Plan Review Notes
Plan Review Notes For Permit 06010368
Permit Number 06010368
Review Stop E
Sequence Number 7
Notes
Date Text
2007-06-27 15:01:07 
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} CHANGE THE SHEET NUMBER TO A/5 AS THAT IS THE
 ORIGINAL AND LAST REVISED SHEET NUMBER. SHEET A/5 CAN'T
 BE REPLACED BY E.1. REMOVE THE PLUMBING REVISION AND
 PUT IT ON THE PROPERLY NUMBERED (SEE PERMITTED SET).
 PUT THE RISER AND ALL PERTINENT INFORMATION THAT WAS
 OMITTED FROM THIS REVISION, BACK ON SHEET A/5.
  
 2} PUT THE CORRECT DESIGNATION BACK ON THE
 PANELS(EXISTING FOR "A"AND GIVE RATING IN AMPS, AND
 NEW.FOR THE NEW PANEL "B"). ALSO VERIFY THAT PANEL "B"
 HAS BEEN RELOCATED SINCE THE PREVIOUS REVISION..
  
 3} INDICATE THE DEVICE AND LIGHTING LOCATIONS THAT WERE
 PART OF THE ORIGINAL SCOPE OF WORK.
  
 4} THE PARLOR MUST COMPLY WITH 210.52 RECEPTACLE
 SPACING SPACING REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718