Plan Review Notes For Permit 06010368 |
Permit Number |
06010368 |
|
Review Stop |
E |
Sequence Number |
9 |
|
Notes |
Date |
Text |
2007-09-25 11:11:44 | | | | | | | | | NONCOMPLIANT | | | | THESE COMMENTS FROM THE PREVIOUS 8/9/07 REVIEW HAVE NOT | | BEEN ADDRESSED, AND THE SAME ELECTRICAL PLANS WERE | | RESUBMITTED. | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE RISER DIAGRAM INDICATES AN EXISTING 200 AMP | | PANEL "A" AND A NEW 150 AMP PANEL "B". THE PANEL | | SCHEDULES LIST PANEL "A" WITH A 300 AMP MAIN AND PANEL | | "B" AS A NEW 250 AMP SUB-PANEL. THE PANELS ARE RATED AT | | 150 AND 200 AMPS AT THE METER LOCATION ON THE | | SITE/FLOOR PLAN. THE NEW SUB-PANEL LOCATION LISTS THE | | PANEL AS 250 AMP. CORRECTLY LABEL ALL THE SERVICE | | EQUIPMENT ON THE PLAN. 106.5, FBC AS AMENDED. | | | | 2} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND | | 210.52(A)(2). LOCATE SAME IN THE "NEW FAMILY ROOM", ONE | | MISSING IN THE "NEW WET BAR", AND "NEW BEDROOM", SEE | | REVIEWED PLAN FOR LOCATIONS. | | | | 3} PER 210.70(B)(2)(B) "AT LEAST ONE WALL | | SWITCH,CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO | | PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR | | ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS" THIS IS | | MISSING IN THE "NEW PLAY ROOM". | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|