Plan Review Notes
Plan Review Notes For Permit 06010310
Permit Number 06010310
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-10 00:00:00IN REVIEW
 ******** UNSAT **********
  
 THE HARRICKHOTEL / CONDO
  
  
 1) NOTE: PLEASE BE SURE TO REFERENCE ALL
 THE CURRENT CODE IN EFFECT AS FOLLOWS.
 NFPA-20 (2002), NFPA-110 (2002). OTHERS
 ARE SHOWN CURRENT TO DATE.
  
 2) NOTE: PLEASE SEE "KEY NOTES" ON E1.1,
 #4 SEEMS TO BE #1, AND #1 SEEMS TO BE
 IDENTIFIED IN TWO LOCATIONS? PLEASE
 CORRELATE.
  
 3) NOTE: PLEASE CLARIFY AREAS INCLUDING
 FIRST FLOOR WHICH MENTIONS A FUTURE
 TENANT BUILD OUT YET, THIS ARE SEEMS TO
 BE THE LOBBY AREA OF THE HOTEL/ CONDO.
 HOW IS THIS TENANT BLD OUT?
  
 4) NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
 PLEASE ALSO PROVIDE ALL AREA AND ROOM
 DESIGNATIONS FOR UNITS AS SOME CODE
 COMPLIANCE ITEMS CAN NOT BE VERIFIED AT
 THIS TIME.
 215.5
  
 5) NOTE: PLEASE CORRELATE ALL DOORS FOR
 ELECTRICAL ROOMS FOR OUT SWING. PLEASE
 SEE ELECTRICAL PLANS INDICATE THE
 CORRECT OUT-SWING FOR MAIN ELECTRICAL
 ROOM; HOWEVER ARCHITECTURAL PLANS SHOW
 DOORS SWINGING INWARDS.
 PLEASE ALSO PLACE NOTE ON PLANS FOR
 REQUIRED PANIC HARDWARE.
 110.26
 PLEASE ALSO SEE ANY INTERFERENCE WITH
 MINIMUM WIDTHS AND EGRESS PATHS WHICH
 MAY BE AFFECTED.
 PLEASE PROVIDE NOTE FOR PANIC HARDWARE
 WHICH WILL BE REQUIRED.
 6) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM
 SHALL CONTAIN TWICE THE CLEARANCES
 REQUIRED PER 110.26 FOR ATS EQUIPMENT
 PER NFPA-110 7.2.2.1.
 THIS WILL AFFECT LAYOUT AS SHOWN.
  
 7) NOTE: PLEASE SEE 6.24* FOR MANUAL
 MEANS OF DISCONNECT REQUIRED FOR ATS
 DEVICES.
 CAN NOT VERIFY AT THIS TIME.
  
 8) NOTE: PLEASE SEE 7.2.1.1 FOR MIN 2HR
 RATINGS FOR EPSS EQUIPMENT. NFPA-110
  
 9) NOTE: PLEASE SEE COLOR CODING OF
 277/480V SYSTEMS SHALL BE "BROWN,
 PURPLE, AND YELLOW". ORANGE IS ONLY FOR
 HIGH-LEG SYSTEMS AND IS NOT PERMITTED
 FOR 277/480V.
 215, 90.4.
  
 10) NOTE: PLEASE KNOW, "LIGHTNING
 PROTECTION"SYSTEM AS SHOWN IF
 INSTALLED BY A SUB CONTRACTOR WILL
 REQUIRED THIS TO BE PULLED UNDER A
 SEPARATE PERMIT.
  
 11) NOTE: PLEASE SEE NFPA-1107.3.3*
 THE INTENSITY OF ILLUMINATION IN THE
 ROOM HOUSING THE EPS EQUIPMENT FOR LEVEL
 1 SHALL BE 32.3 LUX (30 FT-CANDLES).
 PLEASE SHOW DETAIL.
  
 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL EPS EQUIPMENT. (ATS). PLEASE SEE
 6.5.2 NFPA-110.
 UNABLE TO VERIFY AT THIS TIME.
  
 13) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR ALL EQUIPMENT:
 ATS'S, GENERATOR, FIRE PUMP FIRE PUMP
 CONTROLLER, SUB-BASE FUEL TANK ETC.
 PLEASE SEE OTHER COMMENTS AND KNOW THAT
 MANY ITEMS FOR CODE COMPLIANCE CAN NOT
 BE REVIEW AT THIS TIME DUE TO THESE
 ITEMS NOT BEING SUBMITTED FOR REVIEW.
  
  
  
 14) NOTE: PLEASE SEE NFPA-20 7.2FOR
 LOCATION OF FP CONTROLLER, HEIGHT, NEMA
 TYPE 2 ENCLOSURES AND ROOM CONTAINING A
 FLOOR DRAIN.
  
