Plan Review Notes
Plan Review Notes For Permit 06010445
Permit Number 06010445
Review Stop P
Sequence Number 1
Notes
Date Text
2006-01-19 00:00:00DENIED;
 1.W/M DRAIN TO BE 3" PER FBC-2004
 PLUMBING SEC. 406.3.
 2.WATER RISER DIAGRAM; BUILDING SHUTOFF
 REQUIRED PLEASE SHOW. PLEASE SHOW
 WATERHAMMER ARRESTORS ON KIT. SINK.
 3.REMOVE NOTE 26 FROM PLUMBING
 SPECIFCATIONS. HOOKING IRRIGATION PUMP
 TO DOMESTIC WOULD COUSE A CROSS
 CONNECTION.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695