2006-01-18 00:00:00DENIED;
 1.SHOW ROOF DRAINAGE PER. FBC-2004
 PLUMBING CHAPTER 11. GUTTERS AND DOWN
 SPOUTS REQUIRED. PLEASE SIZE AND SHOW ON
 DRAWINGS. RAIN WATER MUST DISCHARGE A
 MINIMUM OF 12" FROM BUILDING.
 2.SHOW SIZE AND QUANITY OF SCUPPERS ON
 PORCHES.
 3.FLOOR DRAIN NOT PERMITED IN ELEVATOR
 PIT. HYDROLIC FLUID CAN NOT DISCHARGE
 INTO DRAINAGE SYSTEM.
 4.RISER DIAGRAM; 1ST FLOOR LAVITORY AND
 W/C ARE NOT VENTED.
 5.3" RISER TO 2ND AND 3RD FLOOR PLUMBING
 SHOULD BE DOWN STREAM OF FIRST FLOOR
 BATHROOM.
 6.2ND FLOOR KITCHEN SINK (SINGLE BOWL)
 NOT VENTED.
 7.MASTER BATHROOM W/M MUST DISCHARGE
 DOWN STREAM OF THE BATHROOM GROUP. SEC
 909.1.
 8.SIZE ALL SECTIONS OF PIPE ON RISER
 DIAGRAM.
 9.3RD FLOOR SHOWER NOT VENTED.
 SEE ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;