Plan Review Notes For Permit 06010343 |
Permit Number |
06010343 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-18 00:00:00 | DENIED; | | 1.SHOW ROOF DRAINAGE PER. FBC-2004 | | PLUMBING CHAPTER 11. GUTTERS AND DOWN | | SPOUTS REQUIRED. PLEASE SIZE AND SHOW ON | | DRAWINGS. RAIN WATER MUST DISCHARGE A | | MINIMUM OF 12" FROM BUILDING. | | 2.SHOW SIZE AND QUANITY OF SCUPPERS ON | | PORCHES. | | 3.FLOOR DRAIN NOT PERMITED IN ELEVATOR | | PIT. HYDROLIC FLUID CAN NOT DISCHARGE | | INTO DRAINAGE SYSTEM. | | 4.RISER DIAGRAM; 1ST FLOOR LAVITORY AND | | W/C ARE NOT VENTED. | | 5.3" RISER TO 2ND AND 3RD FLOOR PLUMBING | | SHOULD BE DOWN STREAM OF FIRST FLOOR | | BATHROOM. | | 6.2ND FLOOR KITCHEN SINK (SINGLE BOWL) | | NOT VENTED. | | 7.MASTER BATHROOM W/M MUST DISCHARGE | | DOWN STREAM OF THE BATHROOM GROUP. SEC | | 909.1. | | 8.SIZE ALL SECTIONS OF PIPE ON RISER | | DIAGRAM. | | 9.3RD FLOOR SHOWER NOT VENTED. | | SEE ONE SET OF PLANS MARKED IN RED. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|