Plan Review Notes
Plan Review Notes For Permit 06010368
Permit Number 06010368
Review Stop M
Sequence Number 6
Notes
Date Text
2007-05-11 11:06:31 
 *** REVISION DENIED ***
 1) REVISED PLANS ARE SHOWING THE ORIGINAL ADDITION AS
 EXISTING, THIS IS NOT EXISTING AS IT IS STILL PART OF
 THIS PERMIT, PLEASE CORRECT ALL PLANS.
  
 2) A/C DUCTS HAVE BEEN REMOVED FROM THE ORIGINAL
 ADDITION, PLEASE CORRECT AS THEY ARE STILL PART OF THE
 PERMIT.
  
 3) SHOW ON MECHANICAL PLANS HOW RETURN AIR IS GETTING
 BACK TO THE AIR HANDLER FROM ALL REQUIRED SPACES.
  
 4) BATHROOM EXHAUST FANS HAVE BEEN REMOVED FROM
 BATHROOMS, PLEASE CORRECT.
  
 5) COOLING LOAD CALCULATIONS NEED TO BE RE-CALCULATED
 AS THEY ARE SHOWING THE WRONG AREA AND VOLUME, NEED TO
 BE CALCULATED FOR THE TOTAL ADDITION NOT INCLUDING THE
 ORIGINAL HOUSE.
  
 6) ENERGY CALCULATIONS NEED TO BE RE-DONE FOR THE SAME
 REASON
  
 7) SEE MECHANICAL PLANS A/C NOTES: ARE REFERRING TO
 PALM BEACH COUNTY, PLEASE CORRECT TO SHOW CITY OF WEST
 PALM BEACH.
  
 8) SEE MECHANICAL PLANS TOTAL AREA, PLEASE CORRECT TO
 SHOW AREAS UNDER THIS PERMIT
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729. .