Plan Review Notes For Permit 06010368 |
Permit Number |
06010368 |
|
Review Stop |
M |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2007-06-28 11:22:41 | ** REVISION DENIED ** | | 1) ENERGY CALCULATIONS LINE 11 A & B SHOW THE SUPPLY | | AND RETURN AIR DUCTS IN A CONDITIONED SPACE, THE DUCTS | | ARE IN THE ATTIC AND IS UN-CONDITIONED, PLEASE | | CORRECT. | | | | 2) ENERGY CALCULATIONS LINE 15 IS TAKING CREDIT FOR | | CEILING FANS THE ELECTRICAL PLANS NEED TO SHOW FANS IN | | ALL THE BEDROOMS ALSO THE EXISTING BEDROOMS, PLEASE | | CORRECT. | | | | 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS FOR THE 5 | | TON A/C SYSTEM ALSO, AS THE ZONES HAVE CHANGED. | | | | 4) SEE MECHANICAL PLANS PAGE M/1 "A/C NOTES" STATE PALM | | BEACH COUNTY, THIS IS THE CITY OF WEST PALM BEACH, | | PLEASE CORRECT PLAN. | | | | 5) MECHANICAL PLAN NEEDS TO SHOW THE RETURN AIR GRILLS | | AND SIZE FOR 5 TON AHU SEE YELLOW HIGH LIGHT ON PLAN. | | | | 6) PLEASE SHOW THE LOCATION OF BOTH A/C CONDENSER UNITS | | ON THE MECHANICAL PLANS, AND LABEL THEM. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|