Plan Review Notes For Permit 06010452 |
Permit Number |
06010452 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-04-03 00:00:00 | NEED TO EXPLAIN WHAT TYPE OF BUSINESS IS | | GOING TO RUN OUT OF THIS BAY? | | | | FROM THE DRAWINGS IT LOOKS LIKE | | AUTOMOTIVE REPAIR!!IF SO PLEASE | | APPLY THE REQUIREMENTS FROM ARTICLE 511 | | FROM THE NEC. | | | | BUILDING TO MEET THE REQUIREMENTS OF | | CHAPTER 13 OF THE FL BLDG. CODE FOR | | LIGHTING ,A/C AND EQUIPMENT. | | | | MAINS TO BE GROUPED PLEASE SHOW LOCATION | | 230.72 | | | | FOUR OF THE LIGHTING FIXTURE ARE THROUGH | | A WALL ??? SEE PAGE E1.1 | | | | NEED LOAD CALCULATIONS PER THE NEC | | 215.5, 220. | | | | NOTE 20 NEEDS TO BE CHANGED. | | | | |
|