2006-04-26 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06010310 |
| ADD: 720 S. DIXIE HWY. |
| CONT: THE WEITZ CO |
| TEL: (561)719-0317 |
| |
| ----- THE HARRICK----- |
| |
| ARCH FIRM:OLIVER GLIDEN SPINA & PARTNERS |
| |
| KEITH M SPINA |
| ENGFIRM: ONMJ O'DONNELL, NACCARAATO, |
| MIGNOGNA& JOHNSON STRUCTURAL |
| |
| ENGINEERS |
| PHILLIP J. RIZZO |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE |
| ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUM- BER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICA TION PAGE WHERE THE CHANGES |
| CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS |
| FOR THE BUILDING WHICH ARE REQUIRED TO |
| BE SIGNED AND SEALED BY THE ARCHITECT OR |
| ENGINEER OF RECORD CON- TAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR |
| ENGINEER'S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 4)BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 5) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| CONSTRUCTION ACTIVITY REGULATED BY THIS |
| CODE SHALL BE PERMORMED IN A MANNER SO |
| AS NOT TO ADVERSLY IMPACT THE CONDITION |
| OF ADJACENT PROPERTY, UNLESS SUCH |
| ACTIVITY IS PERMITTED TO AFFECT SAID |
| PROPERTY PURSUANT TO A CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| CONDITIONS AGREEABLE TO THE APPLICABLE |
| PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| LIMITED TO THE CONTROL OF DUST, NOISE, |
| WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| THE STORAGE OF CONSTRUCTION MATERIALS. |
| NEW CONSTRUCTION ACTIVITY SHALL NOT |
| ADVERSELY IMPACT HISTORICSURFACE WATER |
| DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, & MAY REQUIRE SPECIAL |
| DRAINAGE DESIGNCOMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED |
| SITES.ACCORDINGLY, DEVELOPERS, |
| CONTRACTORS, AND OWNERS OF ALL NEW |
| RESIDENTIAL DEVELOPMENET, INCLUDING |
| ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN |
| EXCESS OF 800SQ FT OF PERMEABLE LAND |
| AREA ON ANY PARCELL SHALL AS A PERMIT |
| CONDITION, PROVIDE A PROFESSIONALY |
| PREPARED DRAINAGE PLAN CLEARLY |
| INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE |
| IMPROVEMENT, A CERTIFICATE FROM A |
| LICENSED ENGINEER SHALL BE SUBMITTED TO |
| THE INSPECTOR IN ORDER TO RECEIVE |
| APPROVAL OF THE FINAL INSPECTION. |
| |
| 6) 109.3.10.1 HURICANE PROTECTION. |
| IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| ALLOW CONSTRUCTION RELATED MATERIALS |
| EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION |
| SITE FROM 24 HRS. AFTER A HURRICANE |
| WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN |
| LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| EQUIPMENT AND DEBRIS SHALL BE EITHER |
| REMOVED FROM THE CONSTRUCTION SITE OR |
| SECURED IN SUCH A MANNER AS TO MINIMIZE |
| THE DANGER OF SUCH CONSTRUCTION |
| MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM |
| HIGHWINDS. |
| ANY PERSONS WHO FAILS TO COMPLY TO |
| REMOVE OR SECURE THE CONSTRUCTION |
| MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| EXCEED $500.00. |
| IN ADDITION TO THE ABOVE, A LICENSED |
| CONTRACTOR WHO VIOLATES THIS SECTION |
| SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| TO SECTION 113 OF THIS CHAPTER. |
| |
| 7) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| INFORMATION THAT IS REQUIRED FOR RECORD |
| KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| |
| D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| G) NUMBER OF UNITS |
| H) NUMBER OF FLOORS |
| I) NUMBER OF BEDROOMS |
| J) NUMBER OF ROOMS |
| K) NUMBER OF BEDROOMS |
| L) SQ. FT. LIV SPACE/ FL |
| M) SQ. FT. FOOTPRINT |
| N) SQ. FT. UNDER ROOF (TOTAL) |
| O) OCCUPANT LOAD |
| P) FLOOD ZONE |
| |
| 8) 1609.1.4 PROTECTION OF OPENINGS. |
| IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IN THE LOWER 60 FEET (18.3 M) IN |
| BUILDINGS SHALL BE ASSUMED TO BE |
| OPENINGS AND THE BALANCE OF GLAZED |
| OPENINGS IN THE REST OF THE BUILDING |
| SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IS IMPACT RESISTANT OR PROTECTED WITH AN |
| IMPACT RESISTANT COVERING MEETING THE |
| REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| AND 203 REFERENCED THEREIN AS FOLLOWS: |
| 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| FEET (9.1 M) OF GRADE SHALL MEET THE |
| REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN |
| 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| THE PROVISIONS OF THE SMALL MISSILE |
| TEST. |
| |
| 9) WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 10) THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES |
| BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'.A 'UNITY OF TITLE' SHALL BE |
| RECORDED AT THE COUNTY COURTHOUSE. |
| SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| OF TITLE' DOCUMENT SO THAT FBC TABLE 601 |
| BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| |
| 11) PLANS DO NOT HAVE AN INDEX PAGE |
| MAKING IT DIFICULT TO LOCATE ITEMS FOR |
| PLAN REVIEW. |
| |
| 12) SHEET A2.1.1 INDICATES A FIRE |
| CONTROL ROOM, IF THIS IS THE SAME AS A |
| FIRE COMMAND CENTER THERE ARE MINIMUM |
| ROOM DIMENSIONS, SHOW COMPLIANCE: |
| 911.1 FEATURES. |
| WHERE REQUIRED BY OTHER SECTIONS OF THIS |
| CODE, A FIRE COMMAND CENTER FOR FIRE |
| DEPARTMENT OPERATIONS SHALL BE PROVIDED. |
| THE LOCATION AND ACCESSIBILITY OF THE |
| FIRE COMMAND CENTER SHALL BE SEPARATED |
| FROM THE REMAINDER OF THE BUILDING BY |
| NOT LESS THAN A 1-HOUR |
| FIRE-RESISTANCE-RATED FIRE BARRIER. THE |
| ROOM SHALL BE A MINIMUM OF 96 SQUARE |
| FEET (9 M 2 ) WITH A MINIMUM DIMENSION |
| OF 8 FEET (2438 MM). A LAYOUT OF THE |
| FIRE COMMAND CENTER AND ALL FEATURES |
| REQUIRED BY THE SECTION TO BE CONTAINED |
| THEREIN SHALL BE SUBMITTED FOR APPROVAL |
| PRIOR TO INSTALLATION. THE FIRE COMMAND |
| CENTER SHALL COMPLY WITH NFPA 72 AND |
| SHALL CONTAIN THE FOLLOWING FEATURES. |
| 1.THE EMERGENCY VOICE/ALARM |
| COMMUNICATION SYSTEM UNIT. |
| 2.THE FIRE DEPARTMENT |
| COMMUNICATIONS UNIT. |
| 3.FIRE DETECTION AND ALARM SYSTEM |
| ANNUNCIATOR UNIT. |
| 4.ANNUNCIATOR UNIT VISUALLY |
| INDICATING THE LOCATION OF THE ELEVATORS |
| AND WHETHER THEY ARE OPERATIONAL. |
| 5.STATUS INDICATORS AND CONTROLS |
| FOR AIR-HANDLING SYSTEMS. |
| 6.THE FIRE-FIGHTER?S CONTROL PANEL |
| REQUIRED BY SECTION 909.16 FOR SMOKE |
| CONTROL SYSTEMS INSTALLED IN THE |
| BUILDING. |
| 7.CONTROLS FOR UNLOCKING STAIRWAY |
| DOORS SIMULTANEOUSLY. |
| 8.SPRINKLER VALVE AND WATER-FLOW |
| DETECTOR DISPLAY PANELS. |
| 9.EMERGENCY AND STANDBY POWER |
| STATUS INDICATORS. |
| 10.A TELEPHONE FOR FIRE DEPARTMENT |
| USE WITH CONTROLLED ACCESS TO THE PUBLIC |
| TELEPHONE SYSTEM. |
| 11.FIRE PUMP STATUS INDICATORS. |
| 12.SCHEMATIC BUILDING PLANS |
| INDICATING THE TYPICAL FLOOR PLAN AND |
| DETAILING THE BUILDING CORE, MEANS OF |
| EGRESS, FIRE PROTECTION SYSTEMS, |
| FIRE-FIGHTING EQUIPMENT AND FIRE |
| DEPARTMENT ACCESS. |
| 13.WORKTABLE. |
| 14.GENERATOR SUPERVISION DEVICES, |
| MANUAL START AND TRANSFER FEATURES. |
| 15.PUBLIC ADDRESS SYSTEM, WHERE |
| SPECIFICALLY REQUIRED BY OTHER SECTIONS |
| OF THIS CODE. |
| |
| 13A) A2.1.1 SHOW COMPLIANCE AT THE ENTRY |
| DROP OFF ZONE/ VALET PARKING/ LOADING |
| ZONE. |
| 11-4.6.6 PASSENGER LOADING ZONES. |
| PASSENGER LOADING ZONES SHALL PROVIDE AN |
| ACCESS AISLE AT LEAST 60 INCHES (1525 |
| MM) WIDE AND 20 FEET (6096 MM) LONG |
| ADJACENT AND PARALLEL TO THE VEHICLE |
| PULL-UP SPACE (SEE FIGURE 11-10 ). IF |
| THERE ARE CURBS BETWEEN THE ACCESS AISLE |
| AND THE VEHICLE PULL-UP SPACE, THEN A |
| CURB RAMP COMPLYING WITH SECTION 11-4.7 |
| SHALL BE PROVIDED. VEHICLE STANDING |
| SPACES AND ACCESS AISLES SHALL BE LEVEL |
| WITH SURFACE SLOPES NOT EXCEEDING 1:50 |
| (2 PERCENT) IN ALL DIRECTIONS. |
| FL S S 553.5041(1) |
| |
| 13B) A2.1.1 SHOW COMPLIANCE WITH "VAN |
| ACCESSIBLE PARKING" 11-4.6.4. |
| |
| 14) A2.1.1, EXIT CORRIDOR# 112 INDICATES |
| A RAMP WITH 12" RISE NO HANDRAILS, |
| 1010.8 HANDRAILS. |
| HANDRAILS SHALL BE PROVIDED ALONG BOTH |
| SIDES OF A RAMP RUN WITH A RISE GREATER |
| THAN 6 INCHES (152 MM) AND SHALL CONFORM |
| TO THE REQUIREMENTS IN SECTIONS 1009.11 |
| . IF HANDRAILS ARE NOT CONTINUOUS, THEY |
| SHALL EXTEND AT LEAST 18 INCHES (305 MM) |
| BEYOND THE TOP AND BOTTOM OF THE RAMP |
| SEGMENT AND SHALL BE PARALLEL WITH THE |
| FLOOR OR GROUND SURFACE. ENDS OF |
| HANDRAILS SHALL BE EITHER ROUNDED OR |
| RETURNED SMOOTHLY TO FLOOR, WALL OR |
| POST. HANDRAILS SHALL NOT ROTATE WITHIN |
| THEIR FITTINGS. TOP OF THE HANDRAIL |
| GRIPPING SURFACE SHALL BE NOT LESS THAN |
| 34 INCHES (864 MM) NOR MORE THAN 38 |
| INCHES (965 MM) ABOVE THE RAMP SURFACE. |
| 11-4.8.5 HANDRAILS. |
| IF A RAMP RUN HAS A RISE GREATER THAN 6 |
| INCHES (150 MM) OR A HORIZONTAL |
| PROJECTION GREATER THAN 72 INCHES (1830 |
| MM), THEN IT SHALL HAVE HANDRAILS ON |
| BOTH SIDES. HANDRAILS ARE NOT REQUIRED |
| ON CURB RAMPS OR ADJACENT TO SEATING IN |
| ASSEMBLY AREAS. HANDRAILS SHALL COMPLY |
| WITH SECTION 11-4.26 AND SHALL HAVE THE |
| FOLLOWING FEATURES: |
| (1)HANDRAILS SHALL BE PROVIDED |
| ALONG BOTH SIDES OF RAMP SEGMENTS. THE |
| INSIDE HANDRAIL ON SWITCHBACK OR DOGLEG |
| RAMPS SHALL ALWAYS BE CONTINUOUS. |
| (2)HANDRAILS ON RAMPS WHICH ARE NOT |
| CONTINUOUS SHALL EXTEND NOT LESS THAN 18 |
| INCHES (457 MM) BEYOND THE SLOPED |
| SEGMENT AT BOTH THE TOP AND BOTTOM, AND |
| SHALL BE PARALLEL TO THE FLOOR OR GROUND |
| SURFACE. |
| (3)THE CLEAR SPACE BETWEEN THE |
| HANDRAIL AND THE WALL SHALL BE 1? INCHES |
| (38 MM). |
| (4)GRIPPING SURFACES SHALL BE |
| CONTINUOUS. |
| (5)TOP OF HANDRAIL GRIPPING |
| SURFACES SHALL BE MOUNTED BETWEEN 34 |
| INCHES AND 38 INCHES (865 MM AND 965 MM) |
| ABOVE RAMP SURFACES. |
| (6)ENDS OF HANDRAILS SHALL BE |
| EITHER ROUNDED OR RETURNED SMOOTHLY TO |
| FLOOR, WALL, OR POST. |
| (7)HANDRAILS SHALL NOT ROTATE |
| WITHIN THEIR FITTINGS. |
| |
| 15) COMMON TO ALL FLOORS, THE PLANS DO |
| NOT INDICATE FIRE RESISTANCE RATING TO |
| ANY WALLS, TENANT SEPERATION, CORRIDOR |
| WALLS, ETC.707.2/TABLE 1016.1. |
| |
| 16) A2.2.1 PLANS ARE MISSING DOORS AT |
| 231B. |
| |
| 17) A2.2.1. ELEVATOR LOBBY PLANS |
| INDICATE 45 MIN DOORS WITH THE EXCEPTION |
| OF 201A AND 231B. 707.14.1. |
| |
| 18) PLEASE PROVIDE SINK DETAILS FOR |
| STAFF BREAK ROOM. |
| 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| BE MOUNTED WITH THE COUNTER NO HIGHER |
| THAN 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARENCE THAT IS AT |
| LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH SINKS. |
| |
| 19) A2.2.1 RESTROOM DETAIL INDICATES A |
| SECTION )/ A6.00 FOR ENLARGED PLAN AND |
| DIMENSIONS. NO SUCH SHEET. |
| |
| 20) A2.2.1 DETAIL 1/ A5.5 THIS DETAIL IS |
| A 2ND FLOOR BALCONY GAURD RAIL DETAIL |
| BUT DETAIL IS FOR THE 14TH -21ST FLOORS. |
| PLEASE CORECT. |
| |
| 21)A2.3.1 ROOM 302 (EXIT ACCESS |
| CORRIDOR) THIS IS NOT A EXIT ACCESS |
| CORRIDOR BUT A EXIT PASSAGE.DEFINITION: |
| EXIT PASSAGEWAY. AN EXIT COMPONENT THAT |
| IS SEPARATED FROM ALL OTHER INTERIOR |
| SPACES OF A BUILDING OR STRUCTURE BY |
| FIRE-RESISTANCE-RATED CONSTRUCTION AND |
| OPENING PROTECTIVES, AND PROVIDES FOR A |
| PROTECTED PATH OF EGRESS TRAVEL IN A |
| HORIZONTAL DIRECTION TO THE EXIT |
| DISCHARGE OR THE PUBLIC WAY. EXTENTION |
| OF EXIT.SEE SECTION A0.0. |
| |
| 22)A2.3.1 NORTH WALL INDICATES LOUVERS |
| ON THE NORTH WALL, PLANS DO NOT PROVIDE |
| THE DIMENSION FROM THE BUILING LINE TO |
| THE NORTH NOR EAST PROPERTY LINE. TABLE |
| 503, TABL4 601, TABLE 602 & TABLE 704.8. |
| |
| 23) THE FREIGHT ELEVATOR FOR VEHICLES |
| FLOORS 1-4. |
| 3002.1 HOISTWAY ENCLOSURE PROTECTION. |
| ELEVATOR , DUMBWAITER AND OTHER HOISTWAY |
| ENCLOSURES SHALL HAVE A FIRE-RESISTANCE |
| RATING NOT LESS THAN THAT SPECIFIED IN |
| CHAPTER 6 AND SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH CHAPTER 7 . 707.2 SHAFT |
| ENCLOSURE REQUIRED. |
| |
| OPENINGS THROUGH A FLOOR/CEILING |
| ASSEMBLY SHALL BE PROTECTED BY A SHAFT |
| ENCLOSURE COMPLYING WITH THIS SECTION |
| |
| 3002.1.1 OPENING PROTECTIVES. |
| OPENINGS IN HOISTWAY ENCLOSURES SHALL BE |
| PROTECTED AS REQUIRED IN CHAPTER 7 . |
| |
| 24) PROVIDE INFORMATION ON VEHICLE |
| STORAGE SYSTEM. |
| |
| 25) THIRD & FOURTH FLOOR PARKING GARAGE. |
| |
| 25A)110.4.2* STORAGE & FACTORY- |
| INDUSTRIAL OCCUPANCIES. |
| IT SHALL BE THE RESPONSIBILITY OF THE |
| OWNER, AGENT, PROPIETOR OR OCCUPANT OF |
| GROUP S AND GROUP F OCCUPANCIES, OR ANY |
| OCCUPANCY WHERE EXCESSIVE FLOOR LOADING |
| IS LIKELY TO OCCUR, TO EMPLOY A |
| COMPETENT ARCHI- TECT OR ENGINEER IN |
| COMPUTING THE SAFE FLOOR LOAD CAPACITY. |
| ALL SUCH COMPUTA- TIONS SHALL BE |
| ACCOMPANIED BY AN AFFA- DAVIT FROM THE |
| ARCHITECT OR ENGINEER STATING THE SAFE |
| ALLOWABLE FLOOR LOADS ON EACH FLOOR IN |
| POUNDS PER SQ FT.THE COMPUTATIONS & |
| AFFADAVIT SHALL BE FILED AS A PERMANENT |
| RECORD OF THE BLDG DEPT. |
| |
| 25B) 110.4.3* SIGNS REQUIRED. IN EVERY |
| BUILDING OR PART OF A BUILDING USED FOR |
| STORAGE, INDUSTRIAL OR HAZARDOUS PUR- |
| POSES, THE SAFE FLOOR LOADS, AS REVIEWED |
| BY THE BUILDING OFFICIAL ON THE PLAN, |
| SHALL BE MARKED ON PLATES OF APPROVED DE |
| SIGN WHICH SHALL BE SUPPLIED & SECURELY |
| AFFIXED BY THE OWNER OF THE BUILDING IN |
| A CONSPICUOUS PLACE IN EACH STORY TO |
| WHICH THEY RELATE. SUCH PLATES SHALL NOT |
| BE REMOVEDOR DEFACED, & IF LOST, |
| REMOVED THE OWNER OF THE BUILDING SHALL |
| REPLACE THEM. |
| |
| 25C)1607.9.1.1 HEAVY LIVE LOADS. |
| LIVE LOADS THAT EXCEED 100 PSF (4.79 |
| KN/M 2 ) SHALL NOT BE REDUCED EXCEPT THE |
| LIVE LOADS FOR MEMBERS SUPPORTING TWO OR |
| MORE FLOORS ARE PERMITTED TO BE REDUCED |
| BY A MAXIMUM OF 20 PERCENT, BUT THE LIVE |
| LOAD SHALL NOT BE LESS THAN L AS |
| CALCULATED IN SECTION 1607.9.1 . |
| |
| 25D) 1607.9.1.2 PASSENGER VEHICLE |
| GARAGES. THE LIVE LOADS SHALL NOT BE |
| REDUCED IN PASSENGER VEHICLE GARAGES |
| EXCEPT THE LIVE LOADS FOR MEMBERS |
| SUPPORTING TWO OR MORE FLOORS ARE |
| PERMITTED TO BE REDUCED BY A MAXIMUM OF |
| 20 PERCENT, BUT THE LIVE LOAD SHALL NOT |
| BE LESS THAN L AS CALCULATED IN SECTION |
| 1607.9.1 . |
| |
| 26) MECH M2.3/ M2.4 BOTH INDICATE |
| MECHANICAL EQUIPMENT IN THE EXIT |
| PASSAGEWAY THAT DO NOT HAVE ANY BEARING |
| ON THE STAIR PRESSURIZATION FOR THE EXIT |
| 1020.5 PENETRATIONS. |
| PENETRATIONS INTO AND OPENINGS THROUGH |
| AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT |
| FOR REQUIRED EXIT DOORS, EQUIPMENT AND |
| DUCTWORK NECESSARY FOR INDEPENDENT |
| PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE |
| DEPARTMENT COMMUNICATION AND ELECTRICAL |
| RACEWAY SERVING THE EXIT PASSAGEWAY AND |
| TERMINATING AT A STEEL BOX NOT EXCEEDING |
| 16 SQUARE INCHES (0.010 M 2 ). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN |
| ACCORDANCE WITH SECTION 712 . THERE |
| SHALL BE NO PENETRATIONS OR |
| COMMUNICATING OPENINGS, WHETHER |
| PROTECTED OR NOT, BETWEEN ADJACENT EXIT |
| PASSAGEWAYS. |
| |
| 27) MECH M2.3/ M2.4 BOTH STAIRWELLS |
| INDICATE THE USE OF LOUVER GRAVITY |
| DAMPERS, PROVIDE ADDITIONAL INFORMATION |
| WHERE THEY HAVE A 1 1/2 HR FIRE RATING. |
| |
| 28) SHEET A2.5.1 DETAIL OF ELEVATOR |
| LOBBY 0/ A6.0.0 MISSING DETAIL |
| |
| 29) A2.5.1 ELEVATOR LOBBY DOORS T04A & |
| T04B, BOTH DOORS AND ELEVATOR LOBBY |
| DOORS 5TH FLOOR AND ABOVEARE MISSING |
| THE FIRE RATING OF 3/4 HR SEE 707.14.1./ |
| TABLE 1016.1. |
| |
| 30) SHEET A2.5.1 EAST WEST CUT SECTION, |
| DETAIL1/ A4.2 NO SUCH SECTION. |
| |
| 31) SHEET A2.1.1- A2.10.1 ALL INDICATE |
| PARTITION LEGEND, PROVIDE THE EQUIVALENT |
| THICKNESS AND ASSOCIATED FIRE RESISTANCE |
| RATING FOR BOTH CONCRETE MASONARY WALLS |
| AND CAST IN PLACE CONCRETE. |
| 721.3.2 CONCRETE MASONRY WALLS. |
| THE FIRE-RESISTANCE RATING OF WALLS AND |
| PARTITIONS CONSTRUCTED OF CONCRETE |
| MASONRY UNITS SHALL BE DETERMINED FROM |
| TABLE 721.3.2 . THE RATING SHALL BE |
| BASED ON THE EQUIVALENT THICKNESS OF THE |
| MASONRY AND TYPE OF AGGREGATE USED. |
| REPORT FROM THE BLOCK MANUFACTURER FOR |
| RATING OF BLOCK.NOT U. L. LISTING. |
| 721.2.1.1 CAST-IN-PLACE OR PRECAST |
| WALLS. |
| THE MINIMUM EQUIVALENT THICKNESSES OF |
| CAST-IN-PLACE OR PRECAST CONCRETE WALLS |
| FOR FIRE-RESISTANCE RATINGS OF 1 HOUR TO |
| 4 HOURS ARE SHOWN IN TABLE 721.2.1.1 . |
| FOR SOLID WALLS WITH FLAT VERTICAL |
| SURFACES, THE EQUIVALENT THICKNESS IS |
| THE SAME AS THE ACTUAL THICKNESS. THE |
| VALUES IN TABLE 721.2.1.1 APPLY TO |
| PLAIN, REINFORCED OR PRESTRESSED |
| CONCRETE WALLS. |
| |
| 32) A2.5.1 DETAIL 1/A5.4INDICATES A CUT |
| SECTION THROUGH A BALCONY BUT NO DETAILS |
| GIVEN FOR BALCONY RAILING. GLASS IN |
| HANDRAILS AND GUARDS.2407.1 MATERIALS. |
| GLASS USED AS STRUCTURAL BALUSTRADE |
| PANELS IN RAILINGS SHALL BE CONSTRUCTED |
| OF EITHER SINGLE FULLY TEMPERED GLASS, |
| LAMINATED FULLY TEMPERED GLASS OR |
| LAMINATED HEAT-STRENGTHENED GLASS. |
| GLAZING IN RAILING IN-FILL PANELS SHALL |
| BE OF AN APPROVED SAFETY GLAZING |
| MATERIAL THAT CONFORMS TO THE PROVISIONS |
| OF SECTION 2406.1.1 . FOR ALL GLAZING |
| TYPES, THE MINIMUM NOMINAL THICKNESS |
| SHALL BE ? INCH (6.4 MM). FULLY TEMPERED |
| GLASS AND LAMINATED GLASS SHALL COMPLY |
| WITH CATEGORY II OF CPSC 16 CFR 1201, |
| LISTED IN CHAPTER 35 . |
| |
| 2407.1.1 LOADS. |
| THE PANELS AND THEIR SUPPORT SYSTEM |
| SHALL BE DESIGNED TO WITHSTAND THE LOADS |
| SPECIFIED IN SECTION 1607.7 . A SAFETY |
| FACTOR OF FOUR SHALL BE USED. |
| |
| 2407.1.2 SUPPORT. |
| EACH HANDRAIL OR GUARD SECTION SHALL BE |
| SUPPORTED BY A MINIMUM OF THREE GLASS |
| BALUSTERS OR SHALL BE OTHERWISE |
| SUPPORTED TO REMAIN IN PLACE SHOULD ONE |
| BALUSTER PANEL FAIL. GLASS BALUSTERS |
| SHALL NOT BE INSTALLED WITHOUT AN |
| ATTACHED HANDRAIL OR GUARD . |
| |
| 33)A2.5.1 LAUNDRY CHUTE REQUIRES A 2HR |
| RATED WALL PROVIDE THE EQUIVALENT |
| THICKNESS AND TYPE OF BLOCK TO BE USED, |
| FROM BLOCK MANUFACTURER. |
| |
| |
| 34) SERVICE ELEVATOR MISSING ELEVATOR |
| LOBBY,707.14.1 ELEVATOR LOBBY. |
| ELEVATORS OPENING INTO A |
| FIRE-RESISTANCE-RATED CORRIDOR AS |
| REQUIRED BY SECTION 1016.1 SHALL BE |
| PROVIDED WITH AN ELEVATOR LOBBY AT EACH |
| FLOOR CONTAINING SUCH A CORRIDOR. THE |
| LOBBY SHALL SEPARATE THE ELEVATORS FROM |
| THE CORRIDOR BY FIRE PARTITIONS AND THE |
| REQUIRED OPENING PROTECTION. ELEVATOR |
| LOBBIES SHALL HAVE AT LEAST ONE MEANS OF |
| EGRESS COMPLYING WITH CHAPTER 10 AND |
| OTHER PROVISIONS WITHIN THIS CODE. |
| |
| 35) A2.9.1 COOLING TOWERS ONCE DOOR IS |
| OPENED TO THIS AREA THERE IS NO 36" |
| MEANS OF EGRESS AROUND THE COOLING |
| TOWERS. |
| |
| 36) 1509.7 MECHANICAL UNITS. |
| ROOF MOUNTED MECHANICAL UNITS SHALL BE |
| MOUNTED ON CURBS RAISED A MINIMUM OF 8 |
| INCHES (203 MM) ABOVE THE ROOF SURFACE, |
| OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARANCE |
| HEIGHT IN ACCORDANCE WITH TABLE 1509.7 . |
| |
| |
| 37) A2.9.1 PLAN INDICATES FOR ENLARGED |
| STAIR PLAN AND DIMENSIONS SEE A0.0.0. |
| |
| 38) A2.9.1 MECHANICAL ROOM/ COOLING |
| TOWERS PLANS DO NOT INDICATE THERE IS TO |
| BE A GENERATOR LOCATED IN THIS AREA ,SEE |
| M2.22. PROVIDE DETAILS FOR GENERATOR, |
| FOR COMPLIANCE WITH: |
| 403.10.1 SPECIAL REQUIREMENTS FOR |
| STANDBY POWER SYSTEMS. |
| IF THE STANDBY SYSTEM IS A GENERATOR SET |
| INSIDE A BUILDING, THE SYSTEM SHALL BE |
| LOCATED IN A SEPARATE ROOM ENCLOSED WITH |
| 2-HOUR FIRE-RESISTANCE-RATED FIRE |
| BARRIER ASSEMBLIES. SYSTEM SUPERVISION |
| WITH MANUAL START AND TRANSFER FEATURES |
| SHALL BE PROVIDED AT THE FIRE COMMAND |
| CENTER. SURROUNDING WALL 2HR WITH |
| 1 1/2HR OPENING PROTECTIVES, DOOR M04A. |
| |
| 39) A2.10.1 AT SECTION 1/ A5.1JUST TO |
| THE RIGHT OF THIS SECTION THE HEIGHT OF |
| THE PLANTER WALL 3'-2" AND THE HEIGHT OF |
| THE GLASS RAIL AS 3'-2". SEE DETAIL |
| 1/A5.1 THE GLASS RAILING SITS ATOP OF |
| THE PLANTER WALL AN ADDITIONAL 3'-71/2". |
| |
| 40) A2.10.1 THE ELEVATOR DOORS AND |
| WINDOWS ON EITHER SIDE OF THE ELEVATOR |
| LOBBY ARE MISSING THE 1 1/2 HR RATING. |
| 707.14.1 ELEVATOR LOBBY. |
| ELEVATORS OPENING INTO A |
| FIRE-RESISTANCE-RATED CORRIDOR AS |
| REQUIRED BY SECTION 1016.1 SHALL BE |
| PROVIDED WITH AN ELEVATOR LOBBY AT EACH |
| FLOOR CONTAINING SUCH A CORRIDOR. THE |
| LOBBY SHALL SEPARATE THE ELEVATORS FROM |
| THE CORRIDOR BY FIRE PARTITIONS AND THE |
| REQUIRED OPENING PROTECTION. ELEVATOR |
| LOBBIES SHALL HAVE AT LEAST ONE MEANS OF |
| EGRESS COMPLYING WITH CHAPTER 10 AND |
| OTHER PROVISIONS WITHIN THIS CODE. |
| |
| 41) A2.10.1 THE MENS AND WOMENS |
| HANDICAPPED TOILET STALL DOORS ARE NOT |
| DIMENSIONED PLEASE SEE FIGURE 30, THE |
| STALL DOOR TO BE 32" CLEAR. |
| |
| 42) NOTE: 424.1 PUBLIC SWIMMING POOLS |
| AND BATHING PLACES. |
| PUBLIC SWIMMING POOLS AND BATHING PLACES |
| SHALL COMPLY WITH THE DESIGN AND |
| CONSTRUCTION STANDARDS OF THIS SECTION. |
| NOTE: OTHER ADMINISTRATIVE AND |
| PROGRAMMATIC PROVISIONS MAY APPLY. SEE |
| DEPARTMENT OF HEALTH (DOH) RULE 64E-9, |
| FLORIDA ADMINISTRATIVE CODE AND CHAPTER |
| 514, FLORIDA STATUTES.FAC 514 PUBLIC |
| SWIMMING AND BATHING FACILITIES. |
| |
| 43) A2.10.1 BAR D11 NO CUT SECTION |
| INDICATING COMPLIANCE WITH, FAIR HOUSING |
| REACH RANGES, ACCESSIBLE OUTE BEHIND |
| BAR. |
| |
| 44)A2.11.1 PLANS DO NOT INDICATE |
| ELEVATOR VENTS OR NOTES WHERE TO FIND |
| VENTS. |
| 3004.2 LOCATION OF VENTS. |
| VENTS SHALL BE LOCATED BELOW THE FLOOR |
| OR FLOORS AT THE TOP OF THE HOISTWAY, |
| AND SHALL OPEN EITHER DIRECTLY TO THE |
| OUTER AIR OR THROUGH NONCOMBUSTIBLE |
| DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE |
| DUCTS SHALL BE PERMITTED TO PASS THROUGH |
| THE ELEVATOR MACHINE ROOM PROVIDED THAT |
| PORTIONS OF THE DUCTS LOCATED OUTSIDE |
| THE HOISTWAY OR MACHINE ROOM ARE |
| ENCLOSED BY CONSTRUCTION HAVING NOT LESS |
| THAN THE FIRE PROTECTION RATING REQUIRED |
| FOR THE HOISTWAY. HOLES IN THE MACHINE |
| ROOM FLOORS FOR THE PASSAGE OF ROPES, |
| CABLES OR OTHER MOVING ELEVATOR |
| EQUIPMENT SHALL BE LIMITED SO AS NOT TO |
| PROVIDE GREATER THAN 2 INCHES (51 MM) OF |
| CLEARANCE ON ALL SIDES. |
| |
| 3004.3 AREA OF VENTS. |
| EXCEPT AS PROVIDED FOR IN SECTION |
| 3004.3.1 , THE AREA OF THE VENTS SHALL |
| NOT BE LESS THAN 3? PERCENT OF THE AREA |
| OF THE HOISTWAY NOR LESS THAN 3 SQUARE |
| FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR, |
| AND NOT LESS THAN 3? PERCENT NOR LESS |
| THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR |
| EACH DUMBWAITER CAR IN THE HOISTWAY, |
| WHICHEVER IS GREATER. OF THE TOTAL |
| REQUIRED VENT AREA, NOT LESS THAN |
| ONE-THIRD SHALL BE OF THE PERMANENTLY |
| OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON |
| DETECTION OF SMOKE FROM ANY OF THE |
| ELEVATOR LOBBY SMOKE DETECTORS. |
| |
| 45) A3.1.1 & A3.1.3 NORTH AND EAST |
| ELEVATIONS, THE DISTANCE TO THE PROPERTY |
| LINE IS NOT PROVIDED, THE ALLOWABLE AREA |
| OF OPENINGS PER FLOOR CAN'T BE COMPUTED. |
| 704.8 ALLOWABLE AREA OF OPENINGS. |
| THE MAXIMUM AREA OF UNPROTECTED OR |
| PROTECTED OPENINGS PERMITTED IN AN |
| EXTERIOR WALL IN ANY STORY SHALL NOT |
| EXCEED THE VALUES SET FORTH IN TABLE |
| 704.8 . WHERE BOTH UNPROTECTED AND |
| PROTECTED OPENINGS ARE LOCATED IN THE |
| EXTERIOR WALL IN ANY STORY, THE TOTAL |
| AREA OF THE OPENINGS SHALL COMPLY WITH |
| THE FOLLOWING FORMULA: |
| |
| A/A+AU/AU<1.0 |
| |
| 46) A6.1.1- A6.14.2 1207.2 AIR-BORNE |
| SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING |
| ASSEMBLIES SEPARATING DWELLING UNITS |
| FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND |
| TRANSMISSION CLASS (STC) OF NOT LESS |
| THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN |
| ACCORDANCE WITH ASTM E 90. PENETRATIONS |
| OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| VENTILATING OR EXHAUST DUCTS SHALL BE |
| SEALED, LINED, INSULATED OR OTHERWISE |
| TREATED TO MAINTAIN THE REQUIRED |
| RATINGS. THIS REQUIREMENT SHALL NOT |
| APPLY TO DWELLING UNIT ENTRANCE DOORS; |
| HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 47) A6.1.1- A6.14.1 1207.3 |
| STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING |
| UNIT AND A PUBLIC OR SERVICE AREA WITHIN |
| THE STRUCTURE SHALL HAVE AN IMPACT |
| INSULATION CLASS (IIC) RATING OF NOT |
| LESS THAN 50 (45 IF FIELD TESTED) WHEN |
| TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 48) A6.1.1 DOOR T01E TO BE A MINIMUM OF |
| 32" CLEAR, FAIR HOUSING ANSI A117.1- |
| 404.2.3.SMALL CLOSETS SUCH AS LINEN |
| CLOSETS NOT COVERED, SHELVES WITHIN |
| REACH, THIS CLOSEET IS 3'-0" DEEP. |
| |
| 49) A6.2.1 DOOR T02C1 SEE DOOR CHART FOR |
| WIDTH. |
| |
| 50) A6.3.2 NOTE: REFER TO INTERIOR |
| DESIGNERS DRAWINGS FOR ALL BATH |
| ACCESSORY SPECIFICATIONS AND MOUNTING |
| HEIGHT. THERE IS NO INDEX NOR NOTE |
| INDICATING WHERE THIS INFORMATION CAN BE |
| LOCATED. 11-4.26.2 SIZE AND SPACING OF |
| GRAB BARS AND HANDRAILS. |
| THE DIAMETER OR WIDTH OF THE GRIPPING |
| SURFACES OF A HANDRAIL OR GRAB BAR SHALL |
| BE 1? INCHES TO 1? INCHES (32 MM TO 38 |
| MM), OR THE SHAPE SHALL PROVIDE AN |
| EQUIVALENT GRIPPING SURFACE. IF |
| HANDRAILS OR GRAB BARS ARE MOUNTED |
| ADJACENT TO A WALL, THE SPACE BETWEEN |
| THE WALL AND THE GRAB BAR SHALL BE 1? |
| INCHES (38 MM) [SEE FIGURE 11-39 (A), |
| FIGURE 11-39 (B), FIGURE 11-39 (C), AND |
| FIGURE 11-39 (E)]. HANDRAILS MAY BE |
| LOCATED IN A RECESS IF THE RECESS IS A |
| MAXIMUM OF 3 INCHES (76 MM) DEEP AND |
| EXTENDS AT LEAST 18 INCHES (455 MM) |
| ABOVE THE TOP OF THE RAIL [SEE FIGURE |
| 11-39 (D)]. |
| 11-4.26.3 |
| 11-4.26.3 STRUCTURAL STRENGTH. |
| THE STRUCTURAL STRENGTH OF GRAB BARS, |
| TUB AND SHOWER SEATS, FASTENERS AND |
| MOUNTING DEVICES SHALL MEET THE |
| FOLLOWING SPECIFICATION: |
| (1)BENDING STRESS IN A GRAB BAR OR |
| SEAT INDUCED BY THE MAXIMUM BENDING |
| MOMENT FROM THE APPLICATION OF 250 LBF |
| (1112 N) SHALL BE LESS THAN THE |
| ALLOWABLE STRESS FOR THE MATERIAL OF THE |
| GRAB BAR OR SEAT. |
| (2)SHEAR STRESS INDUCED IN A GRAB |
| BAR OR SEAT BY THE APPLICATION OF 250 |
| LBF (1112 N) SHALL BE LESS THAN THE |
| ALLOWABLE SHEAR STRESS FOR THE MATERIAL |
| OF THE GRAB BAR OR SEAT. IF THE |
| CONNECTION BETWEEN THE GRAB BAR OR SEAT |
| AND ITS MOUNTING BRACKET OR OTHER |
| SUPPORT IS CONSIDERED TO BE FULLY |
| RESTRAINED, THEN DIRECT AND TORSIONAL |
| SHEAR STRESSES SHALL BE TOTALED FOR THE |
| COMBINED SHEAR STRESS, WHICH SHALL NOT |
| EXCEED THE ALLOWABLE SHEAR STRESS. |
| (3)SHEAR FORCE INDUCED IN A |
| FASTENER OR MOUNTING DEVICE FROM THE |
| APPLICATION OF 250 LBF (1112 N) SHALL BE |
| LESS THAN THE ALLOWABLE LATERAL LOAD OF |
| EITHER THE FASTENER OR MOUNTING DEVICE |
| OR THE SUPPORTING STRUCTURE, WHICHEVER |
| IS THE SMALLER ALLOWABLE LOAD. |
| (4)TENSILE FORCE INDUCED IN A |
| FASTENER BY A DIRECT TENSION FORCE OF |
| 250 LBF (1112 N) PLUS THE MAXIMUM MOMENT |
| FROM THE APPLICATION OF 250 LBF (1112N) |
| SHALL BE LESS THAN THE ALLOWABLE |
| WITHDRAWAL LOAD BETWEEN THE FASTENER AND |
