Plan Review Notes
Plan Review Notes For Permit 06010310
Permit Number 06010310
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-04-28 00:00:00******DENIED******
  
 1) FIRE DEPARTMENT CONNECTIONS SHALL BE
 LOCATED NO FURTHER THAN 150' FROM A FIRE
 HYDRANT.
  
 2) BUILDING SHALL MEET ALL REQUIREMENTS
 FOR HIGHRISE STRUCTURES IN ACCORDANCE
 WITH APPLICABLE BUILDING CODES, AND NFPA
 101, CHAPTER 11.
  
 3) IN ADDITION TO ELECTRONIC
 SUPERVISION, DOUBLE CHECK DETECTOR
 ASSEMBLY SHALL BE SECURED WITH CHAIN AND
 LOCK.
  
 4) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 5) INCORRECT CODE EDITIONS ARE
 REFERENCED ON SHT M0.1. AS PART OF LIFE
 SAFETY, MEANS OF EGRESS TO COMPLY WITH
 NFPA 101, 2003 EDITION. NFPA 13, AND
 NFPA 72, 2002 EDITIONS SHALL BE
 REFERENCED.
  
 6) PLEASE VERIFY THE WIDTH OF DOOR 100B
 THAT ENTERS THE LOBBY.
  
 7) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN BUILDING REACHES (3) STORIES OR 30'
 IN HEIGHT.
  
 8) STANDPIPE CONNECTIONS TO BE 2 1/2"- 1
 1/2" REDUCER WITH CHAINS.
  
 9) WARNING SIGNS ARE REQUIRED IN
 ELEVATOR LOBBIES.
  
 10) PLEASE INDICATE ALL ELEVATORS THAT
 ARE STRETCHER ACCESSIBLE.
  
 11) SIGNS SHALL BE PROVIDED IN ALL
 STAIRWELLS INDICATING TOP, BOTTOM, FLOOR
 IDENTITY AND ROOF ACCESS.
  
 12) NO CUTTING OR WELDING OPERATIONS ARE
 PERMITTED WITHOUT APPROVAL OF THE BUREAU
 OF FIRE PREVENTION AND COMPLIANCE WITH
 NFPA 51B.
  
 13) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND GUARDS.
  
 14) IS THERE A DOOR LOCATED AT THE
 BOTTOM OF STAIR #1 AT EXIT CORRIDOR 112?
  
 THERE IS NOT ONE SHOWN.
  
 15) PLEASE PROVIDE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS IN TERMS OF CLASS A,B OR C.
  
 16) THE PARKING GARAGE SHALL COMPLY WITH
 APPLICABLE BUILDING CODES AND NFPA 88A.
  
 17) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 18) PLEASE INDICATE THE QUANTITY AND
 TYPE OF CONTENTS THAT WILL BE STORED IN
 POOL EQUIPMENT ROOM.
  
 19) COOLING TOWERS SHALL COMPLY WITH
 NFPA 214.
  
 20) NO STORAGE ALLOWED IN ELECTRICAL OR
 MECHANICAL EQUIPMENT ROOMS THAT ARE
 SUBJECT TO SERVICING AND INSPECTIONS.
  
 21) PLEASE INDICATE ON PLANS REGARDING
 POOL DECK AREA TO BE SLIP RESISTANT. IN
 ADDITION, PROVIDE OCCUPANT LOAD FOR SAME
 AREA.
  
 22) ADDRESS IS REQUIRED ON BUILDING.
 PLEASE ILLUSTRATE OF PROVIDE NOTE TO
 THIS EFFECT ON ELEVATION SHEETS.
  
 23) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241. JOB
 SITE SHALL BE CLEANED OF DEBRIS DAILY.
  
 24) SOFFITS SHALL NOT INTERFERE WITH
 FIRE PROTECTION EQUIPMENT OR DEVICES.
  
 25) FIRE EXTINGUISHER CABINETS SHALL BE
 INSTALLED AT DISTANCES NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
 26) NO MENTION ON DOOR SCHEDULES
 REGARDING UL CERTIFIED CLOSERS ON RATED
 DOORS.
  
 27) ELEVATORS TO COMPLY WITH ASME A17.1.
  
 28) PLEASE PROVIDE ADDITIONAL
 INFORMATION AND CUT SHEETS FOR CO
 SENSORS IN PARKING GARAGE AREAS.
  
 29) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 30) PLEASE ADD THE STACK EFFECT WORDING
 TO THE MECHANICAL PLANS.
  
 31) PLEASE CORRECT CODE EDITIONS ON ALL
 SHEETS.
  
 32) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 33) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE PUMP, FUEL AND
 ASSOCIATED EQUIPMENT.
  
 34) PLEASE PROVIDE INFORMATION THAT
 WOULD SUPPORT THE APPROVAL OF A 750 GPM
 FIRE PUMP SERVICING A 21 STORY BUILDING.
  
  
 35) BUILDING SHALL BE FULLY FIRE
 SPRINKLER PROTECTED. ANY AREAS NOT PART
 OF THIS SCOPE OF WORK MAY REQUIRE
 REMODEL ONCE OCCUPIED BY FUTURE TENANT.
  
 36) PLEASE INCLUDE LIFE SAFETY SHEETS TO
 ILLUSTRATE ALL ASPECTS OF MEANS OF
 EGRESS INCLUDING MAXIMUM TRAVEL
 DISTANCES.
  
 37) PLEASE INCLUDE THE FIRE SPRINKLER
 LAYOUT FOR TRASH AND LAUNDRY CHUTES.
  
 38) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
 CERTIFICATE OR APPROVED COPY OF SUCH
 SHALL BE AVAILABLE PRIOR TO OR AT THE
 TIME OF FIRE ALARM FINAL.
  
 39) FIRE DEPARTMENT CONNECTIONS ARE
 BEING SHOWN ON THE BUILDING AND FIRE
 BACK FLOW PREVENTER ON FP 4.1. ARE THERE
 A TOTAL OF (3) CONNECTIONS?
  
 40) FIRE ALARM SYSTEM TO MEET THE NFPA
 72 REQUIREMENTS FOR SURVIVABILITY.
  
 41) PLANS DON'T APPEAR TO SHOW COMPLETE
 FIRE ALARM EQUIPMENT LAYOUT ON
 ELECTRICAL SHEETS.
  
 42) SMOKE DETECTORS IN LIVING UNITS ARE
 REQUIRED TO BE SINGLE STATION TYPE. ALL
 OTHER DEVICES SHALL BE TIED INTO THE
 FIRE ALARM SYSTEM.
  
 43) PLEASE PROVIDE FURTHER
 INFORMATION/CUT SHEETS FOR SMOKE GUARD
 SHUTTERS THAT ARE TIED INTO FIRE ALARM
 SYSTEM.
  
 44) THE GENERATOR SHALL COMPLY WITH NFPA
 110, STANDARD FOR EMERGENCY AND STANDBY
 POWER SYSTEMS.
  
 45) SMOKE DETECTORS SHALL BE LOCATED A
 MINIMUM OF (3)' FROM HVAC DIFFUSERS.
  
 46) FIRE ALARM SYSSTEM SHALL BE CLASS A
 OR FULLY ADDRESSABLE.
  
 47) ALL SHAFTS THAT ARE LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE MARKED
 SHAFTWAY IN "6" IN CHARACTERS.
  
 48) ALL FIRE DOORS/WINDOWS TO COMPLY
 WITH NFPA 80. PLEASE ADD NOTE TO PLANS.
  
 49) EXITS SIGNS SHALL BE LOCATED AT
 DISTANCES NOT TO EXCEED 100'.
  
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  