Plan Review Notes For Permit 06010452 |
Permit Number |
06010452 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-09-18 00:00:00 | PROVISO: | | SUBMITTAL FOR THE TEXTILE DUCT & | | DIFFUSERS ARE NOT LISTED WITH UL. | | ANOTHER PRODUCT MAY HAVE TO BE SUBMITTED | | THAT MEET THE CLASS 0 (SURFACE BURNING | | CHARACTERISTICS OF ZERO) OR CLASS 1 | | (FLAME SPREAD INDEX <25 AND SMOKE | | DEVELOPED INDEX <50).THIS ISSUE MUST | | BE RESOLVED PRIOR TO INSTALLATION OF ANY | | DUCT. | | | | NON-METALIC DUCT SHALL COMPLY WITH | | 2004 FMC 603.4, DUCTS SHALL BE | | CONSTRUCTED WITH CLASS 0 OR CLASS 1 DUCT | | MATERIAL IN ACCORDANCE WITH UL 181. | | | | PLEASE NOTE, FABRIC DUCT SUBMITTED | | (PRIHODA) HAS NO UL LISTING. THE TEST | | REPORT PAGE 3 UNDER "LIMITATIONS" THERE | | IS A WARNING WHICH STATES THE FOLLOWING; | | "THIS DOCUMENT DOES NOT REPRESENT TYPE | | APPROVAL OR CERTIFICATION OF THE | | PRODUCT." | | | | | | ADDITIONAL PERMIT REQUIRED FOR THE SPRAY | | PAINT BOOTH.PLANS AND MANUFACTURER | | SUBMITTAL DATA ON FILE WITH BUILDING | | PLANS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | E-MAIL [email protected]. |
|