Plan Review Notes
Plan Review Notes For Permit 06010368
Permit Number 06010368
Review Stop E
Sequence Number 8
Notes
Date Text
2007-08-09 08:36:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
 FBC 2004, 2002 NEC, 2002 NFPA-70. CODES EFFECTIVE FOR
 THIS PERMIT.
  
 1} THE RISER DIAGRAM INDICATES AN EXISTING 200 AMP
 PANEL "A" AND A NEW 150 AMP PANEL "B". THE PANEL
 SCHEDULES LIST PANEL "A" WITH A 300 AMP MAIN AND PANEL
 "B" AS A NEW 250 AMP SUB-PANEL. THE PANELS ARE RATED AT
 150 AND 200 AMPS AT THE METER LOCATION ON THE
 SITE/FLOOR PLAN. THE NEW SUB-PANEL LOCATION LISTS THE
 PANEL AS 250 AMP. CORRECTLY LABEL ALL THE SERVICE
 EQUIPMENT ON THE PLAN. 106.5, FBC AS AMENDED.
  
 2} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). LOCATE SAME IN THE "NEW FAMILY ROOM", ONE
 MISSING IN THE "NEW WET BAR", AND "NEW BEDROOM", SEE
 REVIEWED PLAN FOR LOCATIONS.
  
 3} PER 210.70(B)(2)(B) "AT LEAST ONE WALL
 SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO
 PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR
 ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS" THIS IS
 MISSING IN THE "NEW PLAY ROOM".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]