2007-06-28 11:22:41** REVISION DENIED **
 1) ENERGY CALCULATIONS LINE 11 A & B SHOW THE SUPPLY
 AND RETURN AIR DUCTS IN A CONDITIONED SPACE, THE DUCTS
 ARE IN THE ATTIC AND IS UN-CONDITIONED, PLEASE
 CORRECT.
  
 2) ENERGY CALCULATIONS LINE 15 IS TAKING CREDIT FOR
 CEILING FANS THE ELECTRICAL PLANS NEED TO SHOW FANS IN
 ALL THE BEDROOMS ALSO THE EXISTING BEDROOMS, PLEASE
 CORRECT.
  
 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS FOR THE 5
 TON A/C SYSTEM ALSO, AS THE ZONES HAVE CHANGED.
  
 4) SEE MECHANICAL PLANS PAGE M/1 "A/C NOTES" STATE PALM
 BEACH COUNTY, THIS IS THE CITY OF WEST PALM BEACH,
 PLEASE CORRECT PLAN.
  
 5) MECHANICAL PLAN NEEDS TO SHOW THE RETURN AIR GRILLS
 AND SIZE FOR 5 TON AHU SEE YELLOW HIGH LIGHT ON PLAN.
  
 6) PLEASE SHOW THE LOCATION OF BOTH A/C CONDENSER UNITS
 ON THE MECHANICAL PLANS, AND LABEL THEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.