Date |
Text |
2006-04-10 00:00:00 | IN REVIEW |
| ******** UNSAT ********** |
| |
| THE HARRICKHOTEL / CONDO |
| |
| |
| 1) NOTE: PLEASE BE SURE TO REFERENCE ALL |
| THE CURRENT CODE IN EFFECT AS FOLLOWS. |
| NFPA-20 (2002), NFPA-110 (2002). OTHERS |
| ARE SHOWN CURRENT TO DATE. |
| |
| 2) NOTE: PLEASE SEE "KEY NOTES" ON E1.1, |
| #4 SEEMS TO BE #1, AND #1 SEEMS TO BE |
| IDENTIFIED IN TWO LOCATIONS? PLEASE |
| CORRELATE. |
| |
| 3) NOTE: PLEASE CLARIFY AREAS INCLUDING |
| FIRST FLOOR WHICH MENTIONS A FUTURE |
| TENANT BUILD OUT YET, THIS ARE SEEMS TO |
| BE THE LOBBY AREA OF THE HOTEL/ CONDO. |
| HOW IS THIS TENANT BLD OUT? |
| |
| 4) NOTE: PLEASE PROVIDE ALL ROOM AND |
| AREA DESIGNATIONS ON PLANS. |
| PLEASE ALSO PROVIDE ALL AREA AND ROOM |
| DESIGNATIONS FOR UNITS AS SOME CODE |
| COMPLIANCE ITEMS CAN NOT BE VERIFIED AT |
| THIS TIME. |
| 215.5 |
| |
| 5) NOTE: PLEASE CORRELATE ALL DOORS FOR |
| ELECTRICAL ROOMS FOR OUT SWING. PLEASE |
| SEE ELECTRICAL PLANS INDICATE THE |
| CORRECT OUT-SWING FOR MAIN ELECTRICAL |
| ROOM; HOWEVER ARCHITECTURAL PLANS SHOW |
| DOORS SWINGING INWARDS. |
| PLEASE ALSO PLACE NOTE ON PLANS FOR |
| REQUIRED PANIC HARDWARE. |
| 110.26 |
| PLEASE ALSO SEE ANY INTERFERENCE WITH |
| MINIMUM WIDTHS AND EGRESS PATHS WHICH |
| MAY BE AFFECTED. |
| PLEASE PROVIDE NOTE FOR PANIC HARDWARE |
| WHICH WILL BE REQUIRED. |
| 6) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM |
| SHALL CONTAIN TWICE THE CLEARANCES |
| REQUIRED PER 110.26 FOR ATS EQUIPMENT |
| PER NFPA-110 7.2.2.1. |
| THIS WILL AFFECT LAYOUT AS SHOWN. |
| |
| 7) NOTE: PLEASE SEE 6.24* FOR MANUAL |
| MEANS OF DISCONNECT REQUIRED FOR ATS |
| DEVICES. |
| CAN NOT VERIFY AT THIS TIME. |
| |
| 8) NOTE: PLEASE SEE 7.2.1.1 FOR MIN 2HR |
| RATINGS FOR EPSS EQUIPMENT. NFPA-110 |
| |
| 9) NOTE: PLEASE SEE COLOR CODING OF |
| 277/480V SYSTEMS SHALL BE "BROWN, |
| PURPLE, AND YELLOW". ORANGE IS ONLY FOR |
| HIGH-LEG SYSTEMS AND IS NOT PERMITTED |
| FOR 277/480V. |
| 215, 90.4. |
| |
| 10) NOTE: PLEASE KNOW, "LIGHTNING |
| PROTECTION"SYSTEM AS SHOWN IF |
| INSTALLED BY A SUB CONTRACTOR WILL |
| REQUIRED THIS TO BE PULLED UNDER A |
| SEPARATE PERMIT. |
| |
| 11) NOTE: PLEASE SEE NFPA-1107.3.3* |
| THE INTENSITY OF ILLUMINATION IN THE |
| ROOM HOUSING THE EPS EQUIPMENT FOR LEVEL |
| 1 SHALL BE 32.3 LUX (30 FT-CANDLES). |
| PLEASE SHOW DETAIL. |
| |
| 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR |
| ALL EPS EQUIPMENT. (ATS). PLEASE SEE |
| 6.5.2 NFPA-110. |
| UNABLE TO VERIFY AT THIS TIME. |
| |
| 13) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| SPECS/CUT SHEETS FOR ALL EQUIPMENT: |
| ATS'S, GENERATOR, FIRE PUMP FIRE PUMP |
| CONTROLLER, SUB-BASE FUEL TANK ETC. |
| PLEASE SEE OTHER COMMENTS AND KNOW THAT |
| MANY ITEMS FOR CODE COMPLIANCE CAN NOT |
| BE REVIEW AT THIS TIME DUE TO THESE |
| ITEMS NOT BEING SUBMITTED FOR REVIEW. |
| |
| |
| |
| 14) NOTE: PLEASE SEE NFPA-20 7.2FOR |
