Plan Review Notes
Plan Review Notes For Permit 06010448
Permit Number 06010448
Review Stop M
Sequence Number 2
Notes
Date Text
2006-03-20 00:00:00*** DENIED **
 1) ENERGY CALCULATIONS ARE CALLING FOR
 22,600 TOTAL BTU'S. MECHANICAL PLANS ARE
 CALLING FOR 2 1/2 TON A/C SYSTEM
 ESTIMATED 30,000 TOTAL BTU'S. THE PLANS
 CAN NOT CALL FOR MORE BTU'S. THAN THAN
 THE ENERGY CAL'S.
  
 2) PLEASE SHOW THE TOTAL BTU'S. ON THE
 MECHANICAL PLANS.
  
 3) PLEASE SHOW THE COPPER LINE SIZES ON
 THE MECHANICAL PLANS.
  
 4) PLEAS SHOW THE LOCATION OF THE
 CONDENSATE DRAIN LINE ON THE MECHANICAL
 PLANS.
  
 5) PLEASE SHOW THE LOCATION OF THE
 CONDENSER UNIT ON THE MECH. PLANS.
  
 6) PLEASE SHOW THE CLOTHES DRIER VENT
 LOCATION ON THE MECH. PLANS.
  
 7) PLEASE SHOW THE SIZE OF THE SUPPLY
 AIR DUCT (FLEX) FROM THE AHU TO THE
 MIXING BOX IN THE LIVING ROOM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.