Date |
Text |
2006-09-22 00:00:00 | DENIED; |
| 1ADA DETAIL FOR PHASE 11 ON PAGE A-2 |
| ONLY SHOWS A DETAIL OF LAVATORY. DETAIL |
| OF WHOLE BATHROOM IS REQUIRED, SHOW THE |
| TOILET, SHOWER, AND LAVATORY IN DETAIL. |
| REQUIREMENTS FOR COMPLIANCE CAN BE |
| FOUND, FBC-2004 CHAPTER 11; TOILET SEC. |
| 11-4.16.1 THRU 11-4.16.6; LAVATORY |
| 11-4.19.1 THRU 11-4.19.6; SHOWER DETAIL |
| SECTION 11-4.21.1 THRU 11-4.21.8. |
| 2.HOT WATER REQUIRED TO SERVICE SINK. |
| (SHOW ON PLANS)LOCATION SIZE AND FUIL |
| SORCE OF WATER HEATER. |
| 3.SANITARY RISER DIAGRAM; |
| A)TRENCH DRAIN AND FLOOR DRAIN SHALL |
| NOT BE DOUBLE TRAPPED. SEC.1002.1 |
| B)WHAT IS THE 4" VERTICAL DRAIN AND |
| BACK WATER VALVE FOR? NEED MORE |
| INFOREMATION. |
| C)WHY IS A FLOOR DRAIN NEEDED IN THE |
| FUTURE PAINT BOOTH? (SECOND |
| REQUEST) |
| 4. SAND INTERCEPTER; (SECOND REQUEST) |
| PLANS MUST BE REVIEW AND APROVED BY THE |
| UTILITY DEPARTMENT FOR SIZE AND |
| LOCATION. |
| THE CONTACT PERSON IS; |
| LYNN MASSON |
| PHONE822-2271 |
| FAX 822-2279 |
| E-MAIL [email protected] |
| 5.PLUMBING FIXTURE REQUIREMENT TABLE FOR |
| PHASE 11 IS NOT CORRECT. WORK WILL BE |
| DONE IN IN THIS PART OF THE BUILDING. |
| PLEASE CHANGE CLASIFICATION TO BUSINESS, |
| OR CHANGE BOTH PHASES TO BUSINESS. |
| PLUMBING PLAN REVIEW BY; |
| JOHN LEECH |
| 805-6695 |
| |