Plan Review Notes
Plan Review Notes For Permit 06010421
Permit Number 06010421
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-10 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY
 SEC. R401.3 OF 2004 RESIDENTIAL CODE.
  
 3- PROVIDE STRUCTURAL BUCK DETAIL USING
 2X BUCK AS REQUIRED BY ENTRY DOOR
 PRODUCT APPROVAL SUBMITTED. SEE SECTION
 R613.6.2 2004 RESIDENTIAL CODE FOR
 PROPER BUCK INSTALLATION.
  
 4- OWES $351.21 FOR UPDATED VALUATION
 AND RADON FEES.
  
 5- PROVIDE SPECS/DETAILS FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 6- DRAWINGS S-2 AND S-3 ARE MISSING THE
 ENGINEER'S INFORMATION AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
  
 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR SLIDING GLASS DOORS AND
 FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 UNIT AS SHOWN ON PLANS OR PROVIDE
 COMPLETE INFORMATION FOR STRUCTURAL
 MULLION AS REQUIRED BY SEC. R613.7 2004
 RESIDENTIAL CODE.
 B) SPECIFY SIZE OF FIXED WINDOW.
  
 8- ARCHITECT TO PROVIDE ALLINFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES AND 61G1-16.004 OF
 ADMINISTRATIVE CODE. SEE ATTACHED COPY.
  
 9- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 FOR:
 A) FRENCH DOORS WITH TRANSOM ABOVE.
 OR FRENCH DOORS ALONE. SEE ITEM #7 ABOVE
 B) SLIDING GLASS DOORS WITH TRANSOM
 ABOVE. OR SLIDING GLASS DOORS ALONE. SEE
 ITEM #7 ABOVE.
 C) STRUCTURAL MULLIONS. SEE ITEM #7.
 D) FIXED WINDOWS. SEE ITEM #7 ABOVE.
 E) ALL TRUSS CONNECTORS. SEE PLANS.
 F) SINGLE HUNG WINDOWS. DADE COUNTY
 NOA TO MATCH NOA SUBMITTED FOR FLORIDA
 PRODUCT APPROVAL. VISIT
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 CORRESPONDING NOA.
 G) ROOF SHINGLES. PROVIDE SAME NOA
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
 H) PRECAST LINTELS.
 I) ALUMINUM VENTS.
 J) ALUMINUM SIDING.
  
 10- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 11- DRAWING 1: UPDATE BUILDING CODE
 DATA. SEE 2004 RESIDENTIAL CODE.
  
 12- DRAWING A-1: A) WINDOW C (3'-0" X
 4'-0") DOESN'T MEET THE EGRESS
 REQUIREMENTS OF SEC. R310.1.2 2004
 RESIDENTIAL CODE.
 B) SPECIFY SAFETY GLASS FOR WINDOW IN
 BATHROOM. SEE PLANS. SEC. R308.4 2004
 RESIDENTIAL CODE.
 C) UPDATE CODE REFERENCE FOR ATTIC
 ACCESS. SEE 2004 RESIDENTIAL CODE.
 D) UPDATE CODE REFERENCES SPECIFIED
 ON GENERAL NOTES AND SCHEDULE NOTES. SEE
 2004 RESIDENTIAL CODE.
  
 13- DRAWING A-2: A) DESIGN PRESSURES
 MARK DOESN'T MATCH MARK SHOWED ON DOORS
 AND WINDOWS OPENINGS. REVISE AS REQ'D.
 B) SPECIFY SIZE OF MANUFACTURED
 ALUMINUM LOUVER AT FRONT AND BACK. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 14- DRAWING A-3: A) WHERE IS DETAIL A-5"
 SPECIFIED ON PLANS?
 B) SECTION "A": 1) THERE IS NOT
 ARCHED PORCH BEAM. REVISE AS REQUIRED.
 2) WHERE IS DETAIL SHT 5?
 3) SPECIFIED FIREBLOCKING MATERIAL
 AND LOCATION AT CONCEALED SPACES IN
 SOFFITS AND WALLS. SEE PLANS. SEC.
 R602.8 2004 RESIDENTIAL CODE.
  
