Plan Review Notes
Plan Review Notes For Permit 06010452
Permit Number 06010452
Review Stop P
Sequence Number 6
Notes
Date Text
2007-01-13 17:30:42DENIED
 REFERENCE: CITY MUNICIPAL CODE
 UTILITY DEPT STANDARDS
  
 1. SHT P-1.1 900 GAL SAND/OIL INTERCEPTOR DETAIL.
 UTILITY STANDARDS INDICATE 3" WALLS AND 4" BOTTOM
 REQUIRED ON ALL INTERCEPTORS. (SEE ATTACHED SHEET).
 CITY CODE SECTION 90-124(7)(F) STATES "EACH INTERCEPTOR
 SHALL BE CONSTRUCTED OF STEEL REINFORCED CONCRETE.
 PLANS CALL FOR "FIBRILLATED POLYPROPLYLENE FIBER".
 DETAIL ALSO INDICATES 2.5" WALLS AND 3" BOTTOM. THIS
 DOES NOT MEET MUNICIPAL CODE OR UTILITY STANDARDS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731