Plan Review Notes
Plan Review Notes For Permit 06010368
Permit Number 06010368
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-14 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2. SEE A/5 &
 A/6.
  
 2} INDICATE THE AIC RATING OF THE
 DISCONNECT. THIS IS THE FIRST MEANS AND
 THE CORRECT AIC FOR THE BREAKERS IS MOST
 CRITICAL HERE.
  
 3} INDICATE THE SERVICE CONDUCTOR SIZE
 AND TYPE. 4/0 MIN PER 310.15(B)(5).
  
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT