2006-04-28 00:00:00 | ******DENIED****** |
| |
| 1) FIRE DEPARTMENT CONNECTIONS SHALL BE |
| LOCATED NO FURTHER THAN 150' FROM A FIRE |
| HYDRANT. |
| |
| 2) BUILDING SHALL MEET ALL REQUIREMENTS |
| FOR HIGHRISE STRUCTURES IN ACCORDANCE |
| WITH APPLICABLE BUILDING CODES, AND NFPA |
| 101, CHAPTER 11. |
| |
| 3) IN ADDITION TO ELECTRONIC |
| SUPERVISION, DOUBLE CHECK DETECTOR |
| ASSEMBLY SHALL BE SECURED WITH CHAIN AND |
| LOCK. |
| |
| 4) LIFE SAFETY SHALL COMPLY WITH NFPA |
| 101, 2003 EDITION. |
| |
| 5) INCORRECT CODE EDITIONS ARE |
| REFERENCED ON SHT M0.1. AS PART OF LIFE |
| SAFETY, MEANS OF EGRESS TO COMPLY WITH |
| NFPA 101, 2003 EDITION. NFPA 13, AND |
| NFPA 72, 2002 EDITIONS SHALL BE |
| REFERENCED. |
| |
| 6) PLEASE VERIFY THE WIDTH OF DOOR 100B |
| THAT ENTERS THE LOBBY. |
| |
| 7) TEMPORARY STANDPIPES ARE REQUIRED |
| WHEN BUILDING REACHES (3) STORIES OR 30' |
| IN HEIGHT. |
| |
| 8) STANDPIPE CONNECTIONS TO BE 2 1/2"- 1 |
| 1/2" REDUCER WITH CHAINS. |
| |
| 9) WARNING SIGNS ARE REQUIRED IN |
| ELEVATOR LOBBIES. |
| |
| 10) PLEASE INDICATE ALL ELEVATORS THAT |
| ARE STRETCHER ACCESSIBLE. |
| |
| 11) SIGNS SHALL BE PROVIDED IN ALL |
| STAIRWELLS INDICATING TOP, BOTTOM, FLOOR |
| IDENTITY AND ROOF ACCESS. |
| |
| 12) NO CUTTING OR WELDING OPERATIONS ARE |
| PERMITTED WITHOUT APPROVAL OF THE BUREAU |
| OF FIRE PREVENTION AND COMPLIANCE WITH |
| NFPA 51B. |
| |
| 13) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| REQUIREMENTS FOR HANDRAILS AND GUARDS. |
| |
| 14) IS THERE A DOOR LOCATED AT THE |
| BOTTOM OF STAIR #1 AT EXIT CORRIDOR 112? |
| |
| THERE IS NOT ONE SHOWN. |
| |
| 15) PLEASE PROVIDE MINIMUM INTERIOR |
| FINISH CLASSIFICATION FOR WALLS AND |
| CEILINGS IN TERMS OF CLASS A,B OR C. |
| |
| 16) THE PARKING GARAGE SHALL COMPLY WITH |
| APPLICABLE BUILDING CODES AND NFPA 88A. |
| |
| 17) STAIRS ARE TO BE KEPT UP WITH |
| CONSTRUCTION. |
| |
| 18) PLEASE INDICATE THE QUANTITY AND |
| TYPE OF CONTENTS THAT WILL BE STORED IN |
| POOL EQUIPMENT ROOM. |
| |
| 19) COOLING TOWERS SHALL COMPLY WITH |
| NFPA 214. |
| |
| 20) NO STORAGE ALLOWED IN ELECTRICAL OR |
| MECHANICAL EQUIPMENT ROOMS THAT ARE |
| SUBJECT TO SERVICING AND INSPECTIONS. |
| |
| 21) PLEASE INDICATE ON PLANS REGARDING |
| POOL DECK AREA TO BE SLIP RESISTANT. IN |
| ADDITION, PROVIDE OCCUPANT LOAD FOR SAME |
| AREA. |
| |
| 22) ADDRESS IS REQUIRED ON BUILDING. |
| PLEASE ILLUSTRATE OF PROVIDE NOTE TO |
| THIS EFFECT ON ELEVATION SHEETS. |
| |
| 23) CONSTRUCTION, ALTERATION AND |
| DEMOLITION TO COMPLY WITH NFPA 241. JOB |
| SITE SHALL BE CLEANED OF DEBRIS DAILY. |
| |
| 24) SOFFITS SHALL NOT INTERFERE WITH |
| FIRE PROTECTION EQUIPMENT OR DEVICES. |
| |
| 25) FIRE EXTINGUISHER CABINETS SHALL BE |
| INSTALLED AT DISTANCES NOT TO EXCEED 75' |
| TRAVEL DISTANCE. |
| |
