Plan Review Notes
Plan Review Notes For Permit 06010452
Permit Number 06010452
Review Stop P
Sequence Number 4
Notes
Date Text
2006-09-22 00:00:00DENIED;
 1ADA DETAIL FOR PHASE 11 ON PAGE A-2
 ONLY SHOWS A DETAIL OF LAVATORY. DETAIL
 OF WHOLE BATHROOM IS REQUIRED, SHOW THE
 TOILET, SHOWER, AND LAVATORY IN DETAIL.
 REQUIREMENTS FOR COMPLIANCE CAN BE
 FOUND, FBC-2004 CHAPTER 11; TOILET SEC.
 11-4.16.1 THRU 11-4.16.6; LAVATORY
 11-4.19.1 THRU 11-4.19.6; SHOWER DETAIL
 SECTION 11-4.21.1 THRU 11-4.21.8.
 2.HOT WATER REQUIRED TO SERVICE SINK.
 (SHOW ON PLANS)LOCATION SIZE AND FUIL
 SORCE OF WATER HEATER.
 3.SANITARY RISER DIAGRAM;
 A)TRENCH DRAIN AND FLOOR DRAIN SHALL
 NOT BE DOUBLE TRAPPED. SEC.1002.1
 B)WHAT IS THE 4" VERTICAL DRAIN AND
 BACK WATER VALVE FOR? NEED MORE
 INFOREMATION.
 C)WHY IS A FLOOR DRAIN NEEDED IN THE
 FUTURE PAINT BOOTH? (SECOND
 REQUEST)
 4. SAND INTERCEPTER; (SECOND REQUEST)
 PLANS MUST BE REVIEW AND APROVED BY THE
 UTILITY DEPARTMENT FOR SIZE AND
 LOCATION.
 THE CONTACT PERSON IS;
 LYNN MASSON
 PHONE822-2271
 FAX 822-2279
 E-MAIL [email protected]
 5.PLUMBING FIXTURE REQUIREMENT TABLE FOR
 PHASE 11 IS NOT CORRECT. WORK WILL BE
 DONE IN IN THIS PART OF THE BUILDING.
 PLEASE CHANGE CLASIFICATION TO BUSINESS,
 OR CHANGE BOTH PHASES TO BUSINESS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  