2006-03-01 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- PAY IMPACT FEES TO PALM BEACH COUNTY. |
| NEED PAID RECEIPT & STAMPED DRAWINGS. |
| |
| 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY |
| SEC. R401.3 2004 RESIDENTIAL CODE. |
| |
| 3- PROVIDE STRUCTURAL BUCK DETAIL USING |
| 2X BUCK AS REQUIRED BY ENTRY DOORS |
| PRODUCT APPROVAL SUBMITTED. ALSO, SEE |
| SEC. R613.6.2 OF 2004 RESIDENTIAL CODE |
| FOR PROPER BUCK INSTALLATION. |
| |
| 4- OWES $296.42 FOR UPDATED BUILDING |
| VALUATION AND RADON FEES. |
| |
| 5- PROVIDE SPECS/SECTION/DETAILS FOR |
| DECORATIVE STORM SHUTTERS INSTALLATION. |
| SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| |
| 6- DRAWINGS S-1, S-2 AND S-3 ARE MISSING |
| THE ENGINEER'S INFO. CHAPTER 471 FL. ST. |
| |
| 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR FRENCH DOOR WITH TRANSOM |
| ABOVE SINGLE ASSEMBLY UNIT AS SHOWN ON |
| PLANS IN REAR ELEVATION. OTHERWISE, |
| PROVIDE COMPLETE INFORMATION FOR |
| STRUCTURAL MULLION AS REQ'D BY SEC. |
| R613.7 2004 RESIDENTIAL CODE. |
| B) SPECIFY SIZE OF FIXED WINDOW. |
| |
| 8- ARCHITECT TO PROVIDE FIRM LICENSE |
| NUMBER AS REQ'D BY CHAPTER 481 FL. ST. |
| AND FLORIDA ADMINISTRATIVE CODE. |
| |
| 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL AS REQUIRED BY RULE 9B-72 FOR: |
| A) FRENCH DOORS WITH W/ TRANSOM |
| ABOVE. SEE ITEM #7 ABOVE. |
| B) STRUCTURAL MULLIONS. SEE ITEM #7. |
| C) FIXED WINDOWS. |
| D) ALL TRUSS CONNECTORS. SEE PLANS. |
| E) SINGLE HUNG WINDOWS. PROVIDE SAME |
| DADE COUNTY NOA THAT WAS SUBMITTED FOR |
| FLORIDA PRODUCT APPROVAL. |
| F) ROOF SHINGLES. PROVIDE SAME DADE |
| COUNTY NOA THAT WAS SUBMITTED FOR |
| FLORIDA PRODUCT APPROVAL. |
| G) PRECAST LINTELS. |
| H) ALUMINUM VENTS. |
| I) ALUMINUM SIDING. |
| |
| 10- DESIGNER OF RECORD TO REVIEW AND |
| APPROVE IN WRITTING ALL PRODUCT |
| APPROVALS PRIOR TO SUBMITTAL TO THIS |
| OFFICE AS REQUIRED BY SEC. 106.3.3 OF |
| CITY AMENDMENTS TO FBC 2004. |
| |
| 11- ARCHITECTURAL DRAWING A-1: UPDATE |
| BUILDING CODE DATA INFORMATION. SEE 2004 |
| RESIDENTIAL CODE. |
| |
| 12- DRAWING A-1: A) SPECIFY SAFETY GLASS |
| FOR BATHROOM WINDOW. SEE PLANS. SEC. |
| R308.4 2004 RESIDENTIAL CODE. |
| B) UPDATE CODE REFERENCE FOR ATTIC |
| ACCES. SEE 2004 RESIDENTIAL CODE. |
| C) UPDATE CODE REFERENCES SPECIFIED |
| ON GENERAL NOTES AND SCHEDULE NOTES. SEE |
| 2004 RESIDENTIAL CODE. |
| |
| 13- DRAWING A-2; A) DESIGN PRESSURES |
| MARK DOESN'T MATCH MARK SHOWED ON DOORS |
| AND WINDOWS. OPENINGS. REVISE AS REQ'D. |
| B) SPECIFY SIZE FOR MANUFACTURED |
| ALUMINUM LOUVER AT FRONT AND BACK. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 14- DRAWING A-3: A) WHERE IS DETAIL A-5? |
| SEE COMMENTS ON PLANS. |
| B) SECTION "A": 1) CALLS FOR ALUMINUM |
| SIDING. FRONT ELEVATION SHOWS STUCCO. |
| REVISE AS REQUIRED. |
| 2) WHERE IS DETAIL SH 5 SPECIFIED FOR |
| WOOD COLUMN SURROUND? |
| |
| 15- DRAWING A-4: A) WALL SECTION "A": |
| UPDATE CODE REFERENCE FOR FIREBLOCKING |
