2006-06-28 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK COPY OF PAID RECEIPT AND
 STAMPED PLANS.
  
 2- NOC IS EXPIRED AFTER 90 DAYS OF BEEN
 RECORDED IF WORK IS NOT COMMENCED. NEED
 RE-RECORDED NOC. SEE SEC. 713.13. 9(2)
 OF FLORIDA STATUTES.
  
 3- PROVIDE SPECS/SECTION/DETAILS FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 4- PROVIDE PRODUCT APPROVAL FOR:
 A) SINGLE HUNG WINDOWS. DADE COUNTY NOA
 SUBMITTED IS EXPIRED AND IT DOESN'T
 MATCH THE NOA SUBMITTED TO OBTAIN THE
 FLORIDA PRODUCT APPROVAL. RESUBMIT. GO
 TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 CORRECT NOA.
 B) CONCRETE LINTELS. DADE COUNTY NOA
 SUBMITTED IS FOR 4", 6" & 12" LINTELS.
 NEED NOA FOR 8"X8" LINTELS AS SPECIFIED
 ON PLANS.
 ***NOTE: NOA FOR 8"X8" LINTELS IS
 EXPIRED. NEED TO PROVIDE CURRENT ONE.
 C) ALUMINUM SIDING. PRODUCT APPROVAL
 SUBMITTED IS FOR CEMENTITIOUS SIDING
 PRODUCTS, NOT ALUMINUM AS SPECIFIED ON
 PLANS. NEED SPECIFIED PRODUCT APPROVAL.
 D) ALL SIMPSON STRUCTURAL CONNECTORS
 AS SPECIFIED ON PLANS. PRODUCT APPROVALS
 SUBMITTED ARE FOR USP AND ONLY ONE WAS
 GOOD FOR THE USP HLPTA75 CONNECTOR. THE
 REST OF THE PRODUCT APPROVALS SUBMITTED
 WERE NOT SPECIFIED ON PLANS.
 E) ALUMINUM VENTS SHOWN ON ELEVATIONS.
 F) ASPHALT SHINGLES NOA THAT MATCHES
 NOA SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL. GO TO WWW.FLORIDABUILDING.ORG
 TO DOWNLOAD CORRECT NOA.
  
 5- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS, INCLUDING THE STORM SHUTTERS
 AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC.
 TYPICALLY THIS IS DONE USING THE
 STANDARD REVIEW STAMP USED FOR SHOP
 DRAWINGS REVIEW.
  
 6- STORM SHUTTERS:
 A) PRODUCT APPROVAL SUBMITTED IS
 INCOMPLETE. IT DIDN'T INCLUDE THE DWGS.
 B) INSTALLATION SCHEDULE:
 * WHY THE DESIGN PRESSURES ARE N/A?.
 THIS IS THE MOST IMPORTANT INFORMATION
 TO VERIFY COMPLIANCE OF PRODUCT BASED ON
 THE CALCULATED DESIGN PRESSURES. NEED
 THIS INFORMATION. SEE PLANS.
 C) VERIFY SIZES FOR PANEL SPAN. EG:
 OPENINGS 8 AND 9. IF THE OPENINGS ARE
 5'X6'-8" HOW COME THE PANEL SPAN IS
 88"?. ALSO, THIS APPLIES TO 4' HIGH
 OPENINGS. WHY USING 68" LONG PANELS?.
 D) VERIFY STRUCTURE TO BE ATTACHED TO.
 THIS IS A CONCRETE BLOCK STRUCTURE, NOT
 POURED CONCRETE. REVISE AS REQUIRED.
  
 7- DRAWING A-1: UPDATE CODE REFERENCE
 SPECIFIED FOR ATTIC ACCESS, FIREBLOCKING
 AND WINDOW/DOOR GLAZING PROTECTION. THIS
 IS A RESIDENCE THE CORRECT CODE THAT
 REGULATES DWELLINGS IS THE RESIDENTIAL
 2004 CODE, NOT THE FBC 2004. REVISE AS
 REQ'D AND CITE CORRECT CODE REFERENCE
 SECTIONS FROM THE RESIDENTIAL CODE.
  
 8- REVISE SURVEY. PROPERTY IS LOCATED IN
 FLOOD ZONE "C". NOT "B". CITY OF WPB
 USES COMMUNITY PANEL 120229 0015 B,
 DATED MARCH 1ST 1979.
  
 9- DRAWING A-2: A) BEDROOM #1 WINDOW
 DOESN'T COMPLY WITH EGRESS SECTIONS
 R310.1.1 AND R310.1.2.BOTH WINDOWS IN
 FRONT ELEVATION ARE SHOWN AS 3'X4'
 WINDOWS. ACCORDING TO FLOOR PLAN WINDOW
 IS 3'X5'. CLARIFY/REVISE AS REQUIRED.
 B) WHAT ARE THE LETTERS IDENTIFYING THE
 OPENINGS FOR? THEY DON'T MATCH FLOOR
 PLAN AND THERE IS NOT LEGEND IDENTIFYING
 THIS LETTERS. CLARIFY AS REQUIRED.
 C) SPECIFY SIZE FOR MANUFACTURED
 ALUMINUM LOUVERS AT FRONT AND BACK
 ELEVATIONS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004 AND SECTION R806.
  
 10- DRAWING A-3: SECTION "A", WHERE IS
 DETAIL SHT 5?
  
 11- DRAWING A-4: WALL SECTION "A".
 SPECIFY FIREBLOCKING MATERIAL AND
 REVISE REFERENCE FOR FIREBLOCKING. SEE
 RESIDENTIAL 2004 FOR CORRECT CODE
 SECTION.
  
 12- DRAWING S-1: A) PROVIDE DETAIL/SPECS
 FOR 4"X4" WOOD POST AT REAR WOOD DECK.
 NEED TO SPECIFY ATTACHMENT OF WOOD POST
 TO FOOTING. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
 B) SPECIFY TRUSS CONNECTORS ON ROOF
 FRAMING PLAN. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 13- DRAWING S-2: A) TYP. ONE STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. PROVIDE SPECIFIC
 INFORMATION. SECTION R806 2004.
 B) DETAIL H: USP RT24 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
  
 14- DRAWING S-3: A) REVISE TRUSS ANCHOR
 SCHEDULE. UPLIFT CAPACITY DOESN'T MATCH
 UPLIFT CAPACITY SHOWN ON CURRENT USP
 CATALOGUE. REVISE AS REQUIRED OR PROVIDE
 COMPLETE ENGINEERING PACKAGE SHOWING WHY
 CHANGING THE VALUES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 15- ENERGY CALCULATIONS:
 A) IF THIS IS A MODEL HOUSE. ENERGY
 CALCULATIONS NEED TO BE DONE FOR WORST
 CASE SCENARIO OR MUST BE SITE SPECIFIC
 WITH CORRECT HOUSE ORIENTATION.
 CALCULATIONS SUBMITTED ARE NOT FOR WORST
 CASE SCENARIO.
 B) OVERHANG LENGTH AND HEIGHT DON'T
 MATCH PLANS. SEE SECTION 13-601.2.A.3
 FOR PROPER WAY OF CALCULATING OVERHANG
 LENGTH AND HEIGHT. AND REVISE AS
 REQUIRED.
  
 16- ARCHITECT'S TITLE BLOCK TO INCLUDE
 ALL INFORMATION REQUIRED BY CHAPTER 481
 FLORIDA STATUTES AND 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. SEE
 ATTACHED COPY.NEED NAME OF ARCHITECT
 SIGNING AND SEALING PLANS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712