| LOCATION OF FP CONTROLLER, HEIGHT, NEMA |
| TYPE 2 ENCLOSURES AND ROOM CONTAINING A |
| FLOOR DRAIN. |
| |
| 15) NOTE:PLEASE NOTE ON PLANS THE |
| ACCEPTANCE OF THE EPS AS REQUIRED IN |
| NFPA-110 7.13. |
| |
| |
| 16) NOTE: PLEASE PROVIDE NOTE ON PLANS |
| WHICH PROHIBITS THE INSTALLATION OF ANY |
| ELECTRICAL CONDUITS ETC IN STAIRS UNLESS |
| SPECIFICALLY DESIGNATED TO THE STAIRS. |
| PLEASE ALSO PROVIDE NOTE FOR ELEVATOR |
| EQUIPMENT ROOMS. |
| 215.5 |
| |
| |
| 17) NOTE: PLEASE SUBMIT WIND LOAD |
| CALCULATIONS FOR ALL SITE LIGHTING POLES |
| INCLUSIVE OF ATTACHED LIGHT FIXTURES. |
| PLEASE KNOW, THIS SHOULD INCLUDE ANY |
| POLE FIXTURES ON POOL DECK/ROOF |
| LEVEL(S). |
| THESE CALCULATIONS WHICH ARE REQUIRED AT |
| THIS TIME SHALL MEET THE 2004 FBC WITH |
| RESPECT TO WIND PRESSURES AND DESIGNS |
| 140 MPH. |
| |
| 18) NOTE: PLEASE SEE GFI PROTECTION |
| REQUIRED IN POOL AREAS FOR CIRCUITS |
| EE22-26., PL-22 /27 |
| |
| 19) NOTE: PLEASE SEE FIXTURES ON FIXTURE |
| SCHEDULE WHICH INDICATE 120V TYPE |
| FIXTURES IN POOL AREAS, YET THESE ARE |
| CIRCUITED TO THE 277/480V PANELS?? |
| PLEASE SEE THE CODE DOES NOT SEE TO |
| PROVIDE COMMENTARY FOR ALLOWING 277/480V |
| LIGHTING IN CLOSE PROXIMITY TO POOL |
| AREAS. |
| PLEASE VERIFY FIXTURES TYPES AND |
| VOLTAGES AND ADJUST PLANS AND SCHEDULES |
| AS NEEDED. |
| 680, 215.5. |
| |
| 20) NOTE: PLEASE SEE NOTE TO BE PROVIDED |
| ON ALL E-2.09AB FOR MINIMUM CLEARANCES |
| FOR POOL AREA FIXTURES. PLEASE 680.22 |
| FOR HIGH VOLTAGE FIXTURES (5FT MIN W/ |
| GFI PROTECTION AND 10FT MIN FOR LOW |
| VOLTAGE TYPE FIXTURES. 411.4 |
| |
| |
| 21) NOTE: PLEASE SEE FIXTURE AS T-1 |
| SHOWN IN FIRE PUMP ROOM COULD NOT BE |
| LOCATED ON SCHEDULE. PLEASE KNOW AND |
| BATTERY BACK UP FIXTURE OF SOME SORT |
| WILL BE REQUIRED. THIS FIXTURE AS SHOWN |
| SEEMS TO BE SHADED WHICH LENDS |
| IDENTIFICATION TO MANY OTHER FIXTURES ON |
| PLANS WHICH ARE SHADED AND ARE FIXTURES |
| WITH BATTERY BACK UP. |
| NFPA-20, LS 101 NFPA-70 |
| |
| 22) NOTE:PLEASE SEE NFPA-20.6.2.2 |
| WHICH REQUIRES A MIN OF 8HRS RUNNING @ |
| 100% LOAD FOR FIRE PUMP. PLEASE ALSO |
| BEAR IN MIND THE MINIMUM 100% LOADS FOR |
| ALL OTHER LEGALLY REQUIRED STAND-BY |
| ITEMS |
| |
| 23) NOTE: PLEASE VERIFY POWER LAYOUT FOR |
| FLOORS 1-4. 16-21 SHOWN ON E-2.16, AND |
| 5-15, ? |
| 215.5 |
| |
| 24) NOTE: PLEASE SEE 2.23 WHICH SEEM TO |
| SHOW TWO DIFFERENT B-1 FIXTURES. PLEASE |
| CORRELATE AND SEE ONE SHADED AND THE |
| OTHER IS NOT. |
| REDLINED AT LOCATION(S). |
| |
| 25) NOTE: PLEASE PROVIDE A BATTERY BACK |
| FIXTURE OF SOME SORT IN ELEVATOR |
| EQUIPMENT ROOMS. |
| LS 101 7.8,7.9,700.16 |
| |
| 26) NOTE: PLEASE SEE E2.3, WHICH SHOWS |
| WHAT APPEARS TO BE FCU LOCATED IN FRONT |
| OFPANEL EH-3? |
| PLEASE VERIFY IF UNIT IS CEILING |
| MOUNTED? |
| PLEASE SEE MANY OTHER UNITS IN |
| ELECTRICAL ROOMS AND SPACES WHICH MAY |
| NOT BE PERMITTED. |
| 110.26 |
| |
| |
| 27) NOTE: PLEASE SEE 620.22, 620.23, AND |
| 620.24 FOR ALL MINIMUM REQUIRED |
| DEDICATED BRANCH CIRCUITS. PLEASE SEE |
| SOME APPEAR TO SHARE WITH OTHER AREAS |
| BESIDES ONLY THE ELEVATOR EQUIPMENT |
| ROOMS. |
| ALL ROOMS SHALL CONTAIN THEIR OWN |
| DEDICATED CIRCUITS AND MAY NOT FEED |
| OTHER ROOMS OR OTHER COMMON AREAS. |
| |
| 28) NOTE: PLEASE SEE FIRE PUMP ROOM |
| WHICH SHOWS A SYMBOL WHICH COULD NOT BE |
| IDENTIFIED. THIS IS ALSO LOCATED IN ROOM |
| ADJACENT TO FIRE PUMP ROOM. |
| 215.5 |
| |
| 29) NOTE: PLEASE PROVIDE EMERGENCY |
| LIGHTING FOR EGRESS TO THE PUBLIC RIGHT |
| OF WAY. PLEASE SEE THE BREEZEWAY AREAS/ |
| DRIVE AREA WHICH MAY BE USED AS AN |
| EGRESS PATH WAY. |
| LS 101-7.8,7.9 |
| |
| 30) NOTE: PLEASE SEE FBC 2004 CHAPTER 13 |
| FOR MEANS OF CONTROL REQUIRED FOR |
| EXTERIOR LIGHTING. PLEASE PROVIDE ANY |
| AREA CALCULATIONS AS SET FORTH. |
| 13-415.1.ABC.2 (IF APPLICABLE) |
| |
| 31) NOTE: PLEASE SEE 13-415.1.ABC.1.1 & |
| .2 FOR CONTROL OF INTERIOR LIGHTS. |
| PLEASE KNOW, ALL ROOMS NOT IN USE FOR |
| 24HR OPERATION SHALL CONTAIN MEANS OF |
| BEING AUTOMATICALLY TURNED OFF.PLEASE |
| KNOW, THIS INCLUDES ANY STORAGE, |
| MECHANICAL, CLOSETS ETC. |
| PLEASE SEE OTHER NEW REQUIREMENTS OF |
| CHAPTER 13. |
| |
| |
| 32) NOTE:PLEASE PROVIDE COMPLETE |
| PHOTO-METRICS FOR ALL CORRIDORS, EGRESS |
| PATHS, STAIR TOWERS. |
| PLEASE SEE 2003 NFPA-101 7.8 AND 7.9. |
| THIS REQUIRES A MIN OF 10 FT CANDLES |
| FOR STAIRS UNDER NORMAL POWER AND A |
| MINIMUM OF 1 FT CANDLE UNDER EM POWER. |
| PLEASE ALSO KNOW THAT BATTERY BACK UP |
| FIXTURE IS ALREADY BEING SHOWN IN STAIR |
| TOWERS. |
| PLEASE KNOW THIS MAY BE A "TYPICAL" |
| DETAIL FOR THESE AREAS.. PLEASE SEE |
| OTHER AREAS BESIDES STAIRS SHALL BE |
| PERMITTED TO PROVIDE 1FT CANDLE |
| (AVERAGE) UNDER NORMAL AND EMERGENCY. |
| |
| 33) NOTE:PLEASE SEE THAT ANY AFTER |
| DUSK BEFORE DAWN SWIMMING WILL REQUIRE |
| PHOTO-METRICS FOR POOL AREA(S). PLEASE |
| KNOW, ALL PHOTO-METRICS WILL BE REQUIRED |
| TO BE SUBMITTED TO PALM BEACH COUNTY |
| HEALTH DEPARTMENT FOR REVIEW AND |
| STAMPING. ONLY THE STAMPED PLANS/SHEETS |
| FROM PBCHD SHOULD BE SUBMITTED. |
| |
| 34) NOTE: PLEASE VERIFY SPECS FOR FIRE |
| PUMP CONTROLLER. AS SHOWN THIS IS NOT AN |
| ELECTRIC DRIVE UNITS, HOWEVER PLEASE SEE |
| NFPA-20 AS THE MEANS OF DISCONNECTING IS |
| REQUIRED ON THE OUTSIDE OF THE FIRE PUMP |
| CONTROLLER. PLEASE SEE SPECS WERE NOT |
| SUBMITTED AND UNABLE TO VERIFY THIS AT |
| THIS TIME. |
| |
| 35)NOTE: PLEASE SEE FBC CHAPTER 13, |
| 13-415.1.ABC.1.1 AND .2 WITH RESPECT TO |
| DESIGN IF LIGHTING CONTROL WHICH NOT 24 |
| HRS OF OPERATION, MEANS OF EGRESS OR FOR |
| SECURITY PURPOSES. |
| |
| 36) NOTE: PLEASE PROVIDE VOLTAGE DROP |
| ANALYSIS FOR ALL FEEDERS AND BRANCH |
| CIRCUITS. THIS MAY BE A WORST CASE |
| SCENARIO FOR EACH. |
| THIS MAY ALSO BE NOTED. PLEASE SEE FBC |
