2006-07-07 00:00:00 | ********* UNSAT 4TH REVIEW ************ |
| |
| PLEASE SEE NOTES BELOW AS MANY ARE NEW |
| DUE TO COMPLETELY NEW RISERAND MANY |
| CHANGES ON PLANS. |
| PLEASE SEE OTHER NOTES PER THIS REVIEW. |
| * REPRESENTS FBC ADMINISTRATIVE SECTION |
| 106.1.2 AS ADOPTED BY THE CITY OF WEST |
| PALM BEACH |
| |
| 1) NOTE: IMPORTANT, ONCE ALL REVIEW(S) |
| ARE DONE AND BEFORE PLANS ARE |
| RESUBMITTED, PLEASE COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS FROM SETS AND ONLY |
| INSERT THE NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| PLEASE ALSO REMOVE ALL STAPLED PRODUCT |
| APPROVALS WHICH ARE NOW ATTACHED TO |
| PLANS. THESE SHOULD BE IN TWO SETS |
| SEPARATELY FROM PLANS AND NOT ATTACHED. |
| THIS COMMENT IS FOR OTHER TRADE(S) |
| SHEETS WHICH WERE LEFT IN SETS. |
| PLEASE ONLY SUBMIT ONE COPY OF THE |
| OLD/VOIDED REMOVED SHEETS FOR REFERENCE. |
| |
| 2) NOTE: PLEASE BE SURE PLANS REFLECT |
| THE CURRENT CODES IN EFFECT. PLEASE SEE |
| ELECTRICAL PLANS REFLECT THE 2001 FBC. |
| PLEASE ADJUST AND REFERENC THE FOLLOWING |
| WHICH ARE CURRENTLY UNDER. |
| 2002 NFPA-70 (DONE), 2002 NFPA-72, 2003 |
| NFPA-101, 2004 FBC. |
| |
| 3) NOTE: PLEASE SEE NOTES BELOW WITH |
| RESPECT TO SERVICE(S) BEING PROPOSED. |
| PLEASE KNOW, IN THE MEAN TIME ANY ATS |
| BEING INSTALLED IN ANY SERVICE REQUIRES |
| THE MANUFACTURES SPECS/CUT SHEETS TO BE |
| SUBMITTED. PLEASE BE SURE THESE SHEETS |
| INDICATE A LISTING BY ANRTL. |
| 106.1.2 FBC ADMIN SECT, 110.3 |
| |
| 4) NOTE: PLEASE CORRELATE PLANS WITH |
| RISER DIAGRAM. PLEASE SEE SOME SERVICE |
| EQUIPMENT WHICH IS BEING SHOWN ON RISER, |
| HOWEVER THESE ARE NOT ON PLANS, POWER OR |
| LIGHTING SHEETS? (EDP ETC.) |
| 106.1.2* |
| |
| 5) NOTE: PLEASE CORRELATE ALL CIRCUITING |
| ON PLANS WITH SUBMITTED PANEL SCHEDULES. |
| PLEASE SEE MANY ITEMS ARE BEING SHOWN |
| CIRCUITED TO THE PREVIOUS PANEL |
| SCHEDULES. |
| PLEASE SEE PANEL SCHEDULES WHICH SHOW |
| SPARE, YET CIRCUITS ARE ON PLANS. |
| PLEASE SEE A/C RTU'S BEING SHOWN TO MDP, |
| HOWEVER MDP DO NOT SHOW THESE ANYMORE. |
| PLEASE SEE ME LTS ETC. |
| 106.1.2* |
| |
| 6) NOTE: PLEASE KNOW, EM LIGHTING SHALL |
| BE CIRCUITED PER 700.12E. |
| PLEASE KNOW, AS THE CIRCUIT FOR THE EM |
| LTS IS NOW SHOWN AS A BLANK ON PANEL |
| SCHEDULE. PLEASE KNOW UNLESS THE |
| GENERATOR WAS PERMITTED UNDER THIS |
| PERMIT WHICH IT IS NOT, EM LTSWILL BE |
| REQUIRED WITH BATTERY BACK UP AT A MIN |
| AT THIS TIME AND UNDER THIS PERMIT. |
| PLEASE SEE 700.12E, 700.16, LS 101 7.8, |
| 7.9. |
| |
| 7) NOTE: PLEASE SEE"EDP"IS BEING |
| SHOWN AS 800A MLO AND WITH A LOAD OF |
| 300+ A'S YET, THE OCP DEVICE SHOWN ON |
| MDP IS ONLY SHOWN AS 125A'S? PLEASE SEE |
| THIS EXCEEDS THE RATING OF THE |
| OVERCURRENT DEVICE. |
| 240.4,310.16,240, ETC. |
| |
| 8) NOTE: PLEASE SEE MDP IS NOTED AND |
| CIRCUITS ON MDP ETC ARE NOTED WITH A #1 |
| IN A CIRCLE WHICH MENTIONS TO SEE RISER |
| FOR FEEDERS, CONDUITS ETC. PLEASE SEE |
| RISER DOES NOT INDICATE ANY FEEDERS ETC |
| FROM MDP TO ATS AND FROM ATS TO EDP. |
| PLEASE REVISE AND ADJUST. |
| 240.4,310.16, 215.5 ETC |
| |
| 9) NOTE: PLEASE KNOW, A DISCONNECTING |
| MEANS WILL BE REQUIRED GROUPED FOR |
| FEEDERS COMING FROM FUTURE GENERATOR. |
| THIS MAY BE SOMETHING PLACED INTO THE |
| DESIGN AT THIS TIME OR AT A LATER DATE. |
| PLEASE ALSO SEE NOTES FOR SERVICE. |
| 225.31-225.39, 110.27 |
| |
| 10) NOTE: PLEASE INCLUDE SECT #2 OF P1 |
| ON RISER DIAGRAM. |
| PLEASE ALSO INDICATE IF THE PANEL "P1" |
| CONTAINS OCP FEEDING SECT #2 OR DOES |
| "P1" CONTAIN "FEED-THRU"LUGS. |
| PLEASE SHOW. |
| 106.1.2* |
| |
| 11) NOTE: PLEASE SEE ENERGY CALCULATIONS |
| DO NOT REFLECT LIGHTING INSTALLED AND |
| LIGHTING ALLOWANCE IN CALCS. IT IS NOTED |
| ON PLANS AND LETTER FROM ENGINEER THAT |
| THE "LPD" ARE UNDER MAX LIMITS, YET THE |
| TOTAL WATTAGE ETC SHOULD BE IN |
| CALCULATIONS. |
| FBC 13-415.1.AB.1,13-415.2.ABC.1 |
| |
| 12) NOTE: PLEASE CLARIFY NEWOR |
| EXISTING ROOF TOP GFI(S) FOR A/C |
| EQUIPMENT. |
| 210.63,210.8 |
| |
| 13) NOTE: PLEASE CLARIFY THE NUMBER OF |
| AHU'S IN THIS SPACE, AS "M" SHEET |
| MENITONS AHU'S #1, #2, #3 AND #4?? |
| ?? |
| |
| 14) NOTE: PLEASE SEE NOTICE OF |
| COMMENCMENT ATTACHED TO PACKAGE HAS |
| EXPIRED PER FS 713.13(2). |
| THIS WILL BE REQUIRED OT BE RE-RECORDED |
| AND SUBMITTED BEFORE PICKING UP PERMIT. |
| |
| PLEASE SEE THE FOLLOWING AS COMMENTED |
| WITH RESPECT TO THE SERVICE. |
| |
| ** CALLED ENGINEER ON 7/7/06 AT 4:45 PM |
| AND LEFT MESSAGE TO CONTACT ME WITH |
| RESPECT TO THE SERVICE, SEPARATION ETC. |
| |
| AS PER CONSULTATION WITH MR. ROBERT AND |
| OTHERS. THE FOLLOWING TWO OPTIONS MAY BE |
| DONE. |
| |
| 1) IF OPENING BETWEEN THIS SPACE AND THE |
| ADJOINING FUTURE SPACE IS GOING TO |
| REMAIN, EVEN WITH THE RATED OVER-HEAD |
| DOOR, THEN THE ELECTRICAL SERVICE WILL |
| HAVE TO BE REVISED TO INCLUDE ONLY ONE |
| SERVICE RISER, ONE METER. |
| |
| 2)IF THE WALL IS CLOSED UP TO PROVIDE |
| THE PROPER TENANT SEPARATION AS REQUIRED |
| FOR OCCUPANCY TYPES, THEN ONE SERVICE |
| WITH TWO METERS AND TWO MAINS WOULD BE |
| PERMITTED. |
| |
| PLEASE KNOW ANY EMERGENCY BACK UP SYSTEM |
| MAY STILL BE INSTALLED AFTER EACH MAIN |
| ETC. |
| |
| ** THIS IS CONSIDERED ONE "BUILDING" |
| UNDER THE DEFINITIONS OF THE FBC. |
| ONLY IF SEPARATED BY A "FIRE WALL" WOULD |
| THESE BE CONSIDERED TWO SEPARATE |
| BUILDINGS. PLEASE SEE "FIRE WALL" UNDER |
| DEFINITIONS. |
| IF CONSTRUCTION OF CLOSING IN THE WALL , |
| AND CONTRUCTION OF THE EXISTING WALL, |
| CEILING ETC BETWEEN THE TWO MEET THE |
| "FIRE WALL" REQUIRMENTS, THEN TWO |
| SEPARATE SERVICES WILL BE PERMITTED WITH |
| TWO SEPARATE OPT STAND-BY GENERATOR |
| SYSTEMS. |
| |
| ** PLEASE KNOW, A MEETING SHOULD BE HELD |
| TO GO COMMENTS, DESIGN ETC BEFORE |
| RESUBMITTING PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| PLANS WERE ROUTED TO MR ROBERT BROWN |
| AFTER THE ELECTRICAL REVIEW. |