| 26) NO MENTION ON DOOR SCHEDULES |
| REGARDING UL CERTIFIED CLOSERS ON RATED |
| DOORS. |
| |
| 27) ELEVATORS TO COMPLY WITH ASME A17.1. |
| |
| 28) PLEASE PROVIDE ADDITIONAL |
| INFORMATION AND CUT SHEETS FOR CO |
| SENSORS IN PARKING GARAGE AREAS. |
| |
| 29) DUCT SMOKE DETECTORS SHALL INITIATE |
| A GENERAL FIRE ALARM IN ACCORDANCE WITH |
| LOCAL REQUIREMENTS. |
| |
| 30) PLEASE ADD THE STACK EFFECT WORDING |
| TO THE MECHANICAL PLANS. |
| |
| 31) PLEASE CORRECT CODE EDITIONS ON ALL |
| SHEETS. |
| |
| 32) SEPARATE SHOP DRAWINGS AND PERMITS |
| ARE REQUIRED FOR FIRE SPRINKLER AND FIRE |
| ALARM SYSTEMS. |
| |
| 33) SEPARATE SHOP DRAWINGS AND PERMITS |
| REQUIRED FOR FIRE PUMP, FUEL AND |
| ASSOCIATED EQUIPMENT. |
| |
| 34) PLEASE PROVIDE INFORMATION THAT |
| WOULD SUPPORT THE APPROVAL OF A 750 GPM |
| FIRE PUMP SERVICING A 21 STORY BUILDING. |
| |
| |
| 35) BUILDING SHALL BE FULLY FIRE |
| SPRINKLER PROTECTED. ANY AREAS NOT PART |
| OF THIS SCOPE OF WORK MAY REQUIRE |
| REMODEL ONCE OCCUPIED BY FUTURE TENANT. |
| |
| 36) PLEASE INCLUDE LIFE SAFETY SHEETS TO |
| ILLUSTRATE ALL ASPECTS OF MEANS OF |
| EGRESS INCLUDING MAXIMUM TRAVEL |
| DISTANCES. |
| |
| 37) PLEASE INCLUDE THE FIRE SPRINKLER |
| LAYOUT FOR TRASH AND LAUNDRY CHUTES. |
| |
| 38) FIRE ALARM SYSTEM SHALL BE UL |
| CERTIFIED FOR CENTRAL STATION SERVICE. |
| CERTIFICATE OR APPROVED COPY OF SUCH |
| SHALL BE AVAILABLE PRIOR TO OR AT THE |
| TIME OF FIRE ALARM FINAL. |
| |
| 39) FIRE DEPARTMENT CONNECTIONS ARE |
| BEING SHOWN ON THE BUILDING AND FIRE |
| BACK FLOW PREVENTER ON FP 4.1. ARE THERE |
| A TOTAL OF (3) CONNECTIONS? |
| |
| 40) FIRE ALARM SYSTEM TO MEET THE NFPA |
| 72 REQUIREMENTS FOR SURVIVABILITY. |
| |
| 41) PLANS DON'T APPEAR TO SHOW COMPLETE |
| FIRE ALARM EQUIPMENT LAYOUT ON |
| ELECTRICAL SHEETS. |
| |
| 42) SMOKE DETECTORS IN LIVING UNITS ARE |
| REQUIRED TO BE SINGLE STATION TYPE. ALL |
| OTHER DEVICES SHALL BE TIED INTO THE |
| FIRE ALARM SYSTEM. |
| |
| 43) PLEASE PROVIDE FURTHER |
| INFORMATION/CUT SHEETS FOR SMOKE GUARD |
| SHUTTERS THAT ARE TIED INTO FIRE ALARM |
| SYSTEM. |
| |
| 44) THE GENERATOR SHALL COMPLY WITH NFPA |
| 110, STANDARD FOR EMERGENCY AND STANDBY |
| POWER SYSTEMS. |
| |
| 45) SMOKE DETECTORS SHALL BE LOCATED A |
| MINIMUM OF (3)' FROM HVAC DIFFUSERS. |
| |
| 46) FIRE ALARM SYSSTEM SHALL BE CLASS A |
| OR FULLY ADDRESSABLE. |
| |
| 47) ALL SHAFTS THAT ARE LARGE ENOUGH FOR |
| PERSONS TO FALL INTO MUST BE MARKED |
| SHAFTWAY IN "6" IN CHARACTERS. |
| |
| 48) ALL FIRE DOORS/WINDOWS TO COMPLY |
| WITH NFPA 80. PLEASE ADD NOTE TO PLANS. |
| |
| 49) EXITS SIGNS SHALL BE LOCATED AT |
| DISTANCES NOT TO EXCEED 100'. |
| |
| |
| |
| MIKE WENNERGREN, CAPTAIN/WPBFR |
| FIRE PLAN REVIEW (561) 805-6722 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |