Plan Review Notes For Permit 06010448 |
Permit Number |
06010448 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-03-20 00:00:00 | *** DENIED ** | | 1) ENERGY CALCULATIONS ARE CALLING FOR | | 22,600 TOTAL BTU'S. MECHANICAL PLANS ARE | | CALLING FOR 2 1/2 TON A/C SYSTEM | | ESTIMATED 30,000 TOTAL BTU'S. THE PLANS | | CAN NOT CALL FOR MORE BTU'S. THAN THAN | | THE ENERGY CAL'S. | | | | 2) PLEASE SHOW THE TOTAL BTU'S. ON THE | | MECHANICAL PLANS. | | | | 3) PLEASE SHOW THE COPPER LINE SIZES ON | | THE MECHANICAL PLANS. | | | | 4) PLEAS SHOW THE LOCATION OF THE | | CONDENSATE DRAIN LINE ON THE MECHANICAL | | PLANS. | | | | 5) PLEASE SHOW THE LOCATION OF THE | | CONDENSER UNIT ON THE MECH. PLANS. | | | | 6) PLEASE SHOW THE CLOTHES DRIER VENT | | LOCATION ON THE MECH. PLANS. | | | | 7) PLEASE SHOW THE SIZE OF THE SUPPLY | | AIR DUCT (FLEX) FROM THE AHU TO THE | | MIXING BOX IN THE LIVING ROOM. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|