 15) NOTE:PLEASE NOTE ON PLANS THE
 ACCEPTANCE OF THE EPS AS REQUIRED IN
 NFPA-110 7.13.
  
  
 16) NOTE: PLEASE PROVIDE NOTE ON PLANS
 WHICH PROHIBITS THE INSTALLATION OF ANY
 ELECTRICAL CONDUITS ETC IN STAIRS UNLESS
 SPECIFICALLY DESIGNATED TO THE STAIRS.
 PLEASE ALSO PROVIDE NOTE FOR ELEVATOR
 EQUIPMENT ROOMS.
 215.5
  
  
 17) NOTE: PLEASE SUBMIT WIND LOAD
 CALCULATIONS FOR ALL SITE LIGHTING POLES
 INCLUSIVE OF ATTACHED LIGHT FIXTURES.
 PLEASE KNOW, THIS SHOULD INCLUDE ANY
 POLE FIXTURES ON POOL DECK/ROOF
 LEVEL(S).
 THESE CALCULATIONS WHICH ARE REQUIRED AT
 THIS TIME SHALL MEET THE 2004 FBC WITH
 RESPECT TO WIND PRESSURES AND DESIGNS
 140 MPH.
  
 18) NOTE: PLEASE SEE GFI PROTECTION
 REQUIRED IN POOL AREAS FOR CIRCUITS
 EE22-26., PL-22 /27
  
 19) NOTE: PLEASE SEE FIXTURES ON FIXTURE
 SCHEDULE WHICH INDICATE 120V TYPE
 FIXTURES IN POOL AREAS, YET THESE ARE
 CIRCUITED TO THE 277/480V PANELS??
 PLEASE SEE THE CODE DOES NOT SEE TO
 PROVIDE COMMENTARY FOR ALLOWING 277/480V
 LIGHTING IN CLOSE PROXIMITY TO POOL
 AREAS.
 PLEASE VERIFY FIXTURES TYPES AND
 VOLTAGES AND ADJUST PLANS AND SCHEDULES
 AS NEEDED.
 680, 215.5.
  
 20) NOTE: PLEASE SEE NOTE TO BE PROVIDED
 ON ALL E-2.09AB FOR MINIMUM CLEARANCES
 FOR POOL AREA FIXTURES. PLEASE 680.22
 FOR HIGH VOLTAGE FIXTURES (5FT MIN W/
 GFI PROTECTION AND 10FT MIN FOR LOW
 VOLTAGE TYPE FIXTURES. 411.4
  
  
 21) NOTE: PLEASE SEE FIXTURE AS T-1
 SHOWN IN FIRE PUMP ROOM COULD NOT BE
 LOCATED ON SCHEDULE. PLEASE KNOW AND
 BATTERY BACK UP FIXTURE OF SOME SORT
 WILL BE REQUIRED. THIS FIXTURE AS SHOWN
 SEEMS TO BE SHADED WHICH LENDS
 IDENTIFICATION TO MANY OTHER FIXTURES ON
 PLANS WHICH ARE SHADED AND ARE FIXTURES
 WITH BATTERY BACK UP.
 NFPA-20, LS 101 NFPA-70
  
 22) NOTE:PLEASE SEE NFPA-20.6.2.2
 WHICH REQUIRES A MIN OF 8HRS RUNNING @
 100% LOAD FOR FIRE PUMP. PLEASE ALSO
 BEAR IN MIND THE MINIMUM 100% LOADS FOR
 ALL OTHER LEGALLY REQUIRED STAND-BY
 ITEMS
  
 23) NOTE: PLEASE VERIFY POWER LAYOUT FOR
 FLOORS 1-4. 16-21 SHOWN ON E-2.16, AND
 5-15, ?
 215.5
  
 24) NOTE: PLEASE SEE 2.23 WHICH SEEM TO
 SHOW TWO DIFFERENT B-1 FIXTURES. PLEASE
 CORRELATE AND SEE ONE SHADED AND THE
 OTHER IS NOT.
 REDLINED AT LOCATION(S).
  
 25) NOTE: PLEASE PROVIDE A BATTERY BACK
 FIXTURE OF SOME SORT IN ELEVATOR
 EQUIPMENT ROOMS.
 LS 101 7.8,7.9,700.16
  
 26) NOTE: PLEASE SEE E2.3, WHICH SHOWS
 WHAT APPEARS TO BE FCU LOCATED IN FRONT
 OFPANEL EH-3?
 PLEASE VERIFY IF UNIT IS CEILING
 MOUNTED?
 PLEASE SEE MANY OTHER UNITS IN
 ELECTRICAL ROOMS AND SPACES WHICH MAY
 NOT BE PERMITTED.
 110.26
  
  
 27) NOTE: PLEASE SEE 620.22, 620.23, AND
 620.24 FOR ALL MINIMUM REQUIRED
 DEDICATED BRANCH CIRCUITS. PLEASE SEE
 SOME APPEAR TO SHARE WITH OTHER AREAS
 BESIDES ONLY THE ELEVATOR EQUIPMENT
 ROOMS.
 ALL ROOMS SHALL CONTAIN THEIR OWN
 DEDICATED CIRCUITS AND MAY NOT FEED
 OTHER ROOMS OR OTHER COMMON AREAS.
  
 28) NOTE: PLEASE SEE FIRE PUMP ROOM
 WHICH SHOWS A SYMBOL WHICH COULD NOT BE
 IDENTIFIED. THIS IS ALSO LOCATED IN ROOM
 ADJACENT TO FIRE PUMP ROOM.
 215.5
  
 29) NOTE: PLEASE PROVIDE EMERGENCY
 LIGHTING FOR EGRESS TO THE PUBLIC RIGHT
 OF WAY. PLEASE SEE THE BREEZEWAY AREAS/
 DRIVE AREA WHICH MAY BE USED AS AN
 EGRESS PATH WAY.
 LS 101-7.8,7.9
  
 30) NOTE: PLEASE SEE FBC 2004 CHAPTER 13
 FOR MEANS OF CONTROL REQUIRED FOR
 EXTERIOR LIGHTING. PLEASE PROVIDE ANY
 AREA CALCULATIONS AS SET FORTH.
 13-415.1.ABC.2 (IF APPLICABLE)
  
 31) NOTE: PLEASE SEE 13-415.1.ABC.1.1 &
 .2 FOR CONTROL OF INTERIOR LIGHTS.
 PLEASE KNOW, ALL ROOMS NOT IN USE FOR
 24HR OPERATION SHALL CONTAIN MEANS OF
 BEING AUTOMATICALLY TURNED OFF.PLEASE
 KNOW, THIS INCLUDES ANY STORAGE,
 MECHANICAL, CLOSETS ETC.
 PLEASE SEE OTHER NEW REQUIREMENTS OF
 CHAPTER 13.
  
  
 32) NOTE:PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR ALL CORRIDORS, EGRESS
 PATHS, STAIR TOWERS.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9.
 THIS REQUIRES A MIN OF 10 FT CANDLES
 FOR STAIRS UNDER NORMAL POWER AND A
 MINIMUM OF 1 FT CANDLE UNDER EM POWER.
 PLEASE ALSO KNOW THAT BATTERY BACK UP
 FIXTURE IS ALREADY BEING SHOWN IN STAIR
 TOWERS.
 PLEASE KNOW THIS MAY BE A "TYPICAL"
 DETAIL FOR THESE AREAS.. PLEASE SEE
 OTHER AREAS BESIDES STAIRS SHALL BE
 PERMITTED TO PROVIDE 1FT CANDLE
 (AVERAGE) UNDER NORMAL AND EMERGENCY.
  
 33) NOTE:PLEASE SEE THAT ANY AFTER
 DUSK BEFORE DAWN SWIMMING WILL REQUIRE
 PHOTO-METRICS FOR POOL AREA(S). PLEASE
 KNOW, ALL PHOTO-METRICS WILL BE REQUIRED
 TO BE SUBMITTED TO PALM BEACH COUNTY
 HEALTH DEPARTMENT FOR REVIEW AND
 STAMPING. ONLY THE STAMPED PLANS/SHEETS
 FROM PBCHD SHOULD BE SUBMITTED.
  
 34) NOTE: PLEASE VERIFY SPECS FOR FIRE
 PUMP CONTROLLER. AS SHOWN THIS IS NOT AN
 ELECTRIC DRIVE UNITS, HOWEVER PLEASE SEE
 NFPA-20 AS THE MEANS OF DISCONNECTING IS
 REQUIRED ON THE OUTSIDE OF THE FIRE PUMP
 CONTROLLER. PLEASE SEE SPECS WERE NOT
 SUBMITTED AND UNABLE TO VERIFY THIS AT
 THIS TIME.
  
 35)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 AND .2 WITH RESPECT TO
 DESIGN IF LIGHTING CONTROL WHICH NOT 24
 HRS OF OPERATION, MEANS OF EGRESS OR FOR
 SECURITY PURPOSES.
  
 36) NOTE: PLEASE PROVIDE VOLTAGE DROP
 ANALYSIS FOR ALL FEEDERS AND BRANCH
 CIRCUITS. THIS MAY BE A WORST CASE
 SCENARIO FOR EACH.
 THIS MAY ALSO BE NOTED. PLEASE SEE FBC
 CHAPTER 13, 13-413.1.ABC.1.1, &.2.
 PLEASE SEE RISER MENTIONS VD FOR
 FEEDERS, YET THIS IS BUS-DUCT.
  
 37) NOTE: PLEASE SEE FAIR HOUSING ACT
 REGULATIONS, 24 CFR 100.205 WITH RESPECT
 TO HEIGHTS AND LOCATIONS FOR ALL
 ACCESSIBLE DEVICES.
 PLEASE PLACE NOTE ON PLANS FOR FHAR.
  
 38) NOTE: PLEASE SEE LOCATION OF
 GENERATOR LOCATED ON ROOF TOP IS STILL
 IN REVIEW AND WILL BE GONE OVER WITH
 FIRE MARSHAL'S OFFICE FOR ANY
 DETERMINING FACTOR'S WHICH MAY AFFECT
 THE ELECTRICAL PLANS.
 PLEASE KNOW, AT THIS TIME, THE EDS2 WILL
 BE REQUIRED TO CONTAIN A MAIN, WITH A
 MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT. THE
 BREAKER LOCATED AT THE ROOFTOP GEN
 SHOULD BE THE UNIT TO CONTAIN THE SHUNT
 TRIP BREAKER. PLEASE ALSO KNOW, A MEANS
 OF SHUTTING DOWN THE NATURAL GAS AND
 OTHER FUEL SUPPLY WILL BE REQUIRED.
  
 39) NOTE: PLEASE SEE CODES WITH RESPECT
 TO LOCATIONS OF SMOKE DETECTORS.
 PLEASE SEE FIRE REVIEW COMMENTS AS THESE
 UNITS ARE ALSO TO BE CONDO UNITS
 CONTAINING COOKING FACILITIES, THE SD'S
 MAY NOT BE CONNECTED INTO THE MAIN
 BUILDING FA SYSTEM. PLEASE KNOW, IF THIS
 IS INDEED THE CASE THE SD'S WILL BE 120V
 BATTERY BACK UP AND CIRCUITED TO UNITS.
 THIS WILL AFFECT CIRCUITING AND INVOKE
 ARC FAULT PROTECTION.
 PLEASE SEE 2002 NFPA-72 11.5.1.1,
 11.5.8.3.5. SD'S ARE TO BE LOCATED A MIN
 OF 3FT FROM KITCHEN AND BATH DOORS AND A
 MIN OF 20FT FROM COOKING APPLIANCES.
 (WITH EXCEPTIONS TO THE DISTANCE FROM
 COOKING APPLIANCES.
 PLEASE PLACE NOTES ON PLANS.
  
  
 40) NOTE: PLEASE SEE 210.12 IN THE 2002
 NEC WHICH REQUIRES ARC FAULT PROTECTION
 FOR ALL "OUTLETS" ( SD'S, LTS, FANS,
 RECEPTS ETC.)IN BEDROOMS.
 PLEASE SEE NOTES ON PLANS FOR ALL UNITS
 INDICATE PROTECTION FOR RECEPTS ONLY.
 PLEASE SEE 2002 NEC.
  
  
 41) NOTE: PLEASE SEE 210.52 FOR
 RECEPTACLE SPACING INSIDE DWELLING UNITS
 FOR 2 FT, 6FT AND 12 FT RULE.
 PLEASE SEE UNIT LAYOUT AS MANY OF THESE
 HAVE BEEN REDLINED.
  
 42) NOTE: PLEASE SEE PLANS SEEM TO
 INDICATE A BUS-DUCT FROM NORMAL MDS2 TO
 EDS, YET RISER SHOWS CONDUITS AND
 FEEDERS. PLEASE CORRELATE AND ALSO SEE
 FORTH COMING COMMENTS WITH RESPECT TO
 CONDUCTORS AND SIZES.
  
 43) NOTE: PLEASE SEE DETAIL FOR FC ROOM,
 WHICH A 2' TABLE FOR PLAN/LAYOUT REVIEW,
 HOWEVER OVERVIEW OF ROOM DOES NOT SHOW
 THIS?
  
  
 44) NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL SIGNAGE AND MAPPING TO BE LOCATED IN
 MAIN ELECTRICAL ROOM, FIRE COMMAND ROOM
 ETC.
 230.2E,700.8 ETC.
 PLEASE KNOW, ALL PERMANENT SIGNAGE SHALL
 CONTAIN A MINIMUM OF 1 INCH LETTERING ON
 A CONTRASTING BACKGROUND. PLEASE KNOW,
 MAPPING SHOWING THE PATHS FOR ACCESS TO
 SYSTEMS WILL BE REQUIRED AT FC ROOM
 LOCATION.
  
 45) NOTE: PLEASE PROVIDE ROOM/AREA
 DESIGNATIONS FOR INSIDE UNITS.
 215.5
  
 46) NOTE: PLEASE SEE CIRCUITING FOR
 DINING ROOMS AND AREAS OF THE LIKE SHALL
 BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS.
 210.52B1.
 UNABLE TO VERIFY.
  
 47) NOTE: PLEASE SEE MINIMUM FACILITIES
 FOR CONDO UNITS FOR WASHER/LAUNDRY,
 DRYERS.
 PLEASE VERIFY , IF UNITS ARE GOING TO BE
 OWNED CONDOS?
 220.16,220.18,210.11C1,210.52B
  
 48) NOTE: PLEASE VERIFY PANELS IN UNITS
 AS THESE ARE SHOWN AS 225A, WITH
 30CIRCUITS? PLEASE KNOW THIS IS NOT A
 COMMON SIZE.
 215.5 SEE NEXT COMMENT.
  
 49) NOTE: PLEASE CORRELATE ALL UNIT
 PANELS, OCP AND SIZES.
 PLEASE SEE RISER INDICATES PANELS AS
 100A?S, HOWEVER MANY UNITS ARE 125A
 FEEDS/ OCP ON THESE 100A PANELS. PLEASE
 ALSO SEE PANELS ARE SHOWN AS 225A?
  
 50) NOTE: PLEASE SEE PANEL WHICH ARE
 SHOWN WITH 150A OCP ON 100A PANELS. SEE
 GI, I,
 215.5
  
 51) NOTE: PLEASE SEE RISER DOES NOT
 INDICATE PANEL "G1" , ONLY SHOWS "G"?
 PLEASE CORRELATE.
 PLEASE ALSO SEE THESE ARE ALL SHOWN AS
 100A.
 215.5
  
  
 52) NOTE: PLEASE SEE MANY UNITS WHICH
 SHOW THE CONTROL FOR SWITCHING THE
 RECEPTS. THIS IS OK, HOWEVER PLEASE SEE
 PLANS INDICATE SWITCHING OF THE ENTIRE
 DEVICE. PLEASE KNOW, THIS IS OK, HOWEVER
 AN ADDITIONAL RECEPT WILL BE REQUIRED TO
 MEET OUTLET SPACING PER 210.52, 210.70
 THIS APPEARS TO BE A MISPRINT? PLEASE
 CORRELATE AND ADJUST.
 215.5
  
 53) NOTE: PLEASE SEE WHAT APPEARS TO BE
 TWO DIFFERENT SCALES USED FOR UNIT
 PLANS. PLEASE SEE SOME SHOWN AS 3/8 INCH
 AND OTHERS AS 1/4 INCH.
 PLEASE SEE T-06, P-05.
 PLEASE SEE THESE SEEM TO BE THE SAME
 SIZE.
 215.5
  
 54) NOTE: PLEASE VERIFY ALL AIC RATINGS
 ON PANELS AND BRANCH BREAKERS. PLEASE
 KNOW, IF PANELS MENTION 42K FOR RATINGS,
 THEN IT WILL BE ASSUMED THIS IS FOR BUS
 AND BRKR.
 110.9,215.5
 PLEASE CLARIFY.
  
 55) NOTE: PLEASE VERIFY ALL RANGES/COOK
 TOPS IN UNITS. PLEASE SEE SOME UNITS ARE
 SHOWN AS 4-BURNER AND SOME AS WHAT
 APPEARS TO BE 2-BURNERS? IN EITHER CASE
 PLEASE VERIFY THE 2-20A BREAKER FEEDING
 THESE UNITS AND THE KW RATINGS AS SOME
 UNITS ARE LARGER, YET BOTH SHOW THE SAME
 LOAD AND OCP?
 215.5
  
 56) NOTE: PLEASE SEE NOTES FOR KITCHEN
 GFI RECEPTS REFERENCE THE WRONG CODE.
 SHOULD BE 210.8A6.
  
 57) NOTE: PLEASE SEE NOTEON DRAWING
 NOTES WHICH MENTIONS DINING ROOMS TO BE
 GFI PER 210.52B1? PLEASE KNOW, 210.52B1
 DOES NOT MENTIONS GFI PROTECTION
 REQUIRED FOR DINING ROOM RECEPTS. PLEASE
 SEE DINING ROOM RECEPTS SHALL BE ON ONE
 OR MORE OF THE 20A SMALL APPLIANCE
 CIRCUITS.
  
 58) NOTE: PLEASE VERIFY ALL MAINS ,
 MDS1, MDS2, AND EDS2 AS CONTAINING A
 MANUAL MEANS OF DISCONNECT LOCATE DON
 THE OUTSIDE OF THE EQUIPMENT PER
 230.76,230.79.
 THESE ARE ALL NOTED AS BEING SHUNT TRIP,
 HOWEVER THESE ARE ALSO REQUIRED TO HAVE
 DISC?S PER ABOVE.
  
 59) NOTE: PLEASE VERIFY GROUND FAULT
 PROTECTION SHOWN FOR MDS1?
 PLEASE SEE 240.13, 230.95 ETC WHERE THE
 GFP IS REQUIRED AND NOTE REQUIRED. GFP
 IS NOT REQUIRED ON THIS MAIN, HOWEVER
 MAY BE INSTALLED.
  
 60) NOTE:PLEASE SEE 230.13, 230.95,
 700.7D, 700.26, NFPA-110 6.2.15*, WITH
 RESPECT TO GROUND FAULT PROTECTION ON
 EMERGENCY SIDE OF ED SYSTEM. PLEASE SEE
 SENSING OF GROUND FAULT AND ISOLATION OF
 NEUTRAL IS DESIRED, HOWEVER GFP ON THE
 EM SIDE O THE DISTRIBUTION SYSTEM IS NOT
 DESIRED. PLEASE SEE CODE COMMENTARY FOR
 FURTHER EXPLANATION.
  
 61) NOTE: PLEASE SEE RISER NOTES AS GFP
 IS BEING NOTED FOR ALL SYSTEMS AND ATS'S
 ON THE EM DISTRIBUTION SIDE. PLEASE SEE
 THE NOTE IS REFERENCING THE NEC ARTICLE
 517??
 PLEASE SEE 517 IS FOR HEALTH CARE
 FACILITIES AND DOES NOT APPLY FOR THIS
 BUILDING OR SCOPE.
 PLEASE VERIFY THE ABOVE AND ADJUST RISER
 AS NEEDED.
  
 62) NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE SYSTEM DETAIL FOR THE
 SEPARATELY DERIVED GENERATOR AS SHOWN.
 250.30, 250.50
  
 63) NOTE: PLEASEPROVIDE ATTACHMENT
 LOCATION FOR ALL TRANSFORMERS PER 250.30
 IT IS NOTED THAT A GROUND RISER WAS
 SHOWN.
  
 64) NOTE: PLEASE SEE 250.104 WHICH
 REQUIRE ALL OTHER METAL PIPING SYSTEMS
 TO BE BONDED.
 ( FIRE SPRINKLER ETC)
  
 65) NOTE: PLEASE SEE7.9.3.1
 GALVANIZED FUEL LINES SHALL NOT BE USED.
 NFPA-110 7.9
  
 66) NOTE: PLEASE SEE 450.3, MAX OCP FOR
 THE LINE SIDE OF TRANSFORMERS SHALL BE
 125%. IT IS PERMITTED TO GO THE NEXT
 SIZE UP WHEN THE AMPERAGE DOES NOT
 CORRELATE TO THE OCP DEVICE. PLEASE SEE
 EEL22 WHICH EXCEEDS THIS 125%
  
 67) NOTE: PLEASE SEE EE22 IS SHOWN AS
 400A ON RISER, YET SHOWN AS 225A ON
 PANEL SCHEDULE.
 215.5 PLEASE CORRELATE.
  
 68) NOTE: PLEASE SEE EE2 WHICH IS SHOWN
 AS 200A ON RISER AND SHOWN AS 225A ON
 PANEL SCHEDULE. PLEASE CORRELATE. 215.5
  
 69) NOTE: PLEASE SEE RISER SHOWS EH3 AS
 400A ON RISER AND 600A ON SCHEDULE.
 PLEASE CORRELATE.215.5
  
 70) NOTE: PLEASE SEE EL3, 200A ON RISER
 AND 225A ON SCHEDULE.
 215.5
  
 71) NOTE: PLEASE BE SURE TO GO THROUGH
 ALL FEEDS TO TRANSFORMERS. PLEASE SEE
 EH3, SHOWS A NEUTRAL CONDUCTOR WITH
 FEEDERS TO TRANSFORMER? PLEASE KNOW,
 THESE ARE SEPARATELY DERIVED SYSTEMS
 WHICH CREATE A NEW SYSTEM NEUTRAL.
 PLEASE SEE 250.6, 250.24B, 250.30 ETC.
 215.5
  
 72) NOTE: PLEASE SEE ATS-1 ON RISER IS
 NOTED AS 260A'S?
 PLEASE CORRELATE AS THIS IS FED FROM A
 200A DEVICE AND 260A'S IS NOT A COMMON
 SIZE.
 215.5
  
 73) NOTE: PLEASE SEE 240.3 AS DEVICES
 RATED OVER 800A'S SHALL CONTAIN
 CONDUCTORS RATED AT OR ABOVE THE OCP
 PROVIDED.
 PLEASE SEE FEEDER NOTED TO ATS-2 FROM
 EDS2.
 PLEASE ALSO SEE FEEDER FROM MDS2 WHICH
 SHOWS THE SAME FEEDER #7.
 PLEASE SEE MDS2 AS THIS FEEDER ON
 SCHEDULE DOES NOT CORRELATE WITH THIS.
 215.5
  
 74) NOTE: PLEASE SEE RISER SHOWS PANEL
 PC-2 AS 225A WITH 400A OCP FEEDING THIS
 PANEL.
 240, 215.5 ETC
  
 75) NOTE: PLEASE SEE PANEL PM-2 SHOWS
 400A OCP FEEDING A PANEL RATED AT
 225A'S.
 240.4,408,215.5.
  
 76) NOTE: PLEASE SEE PANEL SCHEDULE FOR
 PM-2, PLEASE SEE AMPS IS SHOWN AS BLANK.
 215.5
 PLEASE ALSO SEE THIS SAME PANEL MENTIONS
 FED FROM MSD2, WHEN IT SHOULD BE MDS2.
 (MISPRINT?)
  
 77) NOTE: PLEASE SEE PANEL PC-2 SHOWS
 AMP'S AS BLANK.
 215.5
 PLEASE ALSO SEE THIS SAME PANEL DETAILS
 BEING FED FROM MSD2, WHEN IT SHOULD READ
 MDS2. (MISPRINT?)
  
 78) NOTE: PLEASE ADJUST FEEDERS TO BOTH
 PC-2 AND PM-2 DEPENDING ON SIZE AND
 RATING OF PANELS. PLEASE SEE PREVIOUS
 COMMENTS WITH RESPECT TO OCP FEEDING
 THESE PANELS.
 215.5, 310.16, 240.4
  
 79) NOTE:PLEASE SEE KL2 WHICH MENTIONS
 FED FROM PM22? THIS DOES NOT CORRELATE
 WITH RISER?
  
 80) NOTE: PLEASE SEE 2002 NEC 210.8B3
 FOR ALL RECEPTS LOCATED IN KITCHENS
 15/20A 125VTO BE GFIPROTECTED.
 PLEASE KNOW, THIS IS REQUIRED WHETHER OR
 NOT THESE ARE COUNTER SPACE RECEPTACLES.
  
 81) NOTE: PLEASE SEE PL-2 WHICH SHOWS
 BEING FED FROM MSD2, INSTEAD OF MDS2.
 PLEASE ALSO SEE THE AMPERAGE IS SHOWN
 BLANK?
 PLEASE CORRELATE AND COMPLETE. 215.5
  
 82) NOTE: PLEASE SEE MISPRINT? FOR KP-2,
 MDS2, MSD2.
 215.5
  
 83) NOTE: PLEASE SEE RISER SHOWS HP-1,
 AND PANEL HP-2 AS 100A'S AND PANEL
 SCHEDULE SHOWS THIS AS 225A'S.?
 PLEASE CORRELATE. 215.5
  
 84) NOTE: PLEASE ALSO SEE NUMEROUS
 PANELS WHICH ARE SHOWN AS 100A'S, YET
 THESE ARE SHOWN AS 42 CIRCUIT PANELS.
 THE # OF CIRCUITS AVAILABLE FOR THESE
 100A?S PANEL SHOULD BE VERIFIED.
 215.5
  
 85) NOTE: PLEASE INDICATE ALL CONDUCTORS
 ON THE SECONDARY SIDE OF TRANSFORMERS.
 PLEASE PROVIDE A TRANSFORMER SCHEDULE
 SHOWING.
 215.5, 310.16, 240.4 ETC.
 THESE CAN NOT BE VERIFIED AT THIS TIME.
  
 86) NOTE: PLEASE CLARIFY THE TWO
 DIFFERENT PANEL/UNIT CALCULATIONS ON
 UNIT LAYOUT SHEETS?
 PLEASE ONLY SHOW ONE AND CORRELATE WITH
 NOTES BELOW.
 215.5
  
 87) NOTE: PLEASE SEE UNIT C WHICH SHOWS
 87A'S AND SHOWN AS 86 ON LOAD SUMMARY?
 215.5
  
 88) NOTE: PLEASE SEE ALL DP PANELS'
 SCHEDULES WHICH FEED HOUSE PANELS.
 PLEASE SEE HOUSE LOADS ARE SHOWN TAKING
 THE DE-RATINGFOR THE UNITS UNDER
 220.32. PLEASE KNOW THE HOUSE PANEL
 LOADS CAN NOT BE DERATED WITH THESE
 DWELLING UNITS.
 215.5
  
 89) NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS AT 125%.
 215.3, 230.42 ETC.
 PLEASE ADJUST ALL LOADS.
  
 90) NOTE:PLEASE SEE PANEL G1 MISSING
 FROM RISER. PLEASE ALSO SEE PREVIOUS
 COMMENTS ABOVE WITH RESPECT TO
 CORRELATION OF OCP AND PANEL SIZES.
 215.5
  
 91) NOTE: PLEASE SEE FIRE ALARM RISER
 WHICH INDICATES 120V POWER SUPPLY TO NAC
 PANELS, YET THESE ARE CIRCUITED ON THE
 277/480V PANELS?
  
 92) NOTE: PLEASE SEE NAC PANELS SHOWN ON
 RISER; HOWEVER THESE COULD NOT BE
 LOCATED ON PANEL SCHEDULE(S)?
 215.5
  
 93) NOTE: PLEASE SEE KEYNOTE WHICH
 MENTIONS KITCHEN/ REST, BUT ONE COULD
 NOT BE LOCATED?
  
  
 94) NOTE: PLEASE PROVIDE INFORMATION FOR
 LOADS, PANELS AND ELECTRICAL PROVISIONS
 BEING ALLOTTED FOR "FUTURE" TENANT
 SPACES.
 PLEASE SUBMIT LOAD FOR SQ FT ETC.
 215.5
  
 95) NOTE:PLEASE SEE RETAIL COMMON
 "SHELL AREAS"CONTAIN MINIMUM LIGHTING
 AS REQUIRED AND PERFIRE MARSHAL'S
 OFFICE,LS 101 7.8, 7.9 HOWEVER PLEASE
 SEE THESE AREAS ARE ALL BEING SHOWN
 CIRCUITED TO PANELSWHICH UNDER THE
 BASE BUILDING. PLEASE PROVIDE NOTES ON
 PLANS, AS ALL OF THIS INTERIOR
 CIRCUITING WILL BE REQUIRED TO BE
 REMOVED AND RE-CIRCUITED TO THE PANELS
 AND SERVICE THESE TENANT SPACES ONCE
 PERMITTED.
 CROSSING OVER OF SERVICES, COMMON AREA
 BRANCH CIRCUITS IS NOT PERMITTED.
 230.70, 225.25 ETC
  
 96) NOTE: PLEASE SEE 700.12E WHICH
 REQUIRES ALL EM/EXT LTS TO BE CIRCUITED
 TO THE LOCAL BRANCH CIRCUIT FEEDING ANY
 ONE AREA.
 PLEASE SEE THIS IS NOTED ON PLANS,
 HOWEVER THERE ARE A COUPLE OF AREAS
 WHICH DO NOT LEND TO THIS CIRCUITING.
 215.5
  
 97) NOTE: PLEASE KNOW, MANY OF THE ABOVE
 ITEMS ARE REDLINED ON ONE SET OF THE
 MEP'S FOR MANY OF THE SD'S, RECEPTS,
 LTS ETC AND LOCATIONS OF COMMENTS.
 PLEASE KNOW, THIS IS IN NO WAY ALL
 LOCATIONS WHICH MAY BE NEEDED. PLEASE GO
 OVER PLANS FOR ALL ITEMS.
  
 98) NOTE: PLEASE KNOW A DETAILED
 RESPONSE LETTER ON HOW ALL COMMENTS WERE
 ADDRESSED AND CLARIFICATIONS NEEDED.
 THIS WILL HELP IN EXPEDITING THE REVIEW
 PROCESS.
  
 99) NOTE: PLEASE SEE ALL COMMENTS FROM
 OTHER REVIEWS WHICH MAY AFFECT
 ELECTRICAL PLANS AND DESIGN.
  
 100) NOTE:ONCE ALL REVIEWS ARE
 COMPLETE AND BEFORE RESUBMITTING PLANS:
 "ALL OLD/VOIDED SHEETS SHALL BE REMOVED
 AND ONLY THE NEW REVISED SHEETS SHOULD
 BE INSERTED INTO THREE COMPLETE SETS FOR
 REVIEW AND STAMPING".
 ONE SET OF ALL OLD/VOIDED SHEETS WHICH
 ARE REMOVED SHOULD BE SUBMITTED FOR
 REFERENCE ALONG WITH THE NEW SETS. ALL
 VOIDED SHEETS MUST BE REMOVED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2006-04-07 00:00:00PLANS WILL GO INTO FAILED STATUS.
  
 ** REVIEW TO CONTINUE ON 4/10.
  
 COMMENTS TO FOLLOW.
2006-04-05 00:00:00REVIEW COMMENCED
2006-03-29 00:00:00ONE ROLL OF PLANS IN ELECTRIC FOR
 REVIEW.