| CHAPTER 13, 13-413.1.ABC.1.1, &.2. |
| PLEASE SEE RISER MENTIONS VD FOR |
| FEEDERS, YET THIS IS BUS-DUCT. |
| |
| 37) NOTE: PLEASE SEE FAIR HOUSING ACT |
| REGULATIONS, 24 CFR 100.205 WITH RESPECT |
| TO HEIGHTS AND LOCATIONS FOR ALL |
| ACCESSIBLE DEVICES. |
| PLEASE PLACE NOTE ON PLANS FOR FHAR. |
| |
| 38) NOTE: PLEASE SEE LOCATION OF |
| GENERATOR LOCATED ON ROOF TOP IS STILL |
| IN REVIEW AND WILL BE GONE OVER WITH |
| FIRE MARSHAL'S OFFICE FOR ANY |
| DETERMINING FACTOR'S WHICH MAY AFFECT |
| THE ELECTRICAL PLANS. |
| PLEASE KNOW, AT THIS TIME, THE EDS2 WILL |
| BE REQUIRED TO CONTAIN A MAIN, WITH A |
| MANUAL MEANS OF DISCONNECT LOCATED ON |
| THE OUTSIDE OF THE EQUIPMENT. THE |
| BREAKER LOCATED AT THE ROOFTOP GEN |
| SHOULD BE THE UNIT TO CONTAIN THE SHUNT |
| TRIP BREAKER. PLEASE ALSO KNOW, A MEANS |
| OF SHUTTING DOWN THE NATURAL GAS AND |
| OTHER FUEL SUPPLY WILL BE REQUIRED. |
| |
| 39) NOTE: PLEASE SEE CODES WITH RESPECT |
| TO LOCATIONS OF SMOKE DETECTORS. |
| PLEASE SEE FIRE REVIEW COMMENTS AS THESE |
| UNITS ARE ALSO TO BE CONDO UNITS |
| CONTAINING COOKING FACILITIES, THE SD'S |
| MAY NOT BE CONNECTED INTO THE MAIN |
| BUILDING FA SYSTEM. PLEASE KNOW, IF THIS |
| IS INDEED THE CASE THE SD'S WILL BE 120V |
| BATTERY BACK UP AND CIRCUITED TO UNITS. |
| THIS WILL AFFECT CIRCUITING AND INVOKE |
| ARC FAULT PROTECTION. |
| PLEASE SEE 2002 NFPA-72 11.5.1.1, |
| 11.5.8.3.5. SD'S ARE TO BE LOCATED A MIN |
| OF 3FT FROM KITCHEN AND BATH DOORS AND A |
| MIN OF 20FT FROM COOKING APPLIANCES. |
| (WITH EXCEPTIONS TO THE DISTANCE FROM |
| COOKING APPLIANCES. |
| PLEASE PLACE NOTES ON PLANS. |
| |
| |
| 40) NOTE: PLEASE SEE 210.12 IN THE 2002 |
| NEC WHICH REQUIRES ARC FAULT PROTECTION |
| FOR ALL "OUTLETS" ( SD'S, LTS, FANS, |
| RECEPTS ETC.)IN BEDROOMS. |
| PLEASE SEE NOTES ON PLANS FOR ALL UNITS |
| INDICATE PROTECTION FOR RECEPTS ONLY. |
| PLEASE SEE 2002 NEC. |
| |
| |
| 41) NOTE: PLEASE SEE 210.52 FOR |
| RECEPTACLE SPACING INSIDE DWELLING UNITS |
| FOR 2 FT, 6FT AND 12 FT RULE. |
| PLEASE SEE UNIT LAYOUT AS MANY OF THESE |
| HAVE BEEN REDLINED. |
| |
| 42) NOTE: PLEASE SEE PLANS SEEM TO |
| INDICATE A BUS-DUCT FROM NORMAL MDS2 TO |
| EDS, YET RISER SHOWS CONDUITS AND |
| FEEDERS. PLEASE CORRELATE AND ALSO SEE |
| FORTH COMING COMMENTS WITH RESPECT TO |
| CONDUCTORS AND SIZES. |
| |
| 43) NOTE: PLEASE SEE DETAIL FOR FC ROOM, |
| WHICH A 2' TABLE FOR PLAN/LAYOUT REVIEW, |
| HOWEVER OVERVIEW OF ROOM DOES NOT SHOW |
| THIS? |
| |
| |
| 44) NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| ALL SIGNAGE AND MAPPING TO BE LOCATED IN |
| MAIN ELECTRICAL ROOM, FIRE COMMAND ROOM |
| ETC. |
| 230.2E,700.8 ETC. |
| PLEASE KNOW, ALL PERMANENT SIGNAGE SHALL |
| CONTAIN A MINIMUM OF 1 INCH LETTERING ON |
| A CONTRASTING BACKGROUND. PLEASE KNOW, |
| MAPPING SHOWING THE PATHS FOR ACCESS TO |
| SYSTEMS WILL BE REQUIRED AT FC ROOM |
| LOCATION. |
| |
| 45) NOTE: PLEASE PROVIDE ROOM/AREA |
