Plan Review Notes For Permit 06010421 |
Permit Number |
06010421 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-25 00:00:00 | *** DENIED *** | | 1)ENERGY CALCULATIONS NEED TO BE ON FORM | | 600A-04 (2004) PER FBC 13-600.3.A . | | | | 2) NEED A/C CONTRACTOR'S LICENCE NUMBER, | | NAME, AND SIGNATURE ON MECHANICAL PLANS. | | ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1 . | | | | 3)NEED JOB SITE ADDRESS ON MECHANICAL | | PLANS. | | | | 4) SUPPLY AIR DUCT FROM AHU TO MIXING | | BOX FOR MASTER BEDROOM IS NOT SIZED. | | | | 5) RETURN AIR TRANSFER DUCT FROM AHU TO | | MASTER BEDROOM IS SHOWING TWO DIFFERENT | | SIZES, PLEASE CORRECT. | | | | 6) MECHANICAL PLANS HAVE TO MUCH FLOOR | | PLAN INFOMATION ON THEM AND ARE | | DIFFICULT TO READ. CONSTRUCTION | | DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY. PER 2004 FBC 106.1.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|