2006-03-10 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- PAY IMPACT FEES TO PALM BEACH COUNTY. |
| BRING BACK STAMPED DRAWINGS AND PAID |
| RECEIPT. |
| |
| 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY |
| SEC. R401.3 OF 2004 RESIDENTIAL CODE. |
| |
| 3- PROVIDE STRUCTURAL BUCK DETAIL USING |
| 2X BUCK AS REQUIRED BY ENTRY DOOR |
| PRODUCT APPROVAL SUBMITTED. SEE SECTION |
| R613.6.2 2004 RESIDENTIAL CODE FOR |
| PROPER BUCK INSTALLATION. |
| |
| 4- OWES $291.47 FOR UPDATED VALUATION |
| AND RADON FEES. |
| |
| 5- PROVIDE SPECS/DETAILS FOR |
| INSTALLATION OF DECORATIVE STORM |
| SHUTTERS. SEC. 106.1.2 CITY AMENDMENTS |
| TO FBC 2004. |
| |
| 6- DRAWINGS S-1, S-2 AND S-3 ARE MISSING |
| THE ENGINEER'S INFORMATION AS REQUIRED |
| BY CHAPTER 471 FLORIDA STATUTES. |
| |
| 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR FRENCH DOORS WITH TRANSOM |
| ABOVE SINGLE UNIT AS SHOWN ON PLANS OR |
| PROVIDE COMPLETE INFORMATION FOR |
| STRUCTURAL MULLION AS REQUIRED BY SEC. |
| R613.7 2004 RESIDENTIAL CODE. |
| B) SPECIFY SIZE OF FIXED WINDOW. |
| |
| 8- ARCHITECT TO PROVIDE ALLINFORMATION |
| ON TITLE BLOCK AS REQUIRED BY CHAPTER |
| 481 FLORIDA STATUTES AND 61G1-16.004 OF |
| ADMINISTRATIVE CODE. SEE ATTACHED COPY. |
| |
| 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL AS REQUIRED BY RULE 9B-72 FOR: |
| A) FRENCH DOORS WITH TRANSOM ABOVE. |
| OR FRENCH DOORS ALONE. SEE ITEM #7 ABOVE |
| B) STRUCTURAL MULLIONS. SEE ITEM #7. |
| C) FIXED WINDOWS. SEE ITEM #7 ABOVE. |
| D) ALL TRUSS CONNECTORS. SEE PLANS. |
| E) SINGLE HUNG WINDOWS. DADE COUNTY |
| NOA TO MATCH NOA SUBMITTED FOR FLORIDA |
| APPROVAL. VISIT WWW.FLORIDABUILDING.ORG |
| TO DOWNLOAD CORRESPONDING NOA. |
| F) ROOF SHINGLES. PROVIDE SAME NOA |
| SUBMITTED FOR FLORIDA PRODUCT APPROVAL. |
| G) PRECAST LINTELS. |
| H) ALUMINUM VENTS. |
| I) ALUMINUM SIDING. |
| |
| 10- DESIGNER OF RECORD TO REVIEW AND |
| APPROVE IN WRITTING ALL PRODUCT |
| APPROVALS PRIOR TO SUBMITTAL TO THIS |
| OFFICE AS REQUIRED BY SEC. 106.3.3 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 11- DRAWING 1: UPDATE BUILDING CODE |
| DATA. SEE 2004 RESIDENTIAL CODE. |
| |
| 12- DRAWING A-1: A) SPECIFY SAFETY GLASS |
| FOR WINDOW IN BATHROOM. SEE PLANS. SEC. |
| R308.4 2004 RESIDENTIAL CODE. |
| B) UPDATE CODE REFERENCE FOR ATTIC |
| ACCESS. SEE 2004 RESIDENTIAL CODE. |
| C) UPDATE CODE REFERENCES SPECIFIED |
| ON GENERAL NOTES AND SCHEDULE NOTES. SEE |
| 2004 RESIDENTIAL CODE. |
| |
| 13- DRAWING A-2: SPECIFY SIZE OF |
| MANUFACTURED ALUMINUM LOUVER AT FRONT |
| AND BACK. SEC. 106.1.2 CITY AMENDMENTS |
| TO FBC 2004. |
| |
| 14- DRAWING A-3: A) WHERE IS DETAIL A-5" |
| SPECIFIED ON PLANS? |
