Plan Review Notes
Plan Review Notes For Permit 06010310
Permit Number 06010310
Review Stop M
Sequence Number 1
Notes
Date Text
2006-03-24 00:00:00DENIED:
 1.PLAN SHEET M0.1 MECHANICAL CODES,
 PLEASE NOTE, THE FOLLOWING CODES SHOULD
 READ AS FOLLOWS: NFPA 90A-2002, NFPA
 90B-2002.
  
 2.PLAN SHEET M2.1 EXHAUST FROM THE
 FIRE PUMP ROOM & THE TRASH ROOM
 TERMINATE OVER THE DOOR AREA.PER 2004
 FMC 401.5 EXHAUST OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FT FROM LOT
 LINES.WHERE OPENINGS FRONT ON A STREET
 OR PUBLIC WAY, THE DISTANCE SHALL BE
 MEASURED TO THE CENTERLINE OF THE STREET
 OR PUBLIC WAY.PER 2004 FMC 401.5.2
 OUTDOOR EXHAUST AIR SHALL NOT BE
 DIRECTED ONTO WALKWAYS OR CREATE A
 NUISANCE.
  
 3.PLAN SHEET M2.1 FRESH AIR INTAKE
 SHALL COMPLY WITH 2004 FMC 401.5 &
 410.5.1.
  
 4.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 TABLE 403.3.PROVIDE CALCUALTIONS FOR
 ALL COMMON, RESIDENTIAL, AND GARAGE
 AREAS.
  
 5.PLAN SHEET M2.2 EXHAUST TERMINATING
 FROM THE TRASH & RESTROOMS.PLEASE
 NOTE, THE TERMINATION IS BELOW A BALCONY
 WITH SLIDING GLASS DOORS.
  
 6.PLEASE CLARIFY RATING OF THE
 SEPARATION WALL BETWEEN THE TRASHOLD (RM
 218) & THE DIRECTOR OF SALES (RM 221).
 SHOW COMPLIANCE WITH NFPA 82-1999
 CHAPTER 3 SUB-SECTION 3-2.3. FIRE
 DAMPERS ARE NOT REQUIRED IN AREAS WHERE
 THE DUCT COMPLIES WITH 2004 FMC 607.5.3
 EXCEPTION #2 ITEMS 2.1 THROUGH 2.6.
 PLEASE ANNOTATE ON PLAN THE LOCATIONS
 THAT THIS WILL APPLY.
  
 7.PLAN SHEET M2.2 CLARIFY THE LINEN
 STORAGE AREA, INDICATE IF A LAUNDRY
 CHUTE WILL BE INSTALLED.
  
 8.PLEASE NOTE, LINEN & TRASH CHUTES
 SHALL COMPLY WITH NFPA 82-1999 CHAPTER 3
 SUB-SECTION 3-2.5.1, WHICH REQUIRES
 AUTOMATIC SPRINKLERS.
  
 9.PLAN SHEET M2.3, PLEASE INDICATE
 WHERE THE MAKE-UP AIR WILL COME FROM FOR
 THE GARAGE VENTILATION.
  
 10. PLANS FOR PARKING AREA (M2.3 & M2.4)
 DO NOT INDICATE WHERE THE CO SENOSRS
 WILL BE SET.PER 2004 FMC 404.1, THE
 ACTIVATION OF THE GARAGE EXHAUST BY
 CARBON MONOXIDE SENSORS SHALL BE AT A
 CONSENTRATION LEVEL NOT GREATER THAN
 25PPM. PLEASE INDICATE HOW THE SENSORS
 WILL BE TESTED.
  
 11. PLAN SHEET M2.5, M2.6, M2.16, &
 M2.17 INDICATE FIRE DAMPERS ON THE
 SUPPLY AND SMOKE EXHAUST DUCTS FOR THE
 COMMON AREAS. ACCORDING TO THE LEGEND ON
 PLAN SHEET M0.1 FIRE DAMPERS ARE THE
 ONLY DAMPERS INDICATED ON THE PLANS.
 PLAN SHEET M5.3, INDICATES THE FIRE
 DAMPERS DEPICTED ON THE PLANS SHOULD
 ACTUALLY BE COMBINATION FIRE/SMOKE
 DAMPERS.PLEASE VERIFY AND CORRELATE
 WITH SMOKE CONTROL SYSTEM.PLEASE
 INDICATE THE CORRECT SYMBOL AS INDICATED
 UNDER THE "MECHANICAL SYMBOLS" DEPICTED
 ON PLAN SHEET M0.1.
  
 12. PLAN SHEET M2.5, PLEASE CLARIFY THE
 SUPPLY AIR FROM AHU-1 WHICH SERVES THE
 CORRIDOR.IS THE INTENT OF THIS FOR
 COMPLIANCE WITH THE OUTSIDE AIR
 REQUIREMENTS OF 2004 FMC TABLE 403.3?
  
 13. PLAN SHEET M2.5 UNIT 503, PLEASE
 INDICATE LOCATION OF THE RETURN AIR BACK
 TO FCU-V5.
  
 14. PLAN SHEET M2.5, M2.6, M2.16, &
 M2.17 PLEASE INDICATE DUCT, GRILLE SIZE
 & CFM FOR THE SUPPLY DUCT TO THE
 BATHROOM AREAS.
  
 15. PLEASE NOTE DEPENDING ON THE
 RESPONSE TO ITEM 14 R/A TRANSFER GRILLS
 MAY NOT BE SIZED LARGE ENOUGH.
  
 16. PLAN SHEET M2.21 KEY NOTE 1
 REFERENCES DETAIL 07 ON PLAN SHEET M8.1.
 PLAN SHEET M8.1 WAS NOT SUBMITTED FOR
 REVIEW.
  
 17. PLAN SHEET M2.1 KEY NOTE 3 "RISER
 SIZE EQUAL TO VERTICAL RUN".PLEASE
 CLARIFY, "RISER SIZE EQUAL TO VERTICAL
 RUN", A RISER IS A VERTICAL RUN.SHOULD
 THIS READ, "RISER SIZE EQUAL TO
 HORIZONTAL RUN"?
  
 18. PLEASE SIZE ALL DUCTWORK AND PIPING.
  
 19. PLEASE PROVIDE ADDTIONAL INFORMATION
 ABOUT THE MECHANICAL ROOMS LOCATED ON
 THE ROOF (GENERATOR, AHU, PUMP COOLING
 TOWERS).ARE THESE AREAS ENCLOSED?
 PLEASE PROVIDE INFORMATION ON THE
 VENTILATION OF THESE AREAS SHOULD THEY
 BE ENCLOSED.
  
 20. PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORDIANCE WTIH 2004
 FBC CHAPTER 13.
  
 21. PLEASE PROVIDE SUBMITTALS FOR ALL
 EQUIPMENT & APPLIANCES.
  
 22. PLEASE PROVIDE FILL INFORMATION FOR
 THE EMERGENCY GENERATOR.
  