| AND SPECIFY FIREBLOCKING MATERIAL. SEE |
| 2004 RESIDENTIAL CODE. |
| B) WALL SECTION "B": 1) FOUNDATION |
| DOESN'T MATCH PLANS. REVISE AS REQUIRED. |
| 2) CLARIFY IF USING ALUMINUM SIDING OR |
| STUCCO. SEE FRONT ELEVATION. |
| 3) SPECIFY NAILING SPACING FOR 5/8" |
| PLYWOOD SHOWN ON PORCH CEILING. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 16- DRAWING S-1: A) FOUNDATION PLAN: |
| 1) SPECIFY SIZE OF CONTINUOUS FOOTING |
| AT FRONT PORCH. SEE PLANS. |
| 2) SPECIFY SIZE OF PRECAST CONCRETE |
| PAD AT REAR PORCH. SEE PLANS. |
| 3) WHERE IS DETAIL A ON SHEET S-2? |
| |
| B) ROOF FRAMING PLAN: 1) SPECIFY |
| TRUSS CONNECTORS. |
| 2) WHERE IS DETAIL 2 SHEET S-2, |
| DETAIL E SHEET S-2 AND DETAIL C SHEET |
| S-2?. SEE PLANS. |
| |
| 17- DRAWING S-2: A) TYP. 1 STORY |
| SECTION: SPECIFY SIZE AND LOCATION OF |
| ATTIC VENTS. R806 2004 RESIDENTIAL CODE |
| B) DETAIL D: 1) HOW IS 2"X6" SILL |
| PLATE ATTACHED TO CONCRETE BEAM? |
| 2) HOW IS 2"X6" "L" BRACE NAILED TO |
| BOTTOM SILL? |
| 3) CLARIFY INSTALLATION OF USP TA18. |
| IT'S SHOWN AS NAILED TO CONCRETE BEAM |
| INSTEAD OF BEING EMBEDED IN CONCRETE |
| BEAM. SEE USP CATALOGUE FOR PROPER |
| INSTALLATION. REVISE AS REQ'D |
| C) DETAIL A. PORCH FOOTING TO SHOW |
| CONCRETE STEPS AND DETAILS TO MATCH |
| SECTION "A" ON DRAWING A-3. |
| |
| 18- DRAWING S-3: A) GENERAL NOTES. |
| UPDATE ALL REFERENCE STANDARDS. SEE 2004 |
| RESIDENTIAL CODE AND 2004 FBC 2004 FOR |
| ADOPTED STANDARDS AND SPECIFIC EDITION. |
| B) UPDATE CODE SECTIONS REFERENCED |
| FOR WIND LOADS, EMERGENCY EGRESS AND |
| GLASS IMPACT PROTECTION. SEE PLANS. |
| C) VENTILATION AND EGRESS ARE 2 |
| DIFFERENT CODE ISSUES. CLEAR OPENING FOR |
| EGRESS HAS NOTHING TO DO WITH CLEAR |
| OPENING FOR VENTILATION. REVISE NOTE. |
| D) TRUSS ANCHOR SCHEDULE: NUMBER OF |
| NAILS AND UPLIFT LOADS SPECIFIED TO |
| MATCH USP CURRENT CATALOGUE. OTHERWISE, |
| PROVIDE COMPLETE ENGINEERING CALCS FOR |
| SIZE AND NUMBER OF NAILS THAT ARE |
| DIFFERENT THAN THOSE PUBLISHED BY THE |
| MANUFACTURER. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| E) ADDITION TO STRUCTURE NOTES DON'T |
| APPLY TO THIS JOB. |
| |
| 19- SURVEY TO HAVE SURVEYOR'S ORIGINAL |
| SIGNATURE, NOT COPY, AS REQUIRED BY |
| CHAPTER 472 FLORIDA STATUTES. |
| |
| 20- STORM SHUTTERS: |
| A) PROVIDE KEY PLAN. |
| B) PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED SAMPLE THAT |
| COVERS ALL REQUIRED INFORMATION TO |
| PERFORM BUILDING REVIEW AND PRODUCT |
| COMPLIANCE WITH PROPOSED INSTALLATION. |
| |
| 21- ENERGY CALCULATIONS: A) NEED ENERGY |
| CALCULATIONS USING FORM 600A-2004. |
| B) CONDITIONED FLOOR AREA DOESN'T |
| MATCH PLANS. |
| C) BUILDING ORIENTATION, OVERHANG |
| LENGTH, OVERHANG HEIGHT AND AREA DON'T |
| MATCH PLANS. REVISE AS REQUIRED. SEE |
| CHAPTER 13 FBC 2004 FOR PROPER WAY OF |
| CALCULATING THESE ITEMS. |
| D) OWNER/AGENT TO SIGN BOTTOM OF FORM |
| |
| ***NOTE: TO EXPEDITE REVIEW PROCESS, |
| PLEASE RETURN REVIEWED SET AFTER |
| CORRECTIONS ARE DONE TO ORIGINALS. |
| |