 15- DRAWING A-4: A) WALL SECTION "A".
 UPDATE CODE REFERENCE SPECIFIED FOR
 FIREBLOCKING AND SPECIFY FIREBLOCKING
 MATERIAL. SEE 2004 RESIDENTIAL CODE.
 B) WALL SECTION "B". FOUNDATION PLAN
 DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 C) PORCH BEAM IS NOT AN ARCHED BEAM.
 REVISE AS REQUIRED. SEE PLANS.
  
 16- DRAWING S-1: A) PROVIDE COMPLETE
 DETAILS AND SPECS FOR WOOD DECK AND WOOD
 STEPS AT REAR AREA OUTSIDE MASTER
 BEDROOM AND AT COVERED PORCH.
 B) ROOF FRAMING PLAN CALLS FOR TRUSS
 ANCHOR A3 BY REAR PORCH. THERE IS NOT
 A3. REVISE AS REQUIRED.
 C) WHERE ARE DETAILS A, C AND E?
 D) WWHERE IS DET 2 SHT S-2?.
 KEY DETAILS TO MATCH DRAWINGS.
  
 17- DRAWING S-2: A) TYP. 1 STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. ALSO, CONSIDER ALUMINUM
 VENTS FOR TOTAL VENTING AREA REQUIRED.
 SEC. R806 2004 RESIDENTIAL CODE.
 B) DETAIL D: 1) HOW IS 2"X6" SILL
 PLATE ATTACHED TO CONCRETE BEAM?
 2) HOW IS 2" X 6" "L" BRACE NAILED TO
 BOTTOM SILL?
 3) USP TA18 IS SHOWN AS BEING
 ATTACHED TO CONCRETE BEAM. THIS
 CONNECTOR IS TO BE EMBEDED IN CONCRETE.
 REVISE AS REQUIRED. SEE USP CATALOGUE.
 4) DETAIL A: SHOW COMPLETE DETAILS
 AND SPECS FOR CONCRETE STEPS AT ENTRY
 PORCH.
  
 18- DRAWING S-3: A) GENERAL NOTES:
 UPDATE ALL REFERENCE STANDARDS AND
 SPECIFIC EDITION TO BE USED. SEE 2004
 RESIDENTIAL CODE AND 2004 FBC.
 B) UPDATE CODE SECTIONS REFERENCED
 FOR WIND LOADS, EMERGENCY EGRESS AND
 GLASS IMPACT PROTECTION NOTES.
 C) VENTILATION AND EGRESS ARE TWO
 DIFFERENT CODE ISSUES.REVISE AS REQ'D.
 D) TRUSS ANCHOR SCHEDULE: NUMBER OF
 NAILS AND UPLIFT LOADS TO MATCH CURRENT
 USP CATALOGUE. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR NUMBER
 AND UPLIFT LOADS THAT DIFFER THOSE
 PUBLISHED BY MANUFACTURER. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
 E) DELETE NOTES CORRESPONDING TO
 STRUCTURE ADDITIONS. THEY DON'T APPLY TO
 THIS PROJECT.
  
 19- SURVEY TO HAVE SURVEYOR'S ORIGINAL
 SIGNATURE, NOT COPY, AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES.
  
 20- STORM SHUTTERS:
 A) PROVIDE KEY PLAN.
 B) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. PROVIDE
 ALL INFORMATION.
  
 21- ENERGY CALCULATIONS:
 A) USE 2004 FORM, NOT 2001.
 B) BUILDING ORIENTATION, OVERHANG
 LENGTH AND HEIGHT AND AREA DON'T MATCH
 PLANS. REVISE AS REQUIRED. SEE CHAPTER
 13 FBC 2004 FOR PRROPER WAY OF
 CALCULATING ENERGY CALCS. REVISE AS
 REQUIRED.
 ***NOTE: IF ENERGY CALCULATIONS ARE NOT
 DONE FOR WORST CASE SCENARIO, THEN THEY
 MUST BE DONE ACCORDING TO THE ACTUAL
 HOUSE ORIENTATION. SEE SURVEY FOR
 CORRECT ORIENTATION.
 C) OWNER/AGENT TO SIGN BOTTOM OF FORM
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712