Plan Review Notes
Plan Review Notes For Permit 06010445
Permit Number 06010445
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-01 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 NEED PAID RECEIPT AND STAMPED DRAWINGS.
  
 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY
 SEC. R401.3 OF 2004 RESIDENTIAL CODE.
  
 3- PROVIDE STRUCTURAL BUCK DETAIL USING
 2X BUCK AS REQUIRED BY ENTRY DOORS
 PRODUCT APPROVAL SUBMITTED. SEE SEC.
 R613.6.2 OF 2004 RESIDENTIAL CODE.
  
 4- OWES $374.36 FOR UPDATED BUILDING
 VALUATION AND RADON FEES.
  
 5- PROVIDE SPECS/SECTION/DETAIL FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SECTION 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 6- DRAWINGS S-2 & S3 ARE MISSING THE
 ENGINEER INFO. CHAPTER 471 FL. ST.
  
 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR DOOR AND TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS FOR
 SLIDING GLASS DOORS AT FAMILY RM &
 FRENCH DOORS AT MASTER BEDROOM.
 OTHERWISE, PROVIDE COMPLETE INFORMATION
 FOR STRUCTURAL MULLIONAS REQUIRED BY
 SEC. R613.7 OF 2004 RESIDENTIAL CODE.
 B) SPECIFY SIZE OF FIXED WINDOW.
  
 8- ARCHITECT TO PROVIDE FIRM LICENSE
 NUMBER AS REQ'D BY CHAPTER 481 FLORIDA
 STATUTES & FLORIDA ADMINISTRATIVE CODE.
  
 9- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQ'D BY RULE 9B-72 FOR:
 A) FRENCH DOORS W/ TRANSOM ABOVE.
 SEE ITEM #7 ABOVE.
 B) SLIDING GLASS DOORS WITH TRANSOM
 ABOVE. SE ITEM #7 ABOVE.
 C) STRUCTURAL MULLIONS. SEE ITEM #7
 D) FIXED WINDOWS. SEE ITEM #7 ABOVE.
 E) ALL TRUSS CONNECTORS. SEE PLANS.
 F) SINGLE HUNG WINDOWS: FLORIDA
 PRODUCT APPROVAL AND DADE COUNTY NOA
 SUBMITTED DON'T MATCH. NEED TO PROVIDE
 THE EXACT SAME INFORMATION THAT WAS
 PROVIDED TO OBTAIN FLORIDA APPROVAL.
 INFORMATION SUBMITTED ARE FOR 2
 DIFFERENT MODEL TYPES. FL 3041 ISFOR
 MODEL TR-9100. DADE COUNTY NOA SUBMITTED
 IS FOR SERIES 2100 WINDOWS.
 G) ROOF SHINGLES. NEED TO PROVIDE THE
 EXACT SAME DADE COUNTY NOA THAT WAS
 SUBMITTED FOR FLORIDA APPROVAL. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 CORRECT NOA.
 H) PRECAST LINTELS.
 I) ALUMINUM VENTS.
 J) ALUMINUM SIDING.
  
 10- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 OF
 CITY AMENDMENTS TO FBC 2004.
  
 11- ARCHITECTURAL DRAWING 1: UPDATE
 BUILDING CODE DATA INFORMATION. SEE 2004
 RESIDENTIAL BUILDING CODE.
  
 12- DRAWING A-1: A) PROVIDE COMPLETE
 DETAILS/SPECS FOR WOOD DECK OUTSIDE
 MASTER BEDROOM AND FOR WOOD STEPS AT
 REAR COVERED PORCH. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 B) SPECIFY SAFETY GLASS FOR WINDOW IN
 BATHROOM LOCATED BETWEEN BEDROOM #1 AND
 #2. SEC. R308.4 2004 RESIDENTIAL CODE.
 C) UPDATE CODE REFERENCE FOR ATTIC
 ACCES. SEE 2004 RESIDENTIAL CODE.
 D) UPDATE CODE REFERENCES SPECIFIED
 ON GENERAL NOTES AND SCHEDULE NOTES. SEE
 2004 RESIDENTIAL CODE. SEE PLANS.
  
 13- DRAWING A-2: A) DESIGN PRESSURES
 MARK DOESN'T MATCH MARK SHOWED ON DOORS
 AND WINDOWS OPENINGS. REVISE AS REQ'D.
 B) SPECIFY SIZE FOR MANUFACTURED
 ALUMINUM LOUVER AT FRONT AND BACK
 ELEVATIONS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 14- DRAWING A-3: A) WHERE IS DETAIL A-5?
 SEE COMMENTS IN PLANS ON SECTIONS A & B.
 B) SECTION "A": 1)PORCH SECTION CALLS
 FOR POURED CONCRETE ARCH. THERE IS NOT
 ARCH ON FRONT PORCH. REVISE AS REQUIRED.
 2) WHERE IS DETAIL SHT 5 SPECIFIED
 FOR WOOD COLUMN?
 3) SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AT CONCEALED SPACES IN SOFFITS
 AND WALLS. SEC. R602.8 2004 RESIDENTIAL
 CODE. SEE COMMENTS IN PLANS.
  
 15- DRAWING A-4: A) WALL SECTION "A".
 UPDATE CODE REFERENCE SPECIFIED FOR
 FIREBLOCKING AND SPECIFY FIREBLOCKING
 MATERIAL. SEE 2004 RESIDENTIAL CODE.
 B) WALL SECTION "B". FOUNDATION
 DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 C) REVISE PORCH BEAM TO MATCH ELEVATION.
 IT IS NOT AN ARCHED BEAM.
  
 16- DRAWING S-1: A) ROOF FRAMING PLAN
 CALLS FOR CONNECTOR A3 BY REAR PORCH.
 THERE IS NOT CONNECTOR A3. SEE TRUSS
 ANCHOR SCHEDULE. REVISE AS REQUIRED.
 B) WHERE ARE DETAILS A, C AND E KEYED
 ON ROOF PLAN?. ALSO, WHERE IS DET SHT
 S-2.MAKE SURE ALL KEYED DETAIL AND
 PAGE MATCH SPECIFIC DETAIL AND PAGE. SEE
 COMMENTS ON PLAN.
  
 17- DRAWING S-2: A) TYP. 1 STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. R806 2004 RESIDENTIAL CODE.
 B) DETAIL D: 1)HOW IS 2"X6" SILL PLATE
 ATTACHED TO CONCRETE BEAM?.
 2) HOW IS 2"X6" "L" BRACE NAILED TO
 BOTTOM SILL?
 3) USP RT24 IS A WOOD TO WOOD
 CONNECTOR. NEED A WOOD TO MASONRY
 CONNECTOR TO ATTACH TO CONCRETE BEAM.
  
 18- DRAWING S-3: A) GENERAL NOTES.
 UPDATE ALL REFERENCE STANDARDS. SEE 2004
 RESIDENTIAL CODE & 2004 FBC FOR
 CORRESPONDING STANDARDS AND SPECIFIC
 EDITION. EG: ACI 318-02. SEE PLANS.
 B) UPDATE CODE SECTIONS REFERENCED
 FOR WIND LOADS, EMERGENCY EGRESS AND
 GLASS IMPACT PROTECTION. SEE PLANS.
 C) VENTILATION AND EGRESS ARE TWO
 DIFFERENT CODE ISSUES. CLEAR OPENING FOR
 EGRESS HAS NOTHING TO DO WITH CLEAR
 OPENING FOR VENTILATION. REVISE NOTE.
 D) TRUSS ANCHOR SCHEDULE: NUMBER OF
 NAILS AND UPLIFT LOADS SPECIFIED TO
 MATCH THOSE PUBLISHED BY THE
 MANUFACTURER IN RECENT CATALOGUE. IF
 DIFFERENT NUMBER AND UPLIFT CALCS ARE
 SPECIFIED, THEN PROVIDE COMPLETE
 ENGINEERING CALCULATIONS TO SHOW WHY
 NUMBER AND UPLIFT LOADS ARE CHANGED.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 E) DELETE ADDITION TO STRUCTURE NOTES.
 THIS IS NEW CONSTRUCTION AND THEY DON'T
 APPLY TO THIS JOB.
  
 19- SURVEY TO HAVE SURVEYOR'S ORIGINAL
 SIGNATURE, NOT COPY, AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES.
  
 20- STORM SHUTTERS:
 A) PROVIDE KEY PLAN.
 B) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE THAT
 COVERS ALL REQUIRED INFORMATION TO
 PERFORM BUILDING REVIEW AND PRODUCT
 COMPLIANCE WITH PROPOSED INSTALLATION.
  
 21- ENERGY CALCULATIONS: A) NEED ENERGY
 CALCULATIONS USING FORM 600A-2004.
 B) CONDITIONED FLOOR AREA DOENS'T
 MATCH AREA SHOWN ON PLANS. REVISE.
 C) BUILDING ORIENTATION, OVERHANG
 LENGTH, OVERHANG HEIGHT AND AREA DON;'T
 MATCH PLANS. SEE CHAPTER 13 OF FBC 2004
 FOR PROPER WAY OF CALCULATING THESE
 ITEMS. REVISE AS REQUIRED.
 D) OWNER TO DATE BOTTOM OF FORM.
  
 ***NOTE: PLEASE RETURN REVIEWED SET TO
 EXPEDITE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER