Plan Review Notes
Plan Review Notes For Permit 06010343
Permit Number 06010343
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-12 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ARCHITECT MUST COMPLY WITH FS
 481, SEAL AND SIGN PLANS.
  
 2} THE REQUIRED LAUNDRY CIRCUIT PER
 210.16(B) IS NOT IN THE LOAD CALC, NOR
 THE POOL HAETER OR STEAMER. PLEASE
 CORRELATE THE CALCULATIONS WITH THE
 EQUIPMENT AND BRANCH CIRCUITS ON THE
 PANEL SCHEDULES.
  
 3} PLEASE LIST THE CORRECT CONDUCTOR AND
 OVERCURRENT PROTECTION FOR THE AIR
 HANDLERS, SEE PANEL "B".
  
 4} THE SMALL APPLIANCE CIRCUITS MUST BE
 SHOWN ON THE PANEL SCHEDULE.
 210.11(C)(3).
  
 5} THE GROUNDING ELECTRODE SYSTEM NEEDS
 TO INCLUDE TO THE FOOTER STEEL. 250.52.
  
 6} A SMOKE DETECTOR IS REQUIRED ON THE
 3RD LEVEL PER 313.1 FBC.
  
 7} THE DISCONNECTS SHOWN FOR THE POOL
 AND A/C UNITS MUST COMPLY WITH 110.26
 CLEARANCE REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  