Plan Review Notes
Plan Review Notes For Permit 06010393
Permit Number 06010393
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-09 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A AND
 NEED TO BE SIGNED BY OWNER/AGENT.
  
 2) ENERGY CAL'S. ARE CALLING FOR 60,000
 TOTAL BTU'S, PLANS ARE CALLING FOR
 90,800 TOTAL BTU'S, PLANS CAN NOT CALL
 FOR MORE TGAN THE ENERGY CAL'S. PLEASE
 CORRECT.
  
 3) NEED TO SHOW SENSIBLE BTU'S. ALSO, ON
 PLANS A/C SCHEDULE.
  
 4) AHU #1 CONDENSATE DRAIN CAN NOT
 DISCHARGE ON THE FRONT PORCH, PER 2004
 FBC/M 1411.3 .
  
 5) AHU #1 PROVIED RETURN AIR TO ALL
 HABITABLE ROOMS WITH DOORS, SEE NOTE #6.
  
 6)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 7) AHU #1 PLEASE SHOW IF YOU ARE USING A
 TRUNK LINE OR MIXING BOXES FOR SUPPLY
 AIR.
  
 8) AHU #2 PROVIED RETURN AIR FOR NEW
 OFFICE, KITCHEN, AND FAMILY ROOM, SEE
 NOTE #6.
  
 9) AHU #2 CAN NOT HAVE AN OPEN RETURN
 AIR PLENUM IN THE GARAGE, SEE 2004 FBC/R
 309.1.1 .
  
 10) AHU #3 ALL RETURN AIR GRILLS ABOVE
 BEDROOM DOORS ARE TO SMALL, SEE NOTE #6.
  
 11) PLEASE NOTE WHEN APPLYING FOR YOUR
 GENERATOR PERMIT. GENERATOR EXHUST MUST
 BE TEN FEET AWAY FROM ANY BUILDING
 OPENINGS (WINDOWS, DOORS, ROOF & EAVE
 VENTS), AND TEN FEET AWAY FROM ADJECENT
 BUILDING OPENS. PER 2004 FBC/M 401.5.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  