Plan Review Notes For Permit 06010452 |
Permit Number |
06010452 |
|
Review Stop |
E |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2006-10-22 08:41:07 | ****** NOTESREDLINED ********* | | | | | | | | 1) PLEASE SEE AS ONLY TWO SETS OF SPEC BOOKS WERE | | SUBMITTED AND THREE SETS OF PLANS WERE SUBMITTED, THE | | THIRD SET OF MANUFACTURES SPECS/CUT SHEETS FOR EACH OF | | THE ATS'S WERE ATTACHED TO THE SET 3OF 3. ON RISER | | SHEET. | | THE OTHER TWO SETS WERE PLACED IN SPEC BOOKS . | | | | 2) PLEASE SEE PLANS CALL FOR SPRAY BOOTH TO BE UNDER | | SEPARATE PERMIT(S) AND ARE NOT INCLUDED IN EITHER PHASE | | ONE OR PHASE TWO ON PLANS. PLEASE KNOW THAT THE | | MANUFACTURES SPEC WERE REMOVED FROM THE TWO SPEC BOOKS | | SUBMITTED AND PLACED WITH THE OTHER THREE SETS OF SPECS | | SUBMITTED SEPARATELY (LOOSE). | | THESE ARE LABELEDNIC AND WILL BE RETURNED TO | | CONTRACTOR FOR FUTURE USE. | | | | 3) NOTE: PLEASE SEE PHASE I RISERCALLS FOR SPACE FOR | | "FUTURE" METER, THIS IS REDLINED AS NO 2ND METER IS | | PERMITTED UNLESS PROPER REQUIRED TENANT SEPARATION IS | | CONSTRUCTED. | | | | 4) PLEASE BE AWAREBOTH PERMITS FOR GEN-ELEC AND FUEL | | PERMITS 06061596(ELEC) AND 06061597(FUEL) HAVE HAD | | ADDRESSES CHANGED TO CORRELATE WITH THE ADDRESS OF 422 | | SUNSET AND GEN-COM PERMIT NUMBER 06061595. | | | | | | ELECTRICAL PLANS STAMPED ALONG WITH SPECS FOR ATS'S. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | 2006-10-22 08:01:50 | REVIEW IN PROGRESS | 2006-10-21 18:44:46 | ELEC REVIEW IN PROGRESS |
|