Notes |
Date |
Text |
2006-01-30 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE A/C CALCULATIONS ON SHEET A/5 DO | | NOT MATCH THE MECHANICAL SPEC'S ON SHEET | | A/7. | | | | 2} RECEPTACLE SPACING DOES NOT COMPLY | | WITH 210.52(A)(1)&(2) IN ANY ROOM OF THE | | ADDITION. SEE REVIEWED SET OF PLANS FOR | | EXAMPLES. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|