Plan Review Notes For Permit 06010421 |
Permit Number |
06010421 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-03-13 00:00:00 | DENIED; | | 1. SEE ELECTRICAL PLAN REVIEW NOTE ONE. | | 2.WATER RISER, WATER HAMMER ARRESTORS | | ARE REQUIRED ON THE AUTOMATIC CLOTHES | | WASHER AND ON KITCHEN SINK. FBC-2004 | | PLUMBING SEC.604.9. | | 3.HOUSE SHUTOFF VALVE REQUIRED ON WATER | | SERVICE. SEC.606. | | 4.3" PIPE REQUIRED FOR AUTOMATIC CLOTHES | | WASHER. SEC.406.3. | | 5.KITCHEN SINK WASTE ARM CAN ONLY BE 6' | | FROM A VENT.SEE TABLE906.1. USE A | | MACHANICAL VENT UNDER THE SINK. | | 6. REMOVE NOTE 26. SEE SEC. 608. NO | | CROSS CONNECTIONS ARE PERMITED IN THE | | WATER SYSTEM. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|