| DESIGNATIONS FOR INSIDE UNITS. |
| 215.5 |
| |
| 46) NOTE: PLEASE SEE CIRCUITING FOR |
| DINING ROOMS AND AREAS OF THE LIKE SHALL |
| BE ON ONE OR MORE OF THE SMALL APPLIANCE |
| CIRCUITS. |
| 210.52B1. |
| UNABLE TO VERIFY. |
| |
| 47) NOTE: PLEASE SEE MINIMUM FACILITIES |
| FOR CONDO UNITS FOR WASHER/LAUNDRY, |
| DRYERS. |
| PLEASE VERIFY , IF UNITS ARE GOING TO BE |
| OWNED CONDOS? |
| 220.16,220.18,210.11C1,210.52B |
| |
| 48) NOTE: PLEASE VERIFY PANELS IN UNITS |
| AS THESE ARE SHOWN AS 225A, WITH |
| 30CIRCUITS? PLEASE KNOW THIS IS NOT A |
| COMMON SIZE. |
| 215.5 SEE NEXT COMMENT. |
| |
| 49) NOTE: PLEASE CORRELATE ALL UNIT |
| PANELS, OCP AND SIZES. |
| PLEASE SEE RISER INDICATES PANELS AS |
| 100A?S, HOWEVER MANY UNITS ARE 125A |
| FEEDS/ OCP ON THESE 100A PANELS. PLEASE |
| ALSO SEE PANELS ARE SHOWN AS 225A? |
| |
| 50) NOTE: PLEASE SEE PANEL WHICH ARE |
| SHOWN WITH 150A OCP ON 100A PANELS. SEE |
| GI, I, |
| 215.5 |
| |
| 51) NOTE: PLEASE SEE RISER DOES NOT |
| INDICATE PANEL "G1" , ONLY SHOWS "G"? |
| PLEASE CORRELATE. |
| PLEASE ALSO SEE THESE ARE ALL SHOWN AS |
| 100A. |
| 215.5 |
| |
| |
| 52) NOTE: PLEASE SEE MANY UNITS WHICH |
| SHOW THE CONTROL FOR SWITCHING THE |
| RECEPTS. THIS IS OK, HOWEVER PLEASE SEE |
| PLANS INDICATE SWITCHING OF THE ENTIRE |
| DEVICE. PLEASE KNOW, THIS IS OK, HOWEVER |
| AN ADDITIONAL RECEPT WILL BE REQUIRED TO |
| MEET OUTLET SPACING PER 210.52, 210.70 |
| THIS APPEARS TO BE A MISPRINT? PLEASE |
| CORRELATE AND ADJUST. |
| 215.5 |
| |
| 53) NOTE: PLEASE SEE WHAT APPEARS TO BE |
| TWO DIFFERENT SCALES USED FOR UNIT |
| PLANS. PLEASE SEE SOME SHOWN AS 3/8 INCH |
| AND OTHERS AS 1/4 INCH. |
| PLEASE SEE T-06, P-05. |
| PLEASE SEE THESE SEEM TO BE THE SAME |
| SIZE. |
| 215.5 |
| |
| 54) NOTE: PLEASE VERIFY ALL AIC RATINGS |
| ON PANELS AND BRANCH BREAKERS. PLEASE |
| KNOW, IF PANELS MENTION 42K FOR RATINGS, |
| THEN IT WILL BE ASSUMED THIS IS FOR BUS |
| AND BRKR. |
| 110.9,215.5 |
| PLEASE CLARIFY. |
| |
| 55) NOTE: PLEASE VERIFY ALL RANGES/COOK |
| TOPS IN UNITS. PLEASE SEE SOME UNITS ARE |
| SHOWN AS 4-BURNER AND SOME AS WHAT |
| APPEARS TO BE 2-BURNERS? IN EITHER CASE |
| PLEASE VERIFY THE 2-20A BREAKER FEEDING |
| THESE UNITS AND THE KW RATINGS AS SOME |
| UNITS ARE LARGER, YET BOTH SHOW THE SAME |
| LOAD AND OCP? |
| 215.5 |
| |
| 56) NOTE: PLEASE SEE NOTES FOR KITCHEN |
| GFI RECEPTS REFERENCE THE WRONG CODE. |
| SHOULD BE 210.8A6. |
| |
| 57) NOTE: PLEASE SEE NOTEON DRAWING |
| NOTES WHICH MENTIONS DINING ROOMS TO BE |
| GFI PER 210.52B1? PLEASE KNOW, 210.52B1 |
| DOES NOT MENTIONS GFI PROTECTION |
| REQUIRED FOR DINING ROOM RECEPTS. PLEASE |
| SEE DINING ROOM RECEPTS SHALL BE ON ONE |
| OR MORE OF THE 20A SMALL APPLIANCE |
| CIRCUITS. |
| |
| 58) NOTE: PLEASE VERIFY ALL MAINS , |
| MDS1, MDS2, AND EDS2 AS CONTAINING A |
| MANUAL MEANS OF DISCONNECT LOCATE DON |
| THE OUTSIDE OF THE EQUIPMENT PER |
| 230.76,230.79. |
| THESE ARE ALL NOTED AS BEING SHUNT TRIP, |
| HOWEVER THESE ARE ALSO REQUIRED TO HAVE |
| DISC?S PER ABOVE. |
| |
| 59) NOTE: PLEASE VERIFY GROUND FAULT |
| PROTECTION SHOWN FOR MDS1? |
| PLEASE SEE 240.13, 230.95 ETC WHERE THE |
| GFP IS REQUIRED AND NOTE REQUIRED. GFP |
| IS NOT REQUIRED ON THIS MAIN, HOWEVER |
| MAY BE INSTALLED. |
| |
| 60) NOTE:PLEASE SEE 230.13, 230.95, |
| 700.7D, 700.26, NFPA-110 6.2.15*, WITH |
| RESPECT TO GROUND FAULT PROTECTION ON |
| EMERGENCY SIDE OF ED SYSTEM. PLEASE SEE |
| SENSING OF GROUND FAULT AND ISOLATION OF |
| NEUTRAL IS DESIRED, HOWEVER GFP ON THE |
| EM SIDE O THE DISTRIBUTION SYSTEM IS NOT |
| DESIRED. PLEASE SEE CODE COMMENTARY FOR |
| FURTHER EXPLANATION. |
| |
| 61) NOTE: PLEASE SEE RISER NOTES AS GFP |
| IS BEING NOTED FOR ALL SYSTEMS AND ATS'S |
| ON THE EM DISTRIBUTION SIDE. PLEASE SEE |
| THE NOTE IS REFERENCING THE NEC ARTICLE |
| 517?? |
| PLEASE SEE 517 IS FOR HEALTH CARE |
| FACILITIES AND DOES NOT APPLY FOR THIS |
| BUILDING OR SCOPE. |
| PLEASE VERIFY THE ABOVE AND ADJUST RISER |
| AS NEEDED. |
| |
| 62) NOTE: PLEASE PROVIDE GROUNDING |
| ELECTRODE SYSTEM DETAIL FOR THE |
| SEPARATELY DERIVED GENERATOR AS SHOWN. |
| 250.30, 250.50 |
| |
| 63) NOTE: PLEASEPROVIDE ATTACHMENT |
| LOCATION FOR ALL TRANSFORMERS PER 250.30 |
| IT IS NOTED THAT A GROUND RISER WAS |
| SHOWN. |
| |
| 64) NOTE: PLEASE SEE 250.104 WHICH |
| REQUIRE ALL OTHER METAL PIPING SYSTEMS |
| TO BE BONDED. |
| ( FIRE SPRINKLER ETC) |
| |
| 65) NOTE: PLEASE SEE7.9.3.1 |
| GALVANIZED FUEL LINES SHALL NOT BE USED. |
| NFPA-110 7.9 |
| |
| 66) NOTE: PLEASE SEE 450.3, MAX OCP FOR |
| THE LINE SIDE OF TRANSFORMERS SHALL BE |
| 125%. IT IS PERMITTED TO GO THE NEXT |
| SIZE UP WHEN THE AMPERAGE DOES NOT |
| CORRELATE TO THE OCP DEVICE. PLEASE SEE |
| EEL22 WHICH EXCEEDS THIS 125% |
| |
| 67) NOTE: PLEASE SEE EE22 IS SHOWN AS |
| 400A ON RISER, YET SHOWN AS 225A ON |
| PANEL SCHEDULE. |
| 215.5 PLEASE CORRELATE. |
| |
| 68) NOTE: PLEASE SEE EE2 WHICH IS SHOWN |
| AS 200A ON RISER AND SHOWN AS 225A ON |
| PANEL SCHEDULE. PLEASE CORRELATE. 215.5 |
| |
| 69) NOTE: PLEASE SEE RISER SHOWS EH3 AS |
| 400A ON RISER AND 600A ON SCHEDULE. |
| PLEASE CORRELATE.215.5 |
| |
| 70) NOTE: PLEASE SEE EL3, 200A ON RISER |
| AND 225A ON SCHEDULE. |
| 215.5 |
| |
| 71) NOTE: PLEASE BE SURE TO GO THROUGH |
| ALL FEEDS TO TRANSFORMERS. PLEASE SEE |
| EH3, SHOWS A NEUTRAL CONDUCTOR WITH |
| FEEDERS TO TRANSFORMER? PLEASE KNOW, |
| THESE ARE SEPARATELY DERIVED SYSTEMS |
| WHICH CREATE A NEW SYSTEM NEUTRAL. |
| PLEASE SEE 250.6, 250.24B, 250.30 ETC. |
| 215.5 |
| |
| 72) NOTE: PLEASE SEE ATS-1 ON RISER IS |
| NOTED AS 260A'S? |
| PLEASE CORRELATE AS THIS IS FED FROM A |
| 200A DEVICE AND 260A'S IS NOT A COMMON |
| SIZE. |
| 215.5 |
| |
| 73) NOTE: PLEASE SEE 240.3 AS DEVICES |
| RATED OVER 800A'S SHALL CONTAIN |
| CONDUCTORS RATED AT OR ABOVE THE OCP |
| PROVIDED. |
| PLEASE SEE FEEDER NOTED TO ATS-2 FROM |
| EDS2. |
| PLEASE ALSO SEE FEEDER FROM MDS2 WHICH |
| SHOWS THE SAME FEEDER #7. |
| PLEASE SEE MDS2 AS THIS FEEDER ON |
| SCHEDULE DOES NOT CORRELATE WITH THIS. |
| 215.5 |
| |
| 74) NOTE: PLEASE SEE RISER SHOWS PANEL |
| PC-2 AS 225A WITH 400A OCP FEEDING THIS |
| PANEL. |
| 240, 215.5 ETC |
| |
| 75) NOTE: PLEASE SEE PANEL PM-2 SHOWS |
| 400A OCP FEEDING A PANEL RATED AT |
| 225A'S. |
| 240.4,408,215.5. |
| |
| 76) NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| PM-2, PLEASE SEE AMPS IS SHOWN AS BLANK. |
| 215.5 |
| PLEASE ALSO SEE THIS SAME PANEL MENTIONS |
| FED FROM MSD2, WHEN IT SHOULD BE MDS2. |
| (MISPRINT?) |
| |
| 77) NOTE: PLEASE SEE PANEL PC-2 SHOWS |
| AMP'S AS BLANK. |
| 215.5 |
| PLEASE ALSO SEE THIS SAME PANEL DETAILS |
| BEING FED FROM MSD2, WHEN IT SHOULD READ |
| MDS2. (MISPRINT?) |
| |
| 78) NOTE: PLEASE ADJUST FEEDERS TO BOTH |
| PC-2 AND PM-2 DEPENDING ON SIZE AND |
| RATING OF PANELS. PLEASE SEE PREVIOUS |
| COMMENTS WITH RESPECT TO OCP FEEDING |
| THESE PANELS. |
| 215.5, 310.16, 240.4 |
| |
| 79) NOTE:PLEASE SEE KL2 WHICH MENTIONS |
| FED FROM PM22? THIS DOES NOT CORRELATE |
| WITH RISER? |
| |
| 80) NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| FOR ALL RECEPTS LOCATED IN KITCHENS |
| 15/20A 125VTO BE GFIPROTECTED. |
| PLEASE KNOW, THIS IS REQUIRED WHETHER OR |
| NOT THESE ARE COUNTER SPACE RECEPTACLES. |
| |
| 81) NOTE: PLEASE SEE PL-2 WHICH SHOWS |
| BEING FED FROM MSD2, INSTEAD OF MDS2. |
| PLEASE ALSO SEE THE AMPERAGE IS SHOWN |
| BLANK? |
| PLEASE CORRELATE AND COMPLETE. 215.5 |
| |
| 82) NOTE: PLEASE SEE MISPRINT? FOR KP-2, |
| MDS2, MSD2. |
| 215.5 |
| |
| 83) NOTE: PLEASE SEE RISER SHOWS HP-1, |
| AND PANEL HP-2 AS 100A'S AND PANEL |
| SCHEDULE SHOWS THIS AS 225A'S.? |
| PLEASE CORRELATE. 215.5 |
| |
| 84) NOTE: PLEASE ALSO SEE NUMEROUS |
| PANELS WHICH ARE SHOWN AS 100A'S, YET |
| THESE ARE SHOWN AS 42 CIRCUIT PANELS. |
| THE # OF CIRCUITS AVAILABLE FOR THESE |
| 100A?S PANEL SHOULD BE VERIFIED. |
| 215.5 |
| |
| 85) NOTE: PLEASE INDICATE ALL CONDUCTORS |
| ON THE SECONDARY SIDE OF TRANSFORMERS. |
| PLEASE PROVIDE A TRANSFORMER SCHEDULE |
| SHOWING. |
| 215.5, 310.16, 240.4 ETC. |
| THESE CAN NOT BE VERIFIED AT THIS TIME. |
| |
| 86) NOTE: PLEASE CLARIFY THE TWO |
| DIFFERENT PANEL/UNIT CALCULATIONS ON |
| UNIT LAYOUT SHEETS? |
| PLEASE ONLY SHOW ONE AND CORRELATE WITH |
| NOTES BELOW. |
| 215.5 |
| |
| 87) NOTE: PLEASE SEE UNIT C WHICH SHOWS |
| 87A'S AND SHOWN AS 86 ON LOAD SUMMARY? |
| 215.5 |
| |
| 88) NOTE: PLEASE SEE ALL DP PANELS' |
| SCHEDULES WHICH FEED HOUSE PANELS. |
| PLEASE SEE HOUSE LOADS ARE SHOWN TAKING |
| THE DE-RATINGFOR THE UNITS UNDER |
| 220.32. PLEASE KNOW THE HOUSE PANEL |
| LOADS CAN NOT BE DERATED WITH THESE |
| DWELLING UNITS. |
| 215.5 |
| |
| 89) NOTE: PLEASE SHOW ALL CONTINUOUS |
| LOADS AND LARGEST MOTOR LOADS AT 125%. |
| 215.3, 230.42 ETC. |
| PLEASE ADJUST ALL LOADS. |
| |
| 90) NOTE:PLEASE SEE PANEL G1 MISSING |
| FROM RISER. PLEASE ALSO SEE PREVIOUS |
| COMMENTS ABOVE WITH RESPECT TO |
| CORRELATION OF OCP AND PANEL SIZES. |
| 215.5 |
| |
| 91) NOTE: PLEASE SEE FIRE ALARM RISER |
| WHICH INDICATES 120V POWER SUPPLY TO NAC |
| PANELS, YET THESE ARE CIRCUITED ON THE |
| 277/480V PANELS? |
| |
| 92) NOTE: PLEASE SEE NAC PANELS SHOWN ON |
| RISER; HOWEVER THESE COULD NOT BE |
| LOCATED ON PANEL SCHEDULE(S)? |
| 215.5 |
| |
| 93) NOTE: PLEASE SEE KEYNOTE WHICH |
| MENTIONS KITCHEN/ REST, BUT ONE COULD |
| NOT BE LOCATED? |
| |
| |
| 94) NOTE: PLEASE PROVIDE INFORMATION FOR |
| LOADS, PANELS AND ELECTRICAL PROVISIONS |
| BEING ALLOTTED FOR "FUTURE" TENANT |
| SPACES. |
| PLEASE SUBMIT LOAD FOR SQ FT ETC. |
| 215.5 |
| |
| 95) NOTE:PLEASE SEE RETAIL COMMON |
| "SHELL AREAS"CONTAIN MINIMUM LIGHTING |
| AS REQUIRED AND PERFIRE MARSHAL'S |
| OFFICE,LS 101 7.8, 7.9 HOWEVER PLEASE |
| SEE THESE AREAS ARE ALL BEING SHOWN |
| CIRCUITED TO PANELSWHICH UNDER THE |
| BASE BUILDING. PLEASE PROVIDE NOTES ON |
| PLANS, AS ALL OF THIS INTERIOR |
| CIRCUITING WILL BE REQUIRED TO BE |
| REMOVED AND RE-CIRCUITED TO THE PANELS |
| AND SERVICE THESE TENANT SPACES ONCE |
| PERMITTED. |
| CROSSING OVER OF SERVICES, COMMON AREA |
| BRANCH CIRCUITS IS NOT PERMITTED. |
| 230.70, 225.25 ETC |
| |
| 96) NOTE: PLEASE SEE 700.12E WHICH |
| REQUIRES ALL EM/EXT LTS TO BE CIRCUITED |
| TO THE LOCAL BRANCH CIRCUIT FEEDING ANY |
| ONE AREA. |
| PLEASE SEE THIS IS NOTED ON PLANS, |
| HOWEVER THERE ARE A COUPLE OF AREAS |
| WHICH DO NOT LEND TO THIS CIRCUITING. |
| 215.5 |
| |
| 97) NOTE: PLEASE KNOW, MANY OF THE ABOVE |
| ITEMS ARE REDLINED ON ONE SET OF THE |
| MEP'S FOR MANY OF THE SD'S, RECEPTS, |
| LTS ETC AND LOCATIONS OF COMMENTS. |
| PLEASE KNOW, THIS IS IN NO WAY ALL |
| LOCATIONS WHICH MAY BE NEEDED. PLEASE GO |
| OVER PLANS FOR ALL ITEMS. |
| |
| 98) NOTE: PLEASE KNOW A DETAILED |
| RESPONSE LETTER ON HOW ALL COMMENTS WERE |
| ADDRESSED AND CLARIFICATIONS NEEDED. |
| THIS WILL HELP IN EXPEDITING THE REVIEW |
| PROCESS. |
| |
| 99) NOTE: PLEASE SEE ALL COMMENTS FROM |
| OTHER REVIEWS WHICH MAY AFFECT |
| ELECTRICAL PLANS AND DESIGN. |
| |
| 100) NOTE:ONCE ALL REVIEWS ARE |
| COMPLETE AND BEFORE RESUBMITTING PLANS: |
| "ALL OLD/VOIDED SHEETS SHALL BE REMOVED |
| AND ONLY THE NEW REVISED SHEETS SHOULD |
| BE INSERTED INTO THREE COMPLETE SETS FOR |
| REVIEW AND STAMPING". |
| ONE SET OF ALL OLD/VOIDED SHEETS WHICH |
| ARE REMOVED SHOULD BE SUBMITTED FOR |
| REFERENCE ALONG WITH THE NEW SETS. ALL |
| VOIDED SHEETS MUST BE REMOVED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
2006-04-07 00:00:00 | PLANS WILL GO INTO FAILED STATUS. |
| |
| ** REVIEW TO CONTINUE ON 4/10. |
| |
| COMMENTS TO FOLLOW. |
2006-04-05 00:00:00 | REVIEW COMMENCED |
2006-03-29 00:00:00 | ONE ROLL OF PLANS IN ELECTRIC FOR |
| REVIEW. |