Plan Review Notes
Plan Review Notes For Permit 06010310
Permit Number 06010310
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-24 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 MUNICIPAL CODE CITY WPB
  
 1. PLEASE SUBMIT A CODE SUMMARY
 INDICATING WHICH CODES THE BUILDING HAS
 BEEN DESIGNED BY.
 2. PLEASE DECLARE OCCUPANCY FOR THE
 BUILDING. SECTION 106.1.1.
 3. PLEASE SUBMIT A SUMMARY CHART
 SUPPLYING INFORMATION ON THE AMOUNT OF
 UNITS, UNIT TYPES WITH AMOUNT OF EACH,
 AND SHOW COMPLIANCE WITH SECTIONS
 11-9.1.2, 11-9.1.3, 11-9.1.4 & 11-9.2.3.
 INDICATE THE ROOM NUMBER FOR EACH
 REQUIREMENT, IE: ACCESSIBLE ROOM, ROOMS
 WITH ROLL IN SHOWERS, ACCOMODATIONS FOR
 PERSONS WITH HEARING IMPAIRMENTS ETC.
 THIS WILL BE REQUIRED FOR THE PERCENTAGE
 FOR ALL UNITS. (HOTEL)
 4. PLEASE INDICATE HOW ALL THE UNITS
 FROM THE PREVIOUS COMMENT WILL BE MADE
 AVAILABLE, AND IF THESE UNITS WILL BE
 SOLD AS CONDO'S WILL THEY BE MADE
 AVAILABLE AT ALL TIMES. SECTION 106.1.1.
 5. PLEASE INDICATE UNIT LOCATIONS AND
 ROOM NUMBERS CONSIDERED "CONDO
 OCCUPANCY". FAIR HOUSING WILL BE
 REQUIRED FOR THOSE UNITS. IF ALL UNITS,
 ALL UNITS SHALL BE REQUIRED TO MEET
 FHA-91 DESIGN MANUAL REQUIREMENTS ONE
 THRU SEVEN.
 6. SHTS A2.91 7 A2.10.1 INDICATE THE
 LOCATION OF ALL PRIMARY AND SECONDARY
 DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS.
 7. SHT A2.11.1 SHOW THE LOCATION OF
 SECONDARY ROOF DRAINS FOR THE AREA SOUTH
 OF THE ELEVATOR EQUIPMENT ROOM, RO2.
 SECTION 1107.
 8. SHTS A6.1.1 THRU A6.14.2 ALL WATER
 CLOSETS SHALL BE 1'6" OFF THE WALL TO
 THE CENTER LINE OF THE FIXTURE. THIS IS
 AN ABSOLUTE MENSUREMENT PER PAGE 6.5 FHA
 DESIGN MANUAL, AND FIGURE 28 SECTION
 11.3.1 FBC-2004. MEASUREMENTS SHOWN ARE
 1'63/8" OR 1'6" MIN. PLEASE CORRECT THE
 W/C MEASUREMENTS.
 9. SHTS A6.1.1 THRU A6.14.2 INDICATE THE
 CORRECT HEIGHT OF THE LAV AS 34" AS
 REQUIRED ON PAGE 7.52 FHA DESIGN MANUAL.
 10. SHTS A6.1.1 THRU A6.14.2 ALL
 ACCESSIBLE UNITS SHOW THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.16.6 DISPENSERS
 FOR LAVS:
 A. 1-4.19.4 EXPOSED PIPES & SURFACES
 FOR TUBS:
 A. 11-4.20.5 CONTROLS
 B. 11-4.20.6 SHOWER UNIT
 FOR SHOWERS:
 A. 11-4.21.3 SEAT
 B. 11-4.21.4 GRAB BARS
 C. 11-4.21.5 CONTROLS
 D. 11-4.21.6 SHOWER UNIT
 E. 11-4.21.7 CURBS
 11. SUBMIT A LEGEND SHOWING THE AMOUNT
 OF UNITS, AND INDICATE UNIT TYPES.
 INDICATE THE AMOUNT OF ACCESSIBLE UNITS,
 AMOUNT OF UNITS WITH ROLL-IN SHOWER,
 AMOUNT OF UNITS WITH ACCOMMODATIONS FOR
 PERSONS WITH HEARING IMPAIRMENTS, AND
 UNITS FOR HOTEL, MOTEL AND CONDOMINIUM
 SPECIAL ACCESSIBILITY FEATURE. SECTIONS
 11-9.1.2, 11-9.1.3, 11-9.1.4 AND
 11-9.2.3. INDICATE THE UNIT NUMBERS FOR
 EACH REQUIREMENT.
 12. SHTS A6.1.1 THRU A6.14.2 ALL
 ACCESSIBLE UNITS, PER SECTION 11-9.2(7)
 KITCHENETTS INDICATE PARALLEL APPROACH.
 THIS IS NOT APPROVED PER SECTION
 11-4.24.5. FORWARD APPROACH IS REQUIRED,
 AND CABINET DOORS ARE NOT APPROVED IN
 THE CLEAR FLOOR SPACE. PLEASE SUBMIT AN
 ELEVATION SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 13. SHTS A6.1.1 THRU A6.14.2 ALL FHA
 UNITS WITH A 2ND BATHROOM, SHOW THE
 OPENING DIMENSION FOR THE WATER CLOSET.
 MINIMUM 33" REQUIRED. W/C SHALL BE 18"
 OFF THE WALL TO CENTER OF FIXTURE, (IF
 WALL ADJACENT TO FIXTURE), OR MINIMUM OF
 18" OFF ONE FIXTURE AND MINIMUM OF 15"
 OFF THE OTHER FIXTURE. SEE PAGES 6.7,
 7.43, 7.44, 7.45, & 7.46.
 14. SHT A8.1.1 FINISH SCHEDULE FOR THE
 COMMON AREA IS NOT COMPLETE. SECTION
 106.1.1.
 15. SHT A8.2.1 REINFORCING AT THE TUB,
 SHOW REINFORCING AT THE HEAD OF THE TUB
 PER PAGE 6.9 FHA DESIGN MANUAL.
 16. SHT P0.1 CODE IS FBC-2004. CHANGE
 CODE REFERENCES.
 17. SHT P2.0 GAS PIPING FROM THE METER
 TO THE GAS RISERS. ONLY ONE RISER SHOWN.
 PLEASE CLARIFY. SECTION 106.1.1.
 18. SHTS P2.0 & P2.1 GREASE LINE INTO
 THE BUILDING SHOWS NO RISER FROM BELOW
 GRADE. SHT A2.1.1 DOES NOT SHOW A
 KITCHEN ON THE FIRST FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
 19. SHT P2.1 GAS LINES SHOWN UNDER THE
 SLAB OF THE BUILDING. PLEASE INDICATE
 HOW THE PIPING WILL BE PRESSURE TESTED
 AND INSPECTED, THEN AFTER THE PIPING
 TEST AND INSPECTION, SHALL HAVE CONDUIT
 INSTALLED OVER THE PIPE AS REQUIRED IN
 SECTIONS 404.11 AND 406.4. SHOW THE
 CONDUIT DETAIL SHOWING COMPLIANCE WITH
 SECTION 404.11.
 20. SHT P2.1 5" COMBINATION WASTE/VENT
 STACK, (#33) SHOWS 4" ON THE HORIZONTAL
 OFFSET. PLEASE CLARIFY. SECTION 704.2
 THE SIZE OF THE DRAINAGE PIPING SHALL
 NOT BE REDUCED IN THE DIRECTION OF FLOW.
 21. SHT P2.2 GAS RISER DIAGRAM INDICATES
 THE GAS FOR THE KITCHEN FLOOR RISES UP
 ABOVE THE SECOND FLOOR. ONLY ON RISER
 SHOWN. PLEASE CORRELATE RISER AND FLOOR
 PLAN. SECTION 106.1.1.
 22. SHT P2.2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTION 1106 & 1107 AND ALL SUBSECTIONS.
 SHOW SQUARE FOOTAGE AREA AND SHOW 1/2
 AREA OF ALL VERTICAL WALLS ADDED TO
 CALCULATIONS. IF SECONDARY ROOF DRAINS
 WILL BE SCUPPERS, THEY WILL BE SIZED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7. THE SIZING OF SCUPPERS CAN NOT
 BE DETERMINED WITH REFERENCE TO THE
 DEFLECTION OF THE ROOF. PLEASE NOTE IN
 CALCULATIONS.
 23. SHT P2.3 DOMESTIC WATER PUMP ROOM
 INDICATES A FLOOR DRAIN. NO PIPING IS
 SHOWN TO FLOOR DRAIN. SHOW PIPING ON THE
 FLOOR PLAN, WITH ALL PIPE SIZE, VENTING,
 TRAPS. SECTION 106.1.1.
 24. SHT P2.5 INDICATE THE LOCATION OF
 THE SECONDARY DRAINS FOR THE AREAS
 OUTSIDE UNITS T05 THRU T08. SUBMIT
 CALCULATION FOR PRIMARY AND SECONDARY
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTION. SHOW AREA TO BE DRAINED FOR
 EACH AREA DRAIN, AND SHOW 1/2 AREA OF
 ALL VERTICAL WALL INCLUDING PARAPETS TO
 EACH AREA. IF SECONDARY DRAINS ARE
 SCUPPERS, INDICATE THAT THE SIZE OF THE
 SCUPPERS HAVE BEEN CALCULATED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7. THE SIZING OF THE SCUPPERS CAN
 NOT BE DETERMINED WITHOUT REFERENCE TO
 THE DEFLECTION OF THE ROOF.
 25. SHT P2.6 RWL'S ARE NOT IDENTIFIED IN
 COLS. OUTSIDE UNIT T03. SECTION 106.1.1.
 26. SHT P2.16 AREA DRAINS OUTSIDE UNITS
 P02 AND P04 INDICATE PIPING DROPING TO
 THE 15TH FLOOR, BUT NO RWL SHOWN ON THE
 15TH FLOOR. PLEASE CLARIFY. SECTION
 106.1.1.
 27. SHT P2.16 INDICATE THE LOCATION OF
 THE SECONDARY DRAINS FOR THE AREAS
 OUTSIDE UNITS P02 THRU P04. SUBMIT
 CALCULATION FOR PRIMARY AND SECONDARY
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTION. SHOW AREA TO BE DRAINED FOR
 EACH AREA DRAIN, AND SHOW 1/2 AREA OF
 ALL VERTICAL WALL INCLUDING PARAPETS TO
 EACH AREA. IF SECONDARY DRAINS ARE
 SCUPPERS, INDICATE THAT THE SIZE OF THE
 SCUPPERS HAVE BEEN CALCULATED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7. THE SIZING OF THE SCUPPERS CAN
 NOT BE DETERMINED WITHOUT REFERENCE TO
 THE DEFLECTION OF THE ROOF.
 28. SHT P2.22 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. IF SECONDARY ROOF DRAIN ARE
 SCUPPERS, THEY WILL BE SIZED PER
 SECTIONS 1101.7, 1107.3, AND TABLE
 1106.7.
 29. SHT P2.22 FLOOR DRAIN AT COOLING
 TOWERS IS NOT AN APPROVED INDIRECT WASTE
 RECEPTOR. SECTIONS 802.3 & 802.3.2.
 FLOOR SINK OR HUB DRAIN REQUIRED.
 RECEPTOR SHALL BE LOCATED UNDER COOLING
 TOWER TO PREVENT STORM WATER FROM
 ENTERING.
 30. SHT P2.23 SHOW THE LOCATION OF ALL
 THE PRIMARY AND SECONDARY ROOF DRAINS.
 SUBMIT CALCULATION FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA OF
 EACH DRAIN AND INDICATE 1/2 AREA OF ALL
 VERTICLE WALLS INCLUDING PARAPETS IN
 CALCULATION. IF SECONDARY DRAINS ARE
 SCUPPERS, THEY SHALL BE SIZED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7.
 31. SHT P2.24 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTION 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW AREA OF EACH DRAIN AND
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS FOR EACH AREA IN
 CALCULATIONS.
 32. SHT P3.1 DETAIL #03 RISER #33 SHALL
 NOT DRAIN THROUGH THE WET VENT FOR THE
 BATHROOM FIXTURES.ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 33. SHT P4.1 SUBMIT A WATER RISER
 DIAGRAM TO REFLECT THE PIPING FOR THE
 1ST AND 2ND FLOORS. SECTION 106.3.5.1.3.
 SHOW ALL PIPE SIZES, VALVES, ETC.
 34. SHT P4.3 GAS RISER DIAGRAM. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 SEPARATE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DEAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS. SOME SECTIONS DO NOT INDICAT
 THE LENGTHS. (SEE HIGHLIGHTED SECTIONS
 ON ONE SET OF PLANS)
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING IF USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTIONS 502 THRU 505.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 35. SHT P4.3 DETIAL 01 INDICATES A
 TYPICAL BASE OF STACK SOVENT. THIS IS
 NOT TYPICAL OF ANY BASE OF STACK FOR THE
 SOVENT SYSTEM. PLEASE CLARIFY. SECTION
 106.1.1.
 36. SHT P4.4 DETAIL 04 DOES NOT REFLECT
 THE FLOOR PLAN FOR THE WATER PIPING TO
 THE SHOWER AND TUB. NO DROPS FOR TUB AND
 SHOWER ARE SHOWN. PLEASE CORRELATE RISER
 AND FLOOR PLAN. SECTION 106.1.1.
 37. SHT P4.4 DETAIL 05 SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE THE RISER AND THE FLOOR
 PLAN. SECTION 106.1.1.
 38. SHT P4.4 DETAIL 06 DOES NOT REFLECT
 THE FLOOR PLAN FOR THE WATER PIPING TO
 THE SHOWER AND TUB. NO DROPS FOR TUB AND
 SHOWER ARE SHOWN. PLEASE CORRELATE RISER
 AND FLOOR PLAN. SECTION 106.1.1.
 39. SHT P4.4 DETAIL 07 DOES NOT REFLECT
 THE FLOOR PLAN. RISER SHOWS A TUB, BUT
 THE FLOOR PLAN SHOWS A SHOWER. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 106.1.1.
 40. SHT P4.4 DETAIL 08 DOES NOT RELFECT
 THE FLOOR PLAN. RISER SHOWS A TUB, BUT
 THE FLOOR PLAN SHOWS A SHOWER. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 106.1.1.
 41. SHT P4.5 DETAIL 06 DOES NOT REFLECT
 THE FLOOR PLAN. RISER SHOWS HOT & COLD
 STUBB OUTS ON THE DROP TO THE LAV AND
 SHOWER. PLEASE CORRELATE RISER AND THE
 FLOOR PLAN. SECTION 106.1.1.
 42. SHT P4.7 SANITARY RISER DIAGRAM FOR
 THE SECOND FLOOR BATHROOM DOES NOT
 REFLECT THE FLOOR PLAN. FIRST W/C SHOWN
 PRIOR TO 4" SAN. DOWN ON THE FLOOR PLAN,
 BUT ON THE OTHER SIDE OF THE 4" SAN.
 DOWN ON THE RISER DIAGRAM. HDCP W/C FOR
 THE WOMEN'S TOILET ROOM IS NOT SHOWN ON
 THE RISER. PLEASE CORRELATE THE RISER
 AND THE FLOOR PLAN. SECTION 106.1.1.
 43. SHT P4.7 DETAIL 02 SANT. RISER
 DIAGRAM FOR 2ND FLOOR PLAN. AIR
 ADMITTENCE VALVES ARE NOT APPROVED AS
 SHOWN. SEE SECTIONS 917.3.1 AND 917.3.2
 917.3.1 LOCATION OF BRANCH.
 THE HORIZONTAL BRANCH DRAIN SHALL
 CONNECT TO THE DRAINAGE STACK OR
 BUILDING DRAIN A MAXIMUM OF FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK.
 917.3.2 RELIEF VENT.
 THE HORIZONTAL BRANCH SHALL BE PROVIDED
 WITH A RELIEF VENT THAT SHALL CONNECT TO
 A VENT STACK, OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR. THE RELIEF
 VENT SHALL CONNECT TO THE HORIZONTAL
 BRANCH DRAIN BETWEEN THE STACK OR
 BUILDING DRAIN AND THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTED TO THE
 HORIZONTAL BRANCH DRAIN. THE RELIEF VENT
 SHALL BE SIZED IN ACCORDANCE WITH
 SECTION 916.2 AND INSTALLED IN
 ACCORDANCE WITH SECTION 905 . THE RELIEF
 VENT SHALL BE PERMITTED TO SERVE AS THE
 VENT FOR OTHER FIXTURE.
 44. SHT P4.7 DETAIL 01 SANT. RISER
 DIAGRAM COLLECTION DOES NOT REFLECT THE
 FLOOR PLAN. RISER SHOWS 10"(1600FU), BUT
 THE FLOOR PLAN SHOWS 8"(1000FU). THE
 BASE OF STACKS P/1, P/3, P/5, 9/7 DOES
 NOT REFLECT THE FLOOR PLAN FOR THE PRL
 PIPING. THE RISER DOES NOT SHOW THE
 CONNECTION FOR THE 5" COMBINATION
 WASTE/VENT STACK (NOTE 33). PLEASE
 CORRELATE INFORMATION ON THE RISERS AND
 THE FLOOR PLAN. SECTION 106.1.1.
 45. SHT P4.7 DETAIL 01 SANT. RISER
 DIAGRAM COLLECTION AIR ADMITTENCE VALVES
 ARE NOT APPROVED.SECTIONS 917.3.2 AND
 917.3.2.
 46. SHT P4.7 DETAIL 01 SANT. RISER
 DIAGRAM COLLECTION, PLEASE INDICATE
 WHERE THE CONTINUATION OF THE 2" UP TO
 SINK ON THE SECOND FLOOR IS LOCATED.
 SHOW PIPE SIZE, VENTING ETC. SECTION
 106.1.1.
 47. SHT P4.7 DETAILS 01 & 02 SHOW ALL
 PIPE SIZES OF ALL SECTIONS OF PIPE AND
 SHOW THE DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. TABLES 710.1(1) & 710.1(2).
 48. SHT P5.1 DETAIL 08 PLEASE INDICATE
 CONDENSATE DRAIN FOR CONDENSATE.
 CONDENSATE SHALL NOT CONNECT TO SANITARY
 PER MUNICIPAL CODE SECTION 90-125(5).
 CONDENSATE SHALL BE PIPED OUT OF THE
 BUILDING SEPARATELY AND CONNECT TO THE
 STORM, CATCH BASIN, OR A DRYWELL. IF ITS
 A ROOF UNIT, IT CAN DRAIN TO A ROOF
 DRAIN. PLEASE CLARIFY.SECTION 106.1.1.
 49. SHT P5.2 DETAIL 01 DOES NOT REFLECT
 ANY BASE OF STACKS SHOWN ON THE FLOOR
 PLAN. PLEASE CORRLEATE WITH FLOOR PLAN.
 SECTION 106.1.1.
 50. SHT P5.2 DETAIL 06 FILTER FOR THE
 ICE MACHINE SHALL COMPLY WITH NSF 42.
 PLEASE SUBMIT MANUF. SPECIFICATION
 SHEETS. SECTION 611.1
 51. SUBMIT A WATER RISER DIAGRAM TO
 REFLECT THE PIPING FOR THE 1ST AND 2ND
 FLOORS. SECTION 106.3.5.1.3.
 52. SUBMIT A WATER RISER DIAGRAM T0
 REFLECT THE PIPING ON THE 14 TH & 15TH
 FLOORS. SECTION 106.3.5.1.3.
 53. SUBMIT A GREASE WASTE ISOMETRIC
 RISER DIAGRAM. SECTION 106.3.5.1.3.
 54. SUBMIT A BUILDING STORM ISOMETRIC
 RISER DIAGRAM SHOWING ALL PIPE SIZES,
 RWL CONNECTIONS AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM, AS WELL AS
 VERTICAL STORM RISERS. SECTION
 106.1.5.1.3.
 55. GREASE INTERCEPTORS SHALL BE SIZED
 BY LYNN MASSON ENVIRONMENTAL COMPLIANCE
 MANAGER. CONTACT HER AT (561) 822-2271,
 OR BY FAX (561) 772-2279, OR BY E-MAIL
 [email protected]. SUBMIT THE
 DETERMINATION SHEET FOR REVIEW WHEN
 RESUBMITTING PLANS REVIEW IN
 CONSTRUCTION SERVICES. WASTER ORD. 3434.
 57. SUBMIT THE DESIGN MANUAL FOR THE
 SOVENT SYSTEM. THIS IS REQUIRED TO MAKE
 SURE ALL CRITERIA FOR THE SYSTEM IS
 BEING MET. SECTION 106.1.1.
 58. PLANS DO NOT SEEM TO BE COMPLETE
 THIS REVIEW AND MORE COMMENTS WILL BE
 FOUTHCOMING WHEN PLANS ARE RESUBMITTED
 AS MORE INFORMATION IS AVAILABLE AND
 ACCORDING TO THE RESPONSE FROM THIS
 REVIEW.
 59. SHTS A6.1.1 THRU A6.14.2 ALL
 ACCESSIBLE BATHROOMS. SOME UNITS
 INDICATE THAT THE SHOWER IS NOT AN ADA
 ACCESSIBLE PLUMBING FIXTURE. ALL SHOWERS
 PROVIDED IN ACCESSIBLE UNITS SHALL BE
 ACCESSIBLE PER SECTION 11-4.21. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.21 AND ALL SUBSECTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE SUBMIT THE HIGHLIGHTED SET OF
 PLUMBING PLANS FROM FIRST REVIEW FOR
 COMPARISON TO HELP EXPEDITE THE SECOND
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692