| B) SECTION "A": 1) WHERE IS DETAIL |
| SHT 5? |
| 2) WHERE IS DETAIL SHT 5 FOR WOOD |
| COLUMN SURROUND? |
| 3) WHERE IS THE CONCRETE SIDEWALK?. |
| SEE SITE PLAN. |
| |
| 15- DRAWING A-4: A) WALL SECTION "A". |
| UPDATE CODE REFERENCE SPECIFIED FOR |
| FIREBLOCKING AND SPECIFY FIREBLOCKING |
| MATERIAL. SEE 2004 RESIDENTIAL CODE. |
| B) WALL SECTION "B". FOUNDATION PLAN |
| DOESN'T MATCH PLANS. REVISE AS REQUIRED. |
| C) PORCH BEAM IS NOT AN ARCHED BEAM. |
| REVISE AS REQUIRED. SEE PLANS. |
| |
| 16- DRAWING S-1: A) PROVIDE COMPLETE |
| DETAILS AND SPECS FOR WOOD DECK AND WOOD |
| STEPS AT REAR AREA. SPECIFY ALL |
| FASTENERS. SEC. 106.1.2 CITY AMENDMENTS |
| TO FBC 2004. |
| B) SPECIFY ROOF TRUSS CONNECTORS. |
| C) WHERE ARE DETAILS C AND E? |
| KEY DETAILS TO MATCH DRAWINGS. |
| |
| 17- DRAWING S-2: A) TYP. 1 STORY |
| SECTION: SPECIFY SIZE AND LOCATION OF |
| ATTIC VENTS. ALSO, CONSIDER ALUMINUM |
| VENTS FOR TOTAL VENTING AREA REQUIRED. |
| SEC. R806 2004 RESIDENTIAL CODE. |
| B) DETAIL D: 1) HOW IS 2"X6" SILL |
| PLATE ATTACHED TO CONCRETE BEAM? |
| 2) HOW IS 2" X 6" "L" BRACE NAILED TO |
| BOTTOM SILL? |
| 3) USP RT24 IS SHOWN AS BEING |
| ATTACHED TO CONCRETE BEAM. SEE USP |
| CATALOGUE FOR PROPER INSTALLATION, SIZE |
| AND FASTENERS. REVISE AS REQUIRED. |
| 4) DETAIL A: SHOW COMPLETE DETAILS |
| AND SPECS FOR CONCRETE STEPS AT ENTRY |
| PORCH. |
| |
| 18- DRAWING S-3: A) GENERAL NOTES: |
| UPDATE ALL REFERENCE STANDARDS AND |
| SPECIFIC EDITION TO BE USED. SEE 2004 |
| RESIDENTIAL CODE AND 2004 FBC CHAPTER |
| 35. |
| B) UPDATE CODE SECTIONS REFERENCED |
| FOR WIND LOADS, EMERGENCY EGRESS AND |
| GLASS IMPACT PROTECTION NOTES. |
| C) VENTILATION AND EGRESS ARE TWO |
| DIFFERENT CODE ISSUES.REVISE AS REQ'D. |
| D) TRUSS ANCHOR SCHEDULE: NUMBER OF |
| NAILS AND UPLIFT LOADS TO MATCH CURRENT |
| USP CATALOGUE. OTHERWISE, PROVIDE |
| COMPLETE ENGINEERING ANALYSIS FOR NUMBER |
| AND UPLIFT LOADS THAT DIFFER THOSE |
| PUBLISHED BY MANUFACTURER. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| E) DELETE NOTES CORRESPONDING TO |
| STRUCTURE ADDITIONS. THEY DON'T APPLY TO |
| THIS PROJECT. |
| |
| 19- A) SURVEY TO HAVE SURVEYOR'S |
| ORIGINAL SIGNATURE, NOT COPY, AS |
| REQUIRED BY CHAPTER 472 FLORIDA |
| STATUTES. |
| B) PROPERTY IS LOCATED ON FLOOD ZONE |
| C, NOT B. REVISE AS REQUIRED. COMMUNITY |
| PANEL 120229 0015 B, MARCH 1ST 1979. |
| |
| 20- STORM SHUTTERS: |
| A) PROVIDE KEY PLAN. |
| B) PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED SAMPLE. PROVIDE |
| ALL INFORMATION. |
| |
| 21- ENERGY CALCULATIONS: |
| A) USE 2004 FORM, NOT 2001. |
| B) OWNER/AGENT TO SIGN BOTTOM OF FORM |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |