Plan Review Notes
Plan Review Notes For Permit 06010452
Permit Number 06010452
Review Stop M
Sequence Number 3
Notes
Date Text
2006-09-18 00:00:00PROVISO:
 SUBMITTAL FOR THE TEXTILE DUCT &
 DIFFUSERS ARE NOT LISTED WITH UL.
 ANOTHER PRODUCT MAY HAVE TO BE SUBMITTED
 THAT MEET THE CLASS 0 (SURFACE BURNING
 CHARACTERISTICS OF ZERO) OR CLASS 1
 (FLAME SPREAD INDEX <25 AND SMOKE
 DEVELOPED INDEX <50).THIS ISSUE MUST
 BE RESOLVED PRIOR TO INSTALLATION OF ANY
 DUCT.
  
 NON-METALIC DUCT SHALL COMPLY WITH
 2004 FMC 603.4, DUCTS SHALL BE
 CONSTRUCTED WITH CLASS 0 OR CLASS 1 DUCT
 MATERIAL IN ACCORDANCE WITH UL 181.
  
 PLEASE NOTE, FABRIC DUCT SUBMITTED
 (PRIHODA) HAS NO UL LISTING. THE TEST
 REPORT PAGE 3 UNDER "LIMITATIONS" THERE
 IS A WARNING WHICH STATES THE FOLLOWING;
 "THIS DOCUMENT DOES NOT REPRESENT TYPE
 APPROVAL OR CERTIFICATION OF THE
 PRODUCT."
  
  
 ADDITIONAL PERMIT REQUIRED FOR THE SPRAY
 PAINT BOOTH.PLANS AND MANUFACTURER
 SUBMITTAL DATA ON FILE WITH BUILDING
 PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].