Date |
Text |
2006-08-10 00:00:00 | *** UNSAT *** |
| |
| ** PLEASE SEE COMMENTS BELOW, SOME ARE |
| EXISTING AND SOME ARE NEW BASED ON PLANS |
| SUBMITTED. |
| |
| 1) NOTE: PLEASE SEE PHASE 1, SHOWS METER |
| FUTURE AND YET AND METER CAN IS BEING |
| INSTALLED. PLEASE SEE PHASE II WHICH |
| SHOWS THE METER BEING INSTALLED AS |
| EXISTING. |
| PLEASE KNOW WITHOUT TENANT SEPARATION |
| THIS METERCAN IS NOT PERMITTED. SEC'S |
| FROM GUTTER SHALL GO DIRECTLY INTO THE |
| MAIN2 OF 2. |
| THIS IS A SINGLE OCCUPANCY , ANY FUTURE |
| METER CAN WILL BE DONE AT THE TIME OF |
| SUCH SEPARATION OF TENANTS TAKES PLACE. |
| THIS WAS THE UDNERSTANDING OF THE LAST |
| MEETING BY THE DESIGN TEAM. |
| PLEASE ALSO SEE PHASE ONE FOR RISER |
| SHOWS CONDUIT AND FEEDERS TO NOTHING |
| AFTER THE MAIN DISCONNECT. |
| |
| 2) NOTE: PLEASE SEE PLANS INDICATE A |
| PHASE 1 FOR E-1.1, YET TITLE BLOCK CALLS |
| FOR PHASE II. PLEASE SEE THIS SHEET DOES |
| NOT CORRELATE WITH PHASING OF THE |
| PROJECT. |
| PLEASE SEE SPRAY BOOTH IS BEING SHOWN AS |
| FUTURE ON PHASE TWO SHEETS, YET SHOWS AS |
| BEING INSTALLED ON OTHER SHEETS AND ON |
| PAHSE TWO PANEL SCHEDULES. |
| PLEASE KNOW ALL INFORMATION AS REQUESTED |
| FOR LOCATIONS ETC WAS NOT SHOWN FOR |
| SPRAY BOOTH. |
| PLEASE SEE NOTE FROM PREVIOUS REVIEW |
| BELOW; |
| "PLEASE SEE NEC 511 AND 516. ALL AREAS |
| AND CLASS LOCATION SHALL BE INDICATED |
| AND LAYED OUT PER NEC 500, 500.5, 501, |
| CLASS 1 DIV 1, CLASS 1 DIV 2? |
| NFPA-88B, 1997 |
| PLEASE SEE THIS SHOWN WITH A "WAREHOUSE" |
| OCCUPANCY WHICH DOES NOT SEEM TO |
| CORRELATE WITH NEW REVISED PLANS AND |
| PROPOSED WORK. |
| |
| 3) NOTE: PLEASE SEE SEAL BY THE ENGINEER |
| IS NOT CLEAR AND VISABLE WITH ALL |
| INFORMATION ON SAID SEAL. THIS OFFICE |
| HAS ATTEMPTED TO SHADE THESE SHEETS TO |
| SHOW ALL INFORMATION, HOWEVER THIS HAS |
| NOT BEEN AFFECTIVE. |
| PLEASE SEE FAC 61G15-23.001 |
| "RAISED SEAL MUST BE CLEAR AND VISABLE" |
| |
| 4) NOTE: MISSING DISCONNECT'S FOR CU'S. |
| 440.11 |
| |
| 5) NOTE: PLEASE SEE MISSING GFI FOR CU'S |
| 210.63, 210.8. |
| |
| 6) NOTE: PLEASE SEE WIRE AND CONDUIT |
| SCHEDULE AS #2 SHOWS AN "EQUIPMENT |
| GROUNDING CONDUCTOR" BEFORE THE FIRST |
| MEANS OF DISCONNECT. PLEASE SEE 250.6, |
| 250.24 B AS THE "EQUIPMENT GROUNDING |
| CONDUCTOR" IS ONLY INSTALLED AFTER THE |
| FIRST MEANS OF DISCONNECT. |
| PLEASE SEE SEC'S TO MAIN 1 OF 1. |
| |
| |
| |
| |
| |
| |
| 6) NOTE: ** IMPORTANT" AS REQUESTED BY |
| THE BUIDLING REVIEWER ON PREVIOUS NOTES: |
| ONCE ALL REVIEWS ARE COMPLETE, BEFORE |
| RESUBMITTING PLANS, PLEASE COMPLETELY |
| REMOVE ALL OLD/VOIDED SHEETS AND ONLY |
| INSERT NEW REVISED SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. ONE COPY |
| OF THE OLD/VOIDED REMOVED SHEETS SHOULD |
| BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP TO ALLEAVIATE ANY DELAYS |
| INTHE PROCESS. |
| |
| ** PLEASE KNOW, ONE SET OF EACH OF THE |
| PREVIOUS SUBMITTED ELECTRICAL PLANS |
| ALONG WITH THE NEW REVISED ELECTRICAL |
| PLANS ARE BEING RETAINED BY THIS OFFICE |
| AS EACH SET CONTAINS COMPLETELY |
| DIFFERENT INFORMATION FOR USE/OCCUPANCY |
| ETC. |
| |
| PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT ELETRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS, OR COMMENTS |
| PLEASE CALL. |
| A CALLED WAS PLACED TO THE ELECTRICAL |
| ENGINEER'S OFFICE AND A MESSAGE WAS LEFT |
| AS OF THIS REVIEW TO GO OVER PLANS. |
| |
| |