2006-03-24 00:00:00 | DENIED: |
| 1.PLAN SHEET M0.1 MECHANICAL CODES, |
| PLEASE NOTE, THE FOLLOWING CODES SHOULD |
| READ AS FOLLOWS: NFPA 90A-2002, NFPA |
| 90B-2002. |
| |
| 2.PLAN SHEET M2.1 EXHAUST FROM THE |
| FIRE PUMP ROOM & THE TRASH ROOM |
| TERMINATE OVER THE DOOR AREA.PER 2004 |
| FMC 401.5 EXHAUST OPENINGS SHALL BE |
| LOCATED A MINIMUM OF 10 FT FROM LOT |
| LINES.WHERE OPENINGS FRONT ON A STREET |
| OR PUBLIC WAY, THE DISTANCE SHALL BE |
| MEASURED TO THE CENTERLINE OF THE STREET |
| OR PUBLIC WAY.PER 2004 FMC 401.5.2 |
| OUTDOOR EXHAUST AIR SHALL NOT BE |
| DIRECTED ONTO WALKWAYS OR CREATE A |
| NUISANCE. |
| |
| 3.PLAN SHEET M2.1 FRESH AIR INTAKE |
| SHALL COMPLY WITH 2004 FMC 401.5 & |
| 410.5.1. |
| |
| 4.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH 2004 FMC |
| TABLE 403.3.PROVIDE CALCUALTIONS FOR |
| ALL COMMON, RESIDENTIAL, AND GARAGE |
| AREAS. |
| |
| 5.PLAN SHEET M2.2 EXHAUST TERMINATING |
| FROM THE TRASH & RESTROOMS.PLEASE |
| NOTE, THE TERMINATION IS BELOW A BALCONY |
| WITH SLIDING GLASS DOORS. |
| |
| 6.PLEASE CLARIFY RATING OF THE |
| SEPARATION WALL BETWEEN THE TRASHOLD (RM |
| 218) & THE DIRECTOR OF SALES (RM 221). |
| SHOW COMPLIANCE WITH NFPA 82-1999 |
| CHAPTER 3 SUB-SECTION 3-2.3. FIRE |
| DAMPERS ARE NOT REQUIRED IN AREAS WHERE |
| THE DUCT COMPLIES WITH 2004 FMC 607.5.3 |
| EXCEPTION #2 ITEMS 2.1 THROUGH 2.6. |
| PLEASE ANNOTATE ON PLAN THE LOCATIONS |
| THAT THIS WILL APPLY. |
| |
| 7.PLAN SHEET M2.2 CLARIFY THE LINEN |
| STORAGE AREA, INDICATE IF A LAUNDRY |
| CHUTE WILL BE INSTALLED. |
| |
| 8.PLEASE NOTE, LINEN & TRASH CHUTES |
| SHALL COMPLY WITH NFPA 82-1999 CHAPTER 3 |
| SUB-SECTION 3-2.5.1, WHICH REQUIRES |
| AUTOMATIC SPRINKLERS. |
| |
| 9.PLAN SHEET M2.3, PLEASE INDICATE |
| WHERE THE MAKE-UP AIR WILL COME FROM FOR |
| THE GARAGE VENTILATION. |
| |
| 10. PLANS FOR PARKING AREA (M2.3 & M2.4) |
| DO NOT INDICATE WHERE THE CO SENOSRS |
| WILL BE SET.PER 2004 FMC 404.1, THE |
| ACTIVATION OF THE GARAGE EXHAUST BY |
| CARBON MONOXIDE SENSORS SHALL BE AT A |
| CONSENTRATION LEVEL NOT GREATER THAN |
| 25PPM. PLEASE INDICATE HOW THE SENSORS |
| WILL BE TESTED. |
| |
| 11. PLAN SHEET M2.5, M2.6, M2.16, & |
| M2.17 INDICATE FIRE DAMPERS ON THE |
| SUPPLY AND SMOKE EXHAUST DUCTS FOR THE |
| COMMON AREAS. ACCORDING TO THE LEGEND ON |
| PLAN SHEET M0.1 FIRE DAMPERS ARE THE |
| ONLY DAMPERS INDICATED ON THE PLANS. |
| PLAN SHEET M5.3, INDICATES THE FIRE |
| DAMPERS DEPICTED ON THE PLANS SHOULD |
| ACTUALLY BE COMBINATION FIRE/SMOKE |
| DAMPERS.PLEASE VERIFY AND CORRELATE |
| WITH SMOKE CONTROL SYSTEM.PLEASE |
| INDICATE THE CORRECT SYMBOL AS INDICATED |
| UNDER THE "MECHANICAL SYMBOLS" DEPICTED |
| ON PLAN SHEET M0.1. |
| |
| 12. PLAN SHEET M2.5, PLEASE CLARIFY THE |
| SUPPLY AIR FROM AHU-1 WHICH SERVES THE |
| CORRIDOR.IS THE INTENT OF THIS FOR |
| COMPLIANCE WITH THE OUTSIDE AIR |
| REQUIREMENTS OF 2004 FMC TABLE 403.3? |
| |
| 13. PLAN SHEET M2.5 UNIT 503, PLEASE |
| INDICATE LOCATION OF THE RETURN AIR BACK |
| TO FCU-V5. |
| |
| 14. PLAN SHEET M2.5, M2.6, M2.16, & |
| M2.17 PLEASE INDICATE DUCT, GRILLE SIZE |
| & CFM FOR THE SUPPLY DUCT TO THE |
| BATHROOM AREAS. |
| |
| 15. PLEASE NOTE DEPENDING ON THE |
| RESPONSE TO ITEM 14 R/A TRANSFER GRILLS |
| MAY NOT BE SIZED LARGE ENOUGH. |
| |
| 16. PLAN SHEET M2.21 KEY NOTE 1 |
| REFERENCES DETAIL 07 ON PLAN SHEET M8.1. |
| PLAN SHEET M8.1 WAS NOT SUBMITTED FOR |
| REVIEW. |
| |
| 17. PLAN SHEET M2.1 KEY NOTE 3 "RISER |
| SIZE EQUAL TO VERTICAL RUN".PLEASE |
| CLARIFY, "RISER SIZE EQUAL TO VERTICAL |
| RUN", A RISER IS A VERTICAL RUN.SHOULD |
| THIS READ, "RISER SIZE EQUAL TO |
| HORIZONTAL RUN"? |
| |
| 18. PLEASE SIZE ALL DUCTWORK AND PIPING. |
| |
| 19. PLEASE PROVIDE ADDTIONAL INFORMATION |
| ABOUT THE MECHANICAL ROOMS LOCATED ON |
| THE ROOF (GENERATOR, AHU, PUMP COOLING |
| TOWERS).ARE THESE AREAS ENCLOSED? |
| PLEASE PROVIDE INFORMATION ON THE |
| VENTILATION OF THESE AREAS SHOULD THEY |
| BE ENCLOSED. |
| |
| 20. PROVIDE ENERGY AND MANUAL J |
| CALCULATIONS IN ACCORDIANCE WTIH 2004 |
| FBC CHAPTER 13. |
| |
| 21. PLEASE PROVIDE SUBMITTALS FOR ALL |
| EQUIPMENT & APPLIANCES. |
| |
| 22. PLEASE PROVIDE FILL INFORMATION FOR |
| THE EMERGENCY GENERATOR. |
| |