06010452 |
Permit Number |
06010452 |
|
Review Stop |
P |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2007-01-13 17:30:42 | DENIED | | REFERENCE: CITY MUNICIPAL CODE | | UTILITY DEPT STANDARDS | | | | 1. SHT P-1.1 900 GAL SAND/OIL INTERCEPTOR DETAIL. | | UTILITY STANDARDS INDICATE 3" WALLS AND 4" BOTTOM | | REQUIRED ON ALL INTERCEPTORS. (SEE ATTACHED SHEET). | | CITY CODE SECTION 90-124(7)(F) STATES "EACH INTERCEPTOR | | SHALL BE CONSTRUCTED OF STEEL REINFORCED CONCRETE. | | PLANS CALL FOR "FIBRILLATED POLYPROPLYLENE FIBER". | | DETAIL ALSO INDICATES 2.5" WALLS AND 3" BOTTOM. THIS | | DOES NOT MEET MUNICIPAL CODE OR UTILITY STANDARDS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|