2006-07-07 00:00:00********* UNSAT 4TH REVIEW ************
  
 PLEASE SEE NOTES BELOW AS MANY ARE NEW
 DUE TO COMPLETELY NEW RISERAND MANY
 CHANGES ON PLANS.
 PLEASE SEE OTHER NOTES PER THIS REVIEW.
 * REPRESENTS FBC ADMINISTRATIVE SECTION
 106.1.2 AS ADOPTED BY THE CITY OF WEST
 PALM BEACH
  
 1) NOTE: IMPORTANT, ONCE ALL REVIEW(S)
 ARE DONE AND BEFORE PLANS ARE
 RESUBMITTED, PLEASE COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT THE NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE ALSO REMOVE ALL STAPLED PRODUCT
 APPROVALS WHICH ARE NOW ATTACHED TO
 PLANS. THESE SHOULD BE IN TWO SETS
 SEPARATELY FROM PLANS AND NOT ATTACHED.
 THIS COMMENT IS FOR OTHER TRADE(S)
 SHEETS WHICH WERE LEFT IN SETS.
 PLEASE ONLY SUBMIT ONE COPY OF THE
 OLD/VOIDED REMOVED SHEETS FOR REFERENCE.
  
 2) NOTE: PLEASE BE SURE PLANS REFLECT
 THE CURRENT CODES IN EFFECT. PLEASE SEE
 ELECTRICAL PLANS REFLECT THE 2001 FBC.
 PLEASE ADJUST AND REFERENC THE FOLLOWING
 WHICH ARE CURRENTLY UNDER.
 2002 NFPA-70 (DONE), 2002 NFPA-72, 2003
 NFPA-101, 2004 FBC.
  
 3) NOTE: PLEASE SEE NOTES BELOW WITH
 RESPECT TO SERVICE(S) BEING PROPOSED.
 PLEASE KNOW, IN THE MEAN TIME ANY ATS
 BEING INSTALLED IN ANY SERVICE REQUIRES
 THE MANUFACTURES SPECS/CUT SHEETS TO BE
 SUBMITTED. PLEASE BE SURE THESE SHEETS
 INDICATE A LISTING BY ANRTL.
 106.1.2 FBC ADMIN SECT, 110.3
  
 4) NOTE: PLEASE CORRELATE PLANS WITH
 RISER DIAGRAM. PLEASE SEE SOME SERVICE
 EQUIPMENT WHICH IS BEING SHOWN ON RISER,
 HOWEVER THESE ARE NOT ON PLANS, POWER OR
 LIGHTING SHEETS? (EDP ETC.)
 106.1.2*
  
 5) NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH SUBMITTED PANEL SCHEDULES.
 PLEASE SEE MANY ITEMS ARE BEING SHOWN
 CIRCUITED TO THE PREVIOUS PANEL
 SCHEDULES.
 PLEASE SEE PANEL SCHEDULES WHICH SHOW
 SPARE, YET CIRCUITS ARE ON PLANS.
 PLEASE SEE A/C RTU'S BEING SHOWN TO MDP,
 HOWEVER MDP DO NOT SHOW THESE ANYMORE.
 PLEASE SEE ME LTS ETC.
 106.1.2*
  
 6) NOTE: PLEASE KNOW, EM LIGHTING SHALL
 BE CIRCUITED PER 700.12E.
 PLEASE KNOW, AS THE CIRCUIT FOR THE EM
 LTS IS NOW SHOWN AS A BLANK ON PANEL
 SCHEDULE. PLEASE KNOW UNLESS THE
 GENERATOR WAS PERMITTED UNDER THIS
 PERMIT WHICH IT IS NOT, EM LTSWILL BE
 REQUIRED WITH BATTERY BACK UP AT A MIN
 AT THIS TIME AND UNDER THIS PERMIT.
 PLEASE SEE 700.12E, 700.16, LS 101 7.8,
 7.9.
  
 7) NOTE: PLEASE SEE"EDP"IS BEING
 SHOWN AS 800A MLO AND WITH A LOAD OF
 300+ A'S YET, THE OCP DEVICE SHOWN ON
 MDP IS ONLY SHOWN AS 125A'S? PLEASE SEE
 THIS EXCEEDS THE RATING OF THE
 OVERCURRENT DEVICE.
 240.4,310.16,240, ETC.
  
 8) NOTE: PLEASE SEE MDP IS NOTED AND
 CIRCUITS ON MDP ETC ARE NOTED WITH A #1
 IN A CIRCLE WHICH MENTIONS TO SEE RISER
 FOR FEEDERS, CONDUITS ETC. PLEASE SEE
 RISER DOES NOT INDICATE ANY FEEDERS ETC
 FROM MDP TO ATS AND FROM ATS TO EDP.
 PLEASE REVISE AND ADJUST.
 240.4,310.16, 215.5 ETC
  
 9) NOTE: PLEASE KNOW, A DISCONNECTING
 MEANS WILL BE REQUIRED GROUPED FOR
 FEEDERS COMING FROM FUTURE GENERATOR.
 THIS MAY BE SOMETHING PLACED INTO THE
 DESIGN AT THIS TIME OR AT A LATER DATE.
 PLEASE ALSO SEE NOTES FOR SERVICE.
 225.31-225.39, 110.27
  
 10) NOTE: PLEASE INCLUDE SECT #2 OF P1
 ON RISER DIAGRAM.
 PLEASE ALSO INDICATE IF THE PANEL "P1"
 CONTAINS OCP FEEDING SECT #2 OR DOES
 "P1" CONTAIN "FEED-THRU"LUGS.
 PLEASE SHOW.
 106.1.2*
  
 11) NOTE: PLEASE SEE ENERGY CALCULATIONS
 DO NOT REFLECT LIGHTING INSTALLED AND
 LIGHTING ALLOWANCE IN CALCS. IT IS NOTED
 ON PLANS AND LETTER FROM ENGINEER THAT
 THE "LPD" ARE UNDER MAX LIMITS, YET THE
 TOTAL WATTAGE ETC SHOULD BE IN
 CALCULATIONS.
 FBC 13-415.1.AB.1,13-415.2.ABC.1
  
 12) NOTE: PLEASE CLARIFY NEWOR
 EXISTING ROOF TOP GFI(S) FOR A/C
 EQUIPMENT.
 210.63,210.8
  
 13) NOTE: PLEASE CLARIFY THE NUMBER OF
 AHU'S IN THIS SPACE, AS "M" SHEET
 MENITONS AHU'S #1, #2, #3 AND #4??
 ??
  
 14) NOTE: PLEASE SEE NOTICE OF
 COMMENCMENT ATTACHED TO PACKAGE HAS
 EXPIRED PER FS 713.13(2).
 THIS WILL BE REQUIRED OT BE RE-RECORDED
 AND SUBMITTED BEFORE PICKING UP PERMIT.
  
 PLEASE SEE THE FOLLOWING AS COMMENTED
 WITH RESPECT TO THE SERVICE.
  
 ** CALLED ENGINEER ON 7/7/06 AT 4:45 PM
 AND LEFT MESSAGE TO CONTACT ME WITH
 RESPECT TO THE SERVICE, SEPARATION ETC.
  
 AS PER CONSULTATION WITH MR. ROBERT AND
 OTHERS. THE FOLLOWING TWO OPTIONS MAY BE
 DONE.
  
 1) IF OPENING BETWEEN THIS SPACE AND THE
 ADJOINING FUTURE SPACE IS GOING TO
 REMAIN, EVEN WITH THE RATED OVER-HEAD
 DOOR, THEN THE ELECTRICAL SERVICE WILL
 HAVE TO BE REVISED TO INCLUDE ONLY ONE
 SERVICE RISER, ONE METER.
  
 2)IF THE WALL IS CLOSED UP TO PROVIDE
 THE PROPER TENANT SEPARATION AS REQUIRED
 FOR OCCUPANCY TYPES, THEN ONE SERVICE
 WITH TWO METERS AND TWO MAINS WOULD BE
 PERMITTED.
  
 PLEASE KNOW ANY EMERGENCY BACK UP SYSTEM
 MAY STILL BE INSTALLED AFTER EACH MAIN
 ETC.
  
 ** THIS IS CONSIDERED ONE "BUILDING"
 UNDER THE DEFINITIONS OF THE FBC.
 ONLY IF SEPARATED BY A "FIRE WALL" WOULD
 THESE BE CONSIDERED TWO SEPARATE
 BUILDINGS. PLEASE SEE "FIRE WALL" UNDER
 DEFINITIONS.
 IF CONSTRUCTION OF CLOSING IN THE WALL ,
 AND CONTRUCTION OF THE EXISTING WALL,
 CEILING ETC BETWEEN THE TWO MEET THE
 "FIRE WALL" REQUIRMENTS, THEN TWO
 SEPARATE SERVICES WILL BE PERMITTED WITH
 TWO SEPARATE OPT STAND-BY GENERATOR
 SYSTEMS.
  
 ** PLEASE KNOW, A MEETING SHOULD BE HELD
 TO GO COMMENTS, DESIGN ETC BEFORE
 RESUBMITTING PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
 PLANS WERE ROUTED TO MR ROBERT BROWN
 AFTER THE ELECTRICAL REVIEW.
2006-07-02 00:00:00SEE DEWEY PALMER WHEN PLANS COME BACK
 IN.