Plan Review Notes
Plan Review Notes For Permit 06010421
Permit Number 06010421
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-20 00:00:00******** UNSAT ************
  
 1)NOTE: PLEASE SEE MISSING FIRM LICENSE
 NUMBER ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. FAC 61G1-16.004, FS 481.219
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEEELECTRICAL PLANS ARE
 SIGNED , DATED AND SEALED BY AN
 ELECTRICAL ENGINEER, HOWEVER PLANS DO
 NOT CONTAIN ANY TITLE BLOCK FOR SAID
 ENGINEER OF RECORD AS REQUIRED PER FAC
 61G15-23.002, FS 471.023
  
 3)NOTE: PLEASE VERIFY THE 1/2" CONDUIT
 SHOWN FOR FUTURE PHONE. IT IS KNOWN TO
 THIS OFFICE THE TELEPHONE COMPANY AND
 CABLE COMPANY REQUIRES A MIN OF 3/4"
 CONDUIT FOR UNDERGROUND INSTALLATIONS.
 THIS IS FOR INFORMATIONAL PURPOSE ONLY
 AS THIS IS NOT AN NEC REQUIREMENT.
  
 4)NOTE: PLEASE CORRELATE LOAD FOR RANGE
 IN LOAD CALCS WITH LOAD ON PANEL
 SCHEDULE.
 PLEASE VERIFY IF INDEED A 40A BRKR WILL
 BE USED AS MOST RANGES REQUIRE A MIN OF
 50A. (RANGE RECEPT IS 50A)
 PLEASE ALSO VERIFY WIRING METHODS TO BE
 USED. PLANS INDICATE CONDUIT AND WIRING,
 HOWEVER IF ROMEX IS USED, THE #8 SHOWN
 WOULD BE REQUIRED TO BE INCREASED TO #6.
 SEE 310.16, 60 DEGREE COL.
 215.5
  
 5)NOTE: PLEASE SEE SD'S ARE SHOWN BEING
 WIRED TO MORE THAN ONE CIRCUIT. PLEASE
 KNOW, THESE ARE REQUIRED TO BE WIRED
 INLINE AND WILL NOT WORK AS SHOWN.
 PLEASE BE SURE CIRCUIT SI ONE CONTAINING
 ARC FAULT PROTECTION.
  
 6)NOTE: PLEASE SEE ITEMS LISTED
 "OFF"PANEL SCHEDULE.
  
 7)NOTE: PLEASE SEE BATH CIRCUIT SHOWN AS
 #15 AWG? MISPRINT.
 PLEASE ALSO SEE BATH CIRCUITS ARE SHOWN
 WITH ARC FAULT BRKRS?
  
 8)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE RECEPTS PER 210.52C1
  
 9)NOTE: PLEASE SEE MISSING REAR GFI
 RECEPT PER 210.52E
  
 10)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES LANSCAPE LTS, HOWEVER PLANS DO
 NOT SHOW ANY. PLEASE KNOW, IF NONE SHOWN
 ON PLANS, THEN LANDSCAPE LIGHTING WILL
 BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT, WHICH WILL INCLUDE PERMIT, PLANS
 AND FEE.
  
 ** PLEASE VERIFY WIRING METHOD, AS PLANS
 INDICATE CONDUIT AND WIRING FOR ALL
 CIRCUITS. IF SHOWN , ROMEX WOULD NOT BE
 PERMITTED.
 THIS IS ONLY A NOTE.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved