2006-04-24 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| MUNICIPAL CODE CITY WPB |
| |
| 1. PLEASE SUBMIT A CODE SUMMARY |
| INDICATING WHICH CODES THE BUILDING HAS |
| BEEN DESIGNED BY. |
| 2. PLEASE DECLARE OCCUPANCY FOR THE |
| BUILDING. SECTION 106.1.1. |
| 3. PLEASE SUBMIT A SUMMARY CHART |
| SUPPLYING INFORMATION ON THE AMOUNT OF |
| UNITS, UNIT TYPES WITH AMOUNT OF EACH, |
| AND SHOW COMPLIANCE WITH SECTIONS |
| 11-9.1.2, 11-9.1.3, 11-9.1.4 & 11-9.2.3. |
| INDICATE THE ROOM NUMBER FOR EACH |
| REQUIREMENT, IE: ACCESSIBLE ROOM, ROOMS |
| WITH ROLL IN SHOWERS, ACCOMODATIONS FOR |
| PERSONS WITH HEARING IMPAIRMENTS ETC. |
| THIS WILL BE REQUIRED FOR THE PERCENTAGE |
| FOR ALL UNITS. (HOTEL) |
| 4. PLEASE INDICATE HOW ALL THE UNITS |
| FROM THE PREVIOUS COMMENT WILL BE MADE |
| AVAILABLE, AND IF THESE UNITS WILL BE |
| SOLD AS CONDO'S WILL THEY BE MADE |
| AVAILABLE AT ALL TIMES. SECTION 106.1.1. |
| 5. PLEASE INDICATE UNIT LOCATIONS AND |
| ROOM NUMBERS CONSIDERED "CONDO |
| OCCUPANCY". FAIR HOUSING WILL BE |
| REQUIRED FOR THOSE UNITS. IF ALL UNITS, |
| ALL UNITS SHALL BE REQUIRED TO MEET |
| FHA-91 DESIGN MANUAL REQUIREMENTS ONE |
| THRU SEVEN. |
| 6. SHTS A2.91 7 A2.10.1 INDICATE THE |
| LOCATION OF ALL PRIMARY AND SECONDARY |
| DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| SUBSECTIONS. |
| 7. SHT A2.11.1 SHOW THE LOCATION OF |
| SECONDARY ROOF DRAINS FOR THE AREA SOUTH |
| OF THE ELEVATOR EQUIPMENT ROOM, RO2. |
| SECTION 1107. |
| 8. SHTS A6.1.1 THRU A6.14.2 ALL WATER |
| CLOSETS SHALL BE 1'6" OFF THE WALL TO |
| THE CENTER LINE OF THE FIXTURE. THIS IS |
| AN ABSOLUTE MENSUREMENT PER PAGE 6.5 FHA |
| DESIGN MANUAL, AND FIGURE 28 SECTION |
| 11.3.1 FBC-2004. MEASUREMENTS SHOWN ARE |
| 1'63/8" OR 1'6" MIN. PLEASE CORRECT THE |
| W/C MEASUREMENTS. |
| 9. SHTS A6.1.1 THRU A6.14.2 INDICATE THE |
| CORRECT HEIGHT OF THE LAV AS 34" AS |
| REQUIRED ON PAGE 7.52 FHA DESIGN MANUAL. |
| 10. SHTS A6.1.1 THRU A6.14.2 ALL |
| ACCESSIBLE UNITS SHOW THE FOLLOWING: |
| FOR W/C'S: |
| A. 11-4.16.5 FLUSH CONTROLS |
| B. 11-4.16.6 DISPENSERS |
| FOR LAVS: |
| A. 1-4.19.4 EXPOSED PIPES & SURFACES |
| FOR TUBS: |
| A. 11-4.20.5 CONTROLS |
| B. 11-4.20.6 SHOWER UNIT |
| FOR SHOWERS: |
| A. 11-4.21.3 SEAT |
| B. 11-4.21.4 GRAB BARS |
| C. 11-4.21.5 CONTROLS |
| D. 11-4.21.6 SHOWER UNIT |
| E. 11-4.21.7 CURBS |
| 11. SUBMIT A LEGEND SHOWING THE AMOUNT |
| OF UNITS, AND INDICATE UNIT TYPES. |
| INDICATE THE AMOUNT OF ACCESSIBLE UNITS, |
| AMOUNT OF UNITS WITH ROLL-IN SHOWER, |
| AMOUNT OF UNITS WITH ACCOMMODATIONS FOR |
| PERSONS WITH HEARING IMPAIRMENTS, AND |
| UNITS FOR HOTEL, MOTEL AND CONDOMINIUM |
| SPECIAL ACCESSIBILITY FEATURE. SECTIONS |
| 11-9.1.2, 11-9.1.3, 11-9.1.4 AND |
| 11-9.2.3. INDICATE THE UNIT NUMBERS FOR |
| EACH REQUIREMENT. |
| 12. SHTS A6.1.1 THRU A6.14.2 ALL |
| ACCESSIBLE UNITS, PER SECTION 11-9.2(7) |
| KITCHENETTS INDICATE PARALLEL APPROACH. |
| THIS IS NOT APPROVED PER SECTION |
| 11-4.24.5. FORWARD APPROACH IS REQUIRED, |
| AND CABINET DOORS ARE NOT APPROVED IN |
| THE CLEAR FLOOR SPACE. PLEASE SUBMIT AN |
| ELEVATION SHOWING COMPLIANCE WITH |
| SECTION 11-4.24 AND ALL SUBSECTIONS. |
| 13. SHTS A6.1.1 THRU A6.14.2 ALL FHA |
| UNITS WITH A 2ND BATHROOM, SHOW THE |
| OPENING DIMENSION FOR THE WATER CLOSET. |
| MINIMUM 33" REQUIRED. W/C SHALL BE 18" |
| OFF THE WALL TO CENTER OF FIXTURE, (IF |
| WALL ADJACENT TO FIXTURE), OR MINIMUM OF |
| 18" OFF ONE FIXTURE AND MINIMUM OF 15" |
| OFF THE OTHER FIXTURE. SEE PAGES 6.7, |
| 7.43, 7.44, 7.45, & 7.46. |
| 14. SHT A8.1.1 FINISH SCHEDULE FOR THE |
| COMMON AREA IS NOT COMPLETE. SECTION |
| 106.1.1. |
| 15. SHT A8.2.1 REINFORCING AT THE TUB, |
| SHOW REINFORCING AT THE HEAD OF THE TUB |
| PER PAGE 6.9 FHA DESIGN MANUAL. |
| 16. SHT P0.1 CODE IS FBC-2004. CHANGE |
| CODE REFERENCES. |
| 17. SHT P2.0 GAS PIPING FROM THE METER |
| TO THE GAS RISERS. ONLY ONE RISER SHOWN. |
| PLEASE CLARIFY. SECTION 106.1.1. |
| 18. SHTS P2.0 & P2.1 GREASE LINE INTO |
| THE BUILDING SHOWS NO RISER FROM BELOW |
| GRADE. SHT A2.1.1 DOES NOT SHOW A |
| KITCHEN ON THE FIRST FLOOR. PLEASE |
| CLARIFY. SECTION 106.1.1. |
| 19. SHT P2.1 GAS LINES SHOWN UNDER THE |
| SLAB OF THE BUILDING. PLEASE INDICATE |
| HOW THE PIPING WILL BE PRESSURE TESTED |
| AND INSPECTED, THEN AFTER THE PIPING |
| TEST AND INSPECTION, SHALL HAVE CONDUIT |
| INSTALLED OVER THE PIPE AS REQUIRED IN |
| SECTIONS 404.11 AND 406.4. SHOW THE |
| CONDUIT DETAIL SHOWING COMPLIANCE WITH |
| SECTION 404.11. |
| 20. SHT P2.1 5" COMBINATION WASTE/VENT |
| STACK, (#33) SHOWS 4" ON THE HORIZONTAL |
| OFFSET. PLEASE CLARIFY. SECTION 704.2 |
| THE SIZE OF THE DRAINAGE PIPING SHALL |
| NOT BE REDUCED IN THE DIRECTION OF FLOW. |
| 21. SHT P2.2 GAS RISER DIAGRAM INDICATES |
| THE GAS FOR THE KITCHEN FLOOR RISES UP |
| ABOVE THE SECOND FLOOR. ONLY ON RISER |
| SHOWN. PLEASE CORRELATE RISER AND FLOOR |
| PLAN. SECTION 106.1.1. |
| 22. SHT P2.2 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS PER |
| SECTION 1106 & 1107 AND ALL SUBSECTIONS. |
| SHOW SQUARE FOOTAGE AREA AND SHOW 1/2 |
| AREA OF ALL VERTICAL WALLS ADDED TO |
| CALCULATIONS. IF SECONDARY ROOF DRAINS |
| WILL BE SCUPPERS, THEY WILL BE SIZED PER |
| SECTIONS 1101.7, 1107.3 AND TABLE |
| 1106.7. THE SIZING OF SCUPPERS CAN NOT |
| BE DETERMINED WITH REFERENCE TO THE |
| DEFLECTION OF THE ROOF. PLEASE NOTE IN |
| CALCULATIONS. |
| 23. SHT P2.3 DOMESTIC WATER PUMP ROOM |
| INDICATES A FLOOR DRAIN. NO PIPING IS |
| SHOWN TO FLOOR DRAIN. SHOW PIPING ON THE |
| FLOOR PLAN, WITH ALL PIPE SIZE, VENTING, |
| TRAPS. SECTION 106.1.1. |
| 24. SHT P2.5 INDICATE THE LOCATION OF |
| THE SECONDARY DRAINS FOR THE AREAS |
| OUTSIDE UNITS T05 THRU T08. SUBMIT |
| CALCULATION FOR PRIMARY AND SECONDARY |
| DRAINS PER SECTIONS 1106 & 1107 AND ALL |
| SUBSECTION. SHOW AREA TO BE DRAINED FOR |
| EACH AREA DRAIN, AND SHOW 1/2 AREA OF |
| ALL VERTICAL WALL INCLUDING PARAPETS TO |
| EACH AREA. IF SECONDARY DRAINS ARE |
| SCUPPERS, INDICATE THAT THE SIZE OF THE |
| SCUPPERS HAVE BEEN CALCULATED PER |
| SECTIONS 1101.7, 1107.3 AND TABLE |
| 1106.7. THE SIZING OF THE SCUPPERS CAN |
| NOT BE DETERMINED WITHOUT REFERENCE TO |
| THE DEFLECTION OF THE ROOF. |
| 25. SHT P2.6 RWL'S ARE NOT IDENTIFIED IN |
| COLS. OUTSIDE UNIT T03. SECTION 106.1.1. |
| 26. SHT P2.16 AREA DRAINS OUTSIDE UNITS |
| P02 AND P04 INDICATE PIPING DROPING TO |
| THE 15TH FLOOR, BUT NO RWL SHOWN ON THE |
| 15TH FLOOR. PLEASE CLARIFY. SECTION |
| 106.1.1. |
| 27. SHT P2.16 INDICATE THE LOCATION OF |
| THE SECONDARY DRAINS FOR THE AREAS |
| OUTSIDE UNITS P02 THRU P04. SUBMIT |
| CALCULATION FOR PRIMARY AND SECONDARY |
| DRAINS PER SECTIONS 1106 & 1107 AND ALL |
| SUBSECTION. SHOW AREA TO BE DRAINED FOR |
| EACH AREA DRAIN, AND SHOW 1/2 AREA OF |
| ALL VERTICAL WALL INCLUDING PARAPETS TO |
| EACH AREA. IF SECONDARY DRAINS ARE |
| SCUPPERS, INDICATE THAT THE SIZE OF THE |
| SCUPPERS HAVE BEEN CALCULATED PER |
| SECTIONS 1101.7, 1107.3 AND TABLE |
| 1106.7. THE SIZING OF THE SCUPPERS CAN |
| NOT BE DETERMINED WITHOUT REFERENCE TO |
| THE DEFLECTION OF THE ROOF. |
| 28. SHT P2.22 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS PER |
| SECTIONS 1106 & 1107 AND ALL |
| SUBSECTIONS. IF SECONDARY ROOF DRAIN ARE |
| SCUPPERS, THEY WILL BE SIZED PER |
| SECTIONS 1101.7, 1107.3, AND TABLE |
| 1106.7. |
| 29. SHT P2.22 FLOOR DRAIN AT COOLING |
| TOWERS IS NOT AN APPROVED INDIRECT WASTE |
| RECEPTOR. SECTIONS 802.3 & 802.3.2. |
| FLOOR SINK OR HUB DRAIN REQUIRED. |
| RECEPTOR SHALL BE LOCATED UNDER COOLING |
| TOWER TO PREVENT STORM WATER FROM |
| ENTERING. |
| 30. SHT P2.23 SHOW THE LOCATION OF ALL |
| THE PRIMARY AND SECONDARY ROOF DRAINS. |
| SUBMIT CALCULATION FOR PRIMARY AND |
| SECONDARY ROOF DRAINS. SHOW THE AREA OF |
| EACH DRAIN AND INDICATE 1/2 AREA OF ALL |
| VERTICLE WALLS INCLUDING PARAPETS IN |
| CALCULATION. IF SECONDARY DRAINS ARE |
| SCUPPERS, THEY SHALL BE SIZED PER |
| SECTIONS 1101.7, 1107.3 AND TABLE |
| 1106.7. |
| 31. SHT P2.24 SUBMIT CALCULATION FOR |
| PRIMARY AND SECONDARY ROOF DRAINS PER |
| SECTION 1106 & 1107 WITH ALL |
| SUBSECTIONS. SHOW AREA OF EACH DRAIN AND |
| SHOW 1/2 AREA OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS FOR EACH AREA IN |
| CALCULATIONS. |
| 32. SHT P3.1 DETAIL #03 RISER #33 SHALL |
| NOT DRAIN THROUGH THE WET VENT FOR THE |
| BATHROOM FIXTURES.ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH |
| DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. |
| 33. SHT P4.1 SUBMIT A WATER RISER |
| DIAGRAM TO REFLECT THE PIPING FOR THE |
| 1ST AND 2ND FLOORS. SECTION 106.3.5.1.3. |
| SHOW ALL PIPE SIZES, VALVES, ETC. |
| 34. SHT P4.3 GAS RISER DIAGRAM. THE |
| FOLLOWING INFORMATION IS REQUIRED FOR |
| SEPARATE GAS PERMIT: |
| A. SUBMIT AN ISOMETRIC DEAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS. SOME SECTIONS DO NOT INDICAT |
| THE LENGTHS. (SEE HIGHLIGHTED SECTIONS |
| ON ONE SET OF PLANS) |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING IF USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTIONS 502 THRU 505. |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| 35. SHT P4.3 DETIAL 01 INDICATES A |
| TYPICAL BASE OF STACK SOVENT. THIS IS |
| NOT TYPICAL OF ANY BASE OF STACK FOR THE |
| SOVENT SYSTEM. PLEASE CLARIFY. SECTION |
| 106.1.1. |
| 36. SHT P4.4 DETAIL 04 DOES NOT REFLECT |
| THE FLOOR PLAN FOR THE WATER PIPING TO |
| THE SHOWER AND TUB. NO DROPS FOR TUB AND |
| SHOWER ARE SHOWN. PLEASE CORRELATE RISER |
| AND FLOOR PLAN. SECTION 106.1.1. |
| 37. SHT P4.4 DETAIL 05 SANITARY RISER |
| DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| PLEASE CORRELATE THE RISER AND THE FLOOR |
| PLAN. SECTION 106.1.1. |
| 38. SHT P4.4 DETAIL 06 DOES NOT REFLECT |
| THE FLOOR PLAN FOR THE WATER PIPING TO |
| THE SHOWER AND TUB. NO DROPS FOR TUB AND |
| SHOWER ARE SHOWN. PLEASE CORRELATE RISER |
| AND FLOOR PLAN. SECTION 106.1.1. |
| 39. SHT P4.4 DETAIL 07 DOES NOT REFLECT |
| THE FLOOR PLAN. RISER SHOWS A TUB, BUT |
| THE FLOOR PLAN SHOWS A SHOWER. PLEASE |
| CORRELATE RISER AND FLOOR PLAN. SECTION |
| 106.1.1. |
| 40. SHT P4.4 DETAIL 08 DOES NOT RELFECT |
| THE FLOOR PLAN. RISER SHOWS A TUB, BUT |
| THE FLOOR PLAN SHOWS A SHOWER. PLEASE |
| CORRELATE RISER AND FLOOR PLAN. SECTION |
| 106.1.1. |
| 41. SHT P4.5 DETAIL 06 DOES NOT REFLECT |
| THE FLOOR PLAN. RISER SHOWS HOT & COLD |
| STUBB OUTS ON THE DROP TO THE LAV AND |
| SHOWER. PLEASE CORRELATE RISER AND THE |
| FLOOR PLAN. SECTION 106.1.1. |
| 42. SHT P4.7 SANITARY RISER DIAGRAM FOR |
| THE SECOND FLOOR BATHROOM DOES NOT |
| REFLECT THE FLOOR PLAN. FIRST W/C SHOWN |
| PRIOR TO 4" SAN. DOWN ON THE FLOOR PLAN, |
| BUT ON THE OTHER SIDE OF THE 4" SAN. |
| DOWN ON THE RISER DIAGRAM. HDCP W/C FOR |
| THE WOMEN'S TOILET ROOM IS NOT SHOWN ON |
| THE RISER. PLEASE CORRELATE THE RISER |
| AND THE FLOOR PLAN. SECTION 106.1.1. |
| 43. SHT P4.7 DETAIL 02 SANT. RISER |
| DIAGRAM FOR 2ND FLOOR PLAN. AIR |
| ADMITTENCE VALVES ARE NOT APPROVED AS |
| SHOWN. SEE SECTIONS 917.3.1 AND 917.3.2 |
| 917.3.1 LOCATION OF BRANCH. |
| THE HORIZONTAL BRANCH DRAIN SHALL |
| CONNECT TO THE DRAINAGE STACK OR |
| BUILDING DRAIN A MAXIMUM OF FOUR BRANCH |
| INTERVALS FROM THE TOP OF THE STACK. |
| 917.3.2 RELIEF VENT. |
| THE HORIZONTAL BRANCH SHALL BE PROVIDED |
| WITH A RELIEF VENT THAT SHALL CONNECT TO |
| A VENT STACK, OR STACK VENT, OR EXTEND |
| OUTDOORS TO THE OPEN AIR. THE RELIEF |
| VENT SHALL CONNECT TO THE HORIZONTAL |
| BRANCH DRAIN BETWEEN THE STACK OR |
| BUILDING DRAIN AND THE MOST DOWNSTREAM |
| FIXTURE DRAIN CONNECTED TO THE |
| HORIZONTAL BRANCH DRAIN. THE RELIEF VENT |
| SHALL BE SIZED IN ACCORDANCE WITH |
| SECTION 916.2 AND INSTALLED IN |
| ACCORDANCE WITH SECTION 905 . THE RELIEF |
| VENT SHALL BE PERMITTED TO SERVE AS THE |
| VENT FOR OTHER FIXTURE. |
| 44. SHT P4.7 DETAIL 01 SANT. RISER |
| DIAGRAM COLLECTION DOES NOT REFLECT THE |
| FLOOR PLAN. RISER SHOWS 10"(1600FU), BUT |
| THE FLOOR PLAN SHOWS 8"(1000FU). THE |
| BASE OF STACKS P/1, P/3, P/5, 9/7 DOES |
| NOT REFLECT THE FLOOR PLAN FOR THE PRL |
| PIPING. THE RISER DOES NOT SHOW THE |
| CONNECTION FOR THE 5" COMBINATION |
| WASTE/VENT STACK (NOTE 33). PLEASE |
| CORRELATE INFORMATION ON THE RISERS AND |
| THE FLOOR PLAN. SECTION 106.1.1. |
| 45. SHT P4.7 DETAIL 01 SANT. RISER |
| DIAGRAM COLLECTION AIR ADMITTENCE VALVES |
| ARE NOT APPROVED.SECTIONS 917.3.2 AND |
| 917.3.2. |
| 46. SHT P4.7 DETAIL 01 SANT. RISER |
| DIAGRAM COLLECTION, PLEASE INDICATE |
| WHERE THE CONTINUATION OF THE 2" UP TO |
| SINK ON THE SECOND FLOOR IS LOCATED. |
| SHOW PIPE SIZE, VENTING ETC. SECTION |
| 106.1.1. |
| 47. SHT P4.7 DETAILS 01 & 02 SHOW ALL |
| PIPE SIZES OF ALL SECTIONS OF PIPE AND |
| SHOW THE DFU'S AS THEY ACCUMULATE IN THE |
| SYSTEM. TABLES 710.1(1) & 710.1(2). |
| 48. SHT P5.1 DETAIL 08 PLEASE INDICATE |
| CONDENSATE DRAIN FOR CONDENSATE. |
| CONDENSATE SHALL NOT CONNECT TO SANITARY |
| PER MUNICIPAL CODE SECTION 90-125(5). |
| CONDENSATE SHALL BE PIPED OUT OF THE |
| BUILDING SEPARATELY AND CONNECT TO THE |
| STORM, CATCH BASIN, OR A DRYWELL. IF ITS |
| A ROOF UNIT, IT CAN DRAIN TO A ROOF |
| DRAIN. PLEASE CLARIFY.SECTION 106.1.1. |
| 49. SHT P5.2 DETAIL 01 DOES NOT REFLECT |
| ANY BASE OF STACKS SHOWN ON THE FLOOR |
| PLAN. PLEASE CORRLEATE WITH FLOOR PLAN. |
| SECTION 106.1.1. |
| 50. SHT P5.2 DETAIL 06 FILTER FOR THE |
| ICE MACHINE SHALL COMPLY WITH NSF 42. |
| PLEASE SUBMIT MANUF. SPECIFICATION |
| SHEETS. SECTION 611.1 |
| 51. SUBMIT A WATER RISER DIAGRAM TO |
| REFLECT THE PIPING FOR THE 1ST AND 2ND |
| FLOORS. SECTION 106.3.5.1.3. |
| 52. SUBMIT A WATER RISER DIAGRAM T0 |
| REFLECT THE PIPING ON THE 14 TH & 15TH |
| FLOORS. SECTION 106.3.5.1.3. |
| 53. SUBMIT A GREASE WASTE ISOMETRIC |
| RISER DIAGRAM. SECTION 106.3.5.1.3. |
| 54. SUBMIT A BUILDING STORM ISOMETRIC |
| RISER DIAGRAM SHOWING ALL PIPE SIZES, |
| RWL CONNECTIONS AND SQUARE FOOTAGE AS IT |
| ACCUMULATES IN THE SYSTEM, AS WELL AS |
| VERTICAL STORM RISERS. SECTION |
| 106.1.5.1.3. |
| 55. GREASE INTERCEPTORS SHALL BE SIZED |
| BY LYNN MASSON ENVIRONMENTAL COMPLIANCE |
| MANAGER. CONTACT HER AT (561) 822-2271, |
| OR BY FAX (561) 772-2279, OR BY E-MAIL |
| [email protected]. SUBMIT THE |
| DETERMINATION SHEET FOR REVIEW WHEN |
| RESUBMITTING PLANS REVIEW IN |
| CONSTRUCTION SERVICES. WASTER ORD. 3434. |
| 57. SUBMIT THE DESIGN MANUAL FOR THE |
| SOVENT SYSTEM. THIS IS REQUIRED TO MAKE |
| SURE ALL CRITERIA FOR THE SYSTEM IS |
| BEING MET. SECTION 106.1.1. |
| 58. PLANS DO NOT SEEM TO BE COMPLETE |
| THIS REVIEW AND MORE COMMENTS WILL BE |
| FOUTHCOMING WHEN PLANS ARE RESUBMITTED |
| AS MORE INFORMATION IS AVAILABLE AND |
| ACCORDING TO THE RESPONSE FROM THIS |
| REVIEW. |
| 59. SHTS A6.1.1 THRU A6.14.2 ALL |
| ACCESSIBLE BATHROOMS. SOME UNITS |
| INDICATE THAT THE SHOWER IS NOT AN ADA |
| ACCESSIBLE PLUMBING FIXTURE. ALL SHOWERS |
| PROVIDED IN ACCESSIBLE UNITS SHALL BE |
| ACCESSIBLE PER SECTION 11-4.21. SUBMIT A |
| DETAIL SHOWING COMPLIANCE WITH SECTION |
| 11-4.21 AND ALL SUBSECTIONS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE SUBMIT THE HIGHLIGHTED SET OF |
| PLUMBING PLANS FROM FIRST REVIEW FOR |
| COMPARISON TO HELP EXPEDITE THE SECOND |
| REVIEW. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |