Date Text
2006-05-14 00:00:00PLANS REDLINED,
  
 SD'S ARE BEING SHOWN ON CIRCUIT A-2, IF
 ON THIS CIRCUIT THEN AFCI PROTECTION
 WILL BE REQUIRED.2002 210.12B
 PANEL SCHEDULE DOES NOT INDICATE AFCI
 PROTECTION FOR A-2
 ** THE SD'S SHOULD BE ON ONE OF THE
 BEDRM CIRCUITS, MAY REVISE LATER.
 PLANS STAMPED AND PASSED.