Plan Review Notes For Permit 06010343 |
Permit Number |
06010343 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-12 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE ARCHITECT MUST COMPLY WITH FS | | 481, SEAL AND SIGN PLANS. | | | | 2} THE REQUIRED LAUNDRY CIRCUIT PER | | 210.16(B) IS NOT IN THE LOAD CALC, NOR | | THE POOL HAETER OR STEAMER. PLEASE | | CORRELATE THE CALCULATIONS WITH THE | | EQUIPMENT AND BRANCH CIRCUITS ON THE | | PANEL SCHEDULES. | | | | 3} PLEASE LIST THE CORRECT CONDUCTOR AND | | OVERCURRENT PROTECTION FOR THE AIR | | HANDLERS, SEE PANEL "B". | | | | 4} THE SMALL APPLIANCE CIRCUITS MUST BE | | SHOWN ON THE PANEL SCHEDULE. | | 210.11(C)(3). | | | | 5} THE GROUNDING ELECTRODE SYSTEM NEEDS | | TO INCLUDE TO THE FOOTER STEEL. 250.52. | | | | 6} A SMOKE DETECTOR IS REQUIRED ON THE | | 3RD LEVEL PER 313.1 FBC. | | | | 7} THE DISCONNECTS SHOWN FOR THE POOL | | AND A/C UNITS MUST COMPLY WITH 110.26 | | CLEARANCE REQUIREMENTS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|