2007-08-09 13:33:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** REVISION DENIED ***
 1) AS REQUESTED IN LAST REVIEW 6-28-07 NOTE #5
 MECHANICAL PLAN NEEDS TO SHOW THE RETURN AIR GRILLS AND
 SIZE FOR 5 TON AHU SEE YELLOW HIGH LIGHT ON PLAN.
  
 2) SHOW ON MECHANICAL PLAN HOW THE RETURN AIR FROM THE
 NEW WET BAR, NEW PLAY ROOM, AND NEW BEDROOM IS GOING TO
 RETURN TO THE AIR HANDLER IF ALL DOORS ARE CLOSED. SEE
 2004 FBC/R M1602.4.
  
 3) REVISED MECHANICAL PLANS SUBMITTED SHOWS ONE 5 TON
 A/C SYSTEM SERVICING THE WHOLE HOUSE, REVISED ENERGY
 CALCULATIONS STATE ONE 5 TON AND ONE 2 TON SERVICING
 THE HOUSE, THE TWO MUST COINCIDE. PLEASE CORRECT.
  
 4) PREVIOUS MECHANICAL PLANS HAD SHOWN TWO A/C SYSTEMS
 TO BE INSTALLED, THIS PLAN ONLY SHOWS ONE SYSTEM,
 PLEASE DOUBLE CHECK THE DESIGN BEFORE RE-SUBMITTING.
  
 5) BEFORE RE-SUBMITTING PLEASE CHECK THEN RE-CHECK THE
 PLANS, ENERGY CALCULATIONS, AND COOLING LOAD
 CALCULATIONS TO MAKE CERTAIN THEY ARE ACCURATE, CORRECT
 AND COINCIDE WITH EACH OTHER.
  
 6)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].