Date |
Text |
2006-02-09 00:00:00 | *** DENIED *** |
| 1)ENERGY CALCULATIONS NEED TO BE ON FORM |
| 600A-04 (2004) PER FBC 13-600.3.A AND |
| NEED TO BE SIGNED BY OWNER/AGENT. |
| |
| 2) ENERGY CAL'S. ARE CALLING FOR 60,000 |
| TOTAL BTU'S, PLANS ARE CALLING FOR |
| 90,800 TOTAL BTU'S, PLANS CAN NOT CALL |
| FOR MORE TGAN THE ENERGY CAL'S. PLEASE |
| CORRECT. |
| |
| 3) NEED TO SHOW SENSIBLE BTU'S. ALSO, ON |
| PLANS A/C SCHEDULE. |
| |
| 4) AHU #1 CONDENSATE DRAIN CAN NOT |
| DISCHARGE ON THE FRONT PORCH, PER 2004 |
| FBC/M 1411.3 . |
| |
| 5) AHU #1 PROVIED RETURN AIR TO ALL |
| HABITABLE ROOMS WITH DOORS, SEE NOTE #6. |
| |
| 6)BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| 7) AHU #1 PLEASE SHOW IF YOU ARE USING A |
| TRUNK LINE OR MIXING BOXES FOR SUPPLY |
| AIR. |
| |
| 8) AHU #2 PROVIED RETURN AIR FOR NEW |
| OFFICE, KITCHEN, AND FAMILY ROOM, SEE |
| NOTE #6. |
| |
| 9) AHU #2 CAN NOT HAVE AN OPEN RETURN |
| AIR PLENUM IN THE GARAGE, SEE 2004 FBC/R |
| 309.1.1 . |
| |
| 10) AHU #3 ALL RETURN AIR GRILLS ABOVE |
| BEDROOM DOORS ARE TO SMALL, SEE NOTE #6. |
| |
| 11) PLEASE NOTE WHEN APPLYING FOR YOUR |
| GENERATOR PERMIT. GENERATOR EXHUST MUST |
| BE TEN FEET AWAY FROM ANY BUILDING |
| OPENINGS (WINDOWS, DOORS, ROOF & EAVE |
| VENTS), AND TEN FEET AWAY FROM ADJECENT |
| BUILDING OPENS. PER 2004 FBC/M 401.5.1 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |
| |