Plan Review Notes
Plan Review Notes For Permit 06010368
Permit Number 06010368
Review Stop B
Sequence Number 3
Notes
Date Text
2006-06-17 00:00:00 
 1) THE CAST-CREET U LINTEL SCHEDULE ON
 SHEET A/1 IS MISSING L-17 AND L-27.
 ADJUST THE SCHEDULE TO REFLECT THE
 DRAWINGS.
  
 2) WITH THE ADDITION FO THE REAR PORCH
 THE VALUE FOR THIS APPLICATION HAS TO BE
 UPDATED . GIVE A FAIR MARKET VALUE FOR
 THE ADDITION OF THE PORCH OR WE WILL
 ADJUST THE COST USING THE MARSHALL-SWIFT
 REFERENCE BOOK. SO, IN ADDITION TO THE
 REVISION FEES ADDITIONAL FEES ARE DUE
 BASE ON THE SQUARE FOOTAGE OF THE NEW
 COVERED POACH
  
 3) R802.10.1 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SECTION R802.10.1 ,
 SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. TRUSS DESIGN DRAWINGS
 SHALL INCLUDE, AT A MINIMUM, THE
 INFORMATION SPECIFIED BELOW. TRUSS
 DESIGN DRAWING SHALL BE PROVIDED WITH
 THE SHIPMENT OF TRUSSES DELIVERED TO THE
 JOBSITE.
  
 4) THE DRAWINGS WE HAVE ON FILE STATES
 THE TOTAL A/C AREA IS 2306 SQ.FT.
 HOWEVER THE NEW DRAWINGS SHOWS THE TOTAL
 A/C AREA IS 2414 SQ.FT. SHOW CLEARLY ON
 THE NEW DRAWINGS WHERE THE ADDITIONAL
 INCREASE IS.
  
 5) F.S.472.025 ALL FINAL DRAWINGS,
 PLANS, SPECIFICATIONS, PLATS, OR REPORTS
 PREPARED OR ISSUED BY THE REGISTRANT IN
 ACCORDANCE WITH MINIMUM TECHNICAL
 STANDARDS SET BY THE BOARD SHALL BE
 SIGNED BY THE REGISTRANT, DATED AND
 STAMPED WITH HIS OR HER SEAL.
 SEE SHEETS A/5-A/7.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL(561)805-6726
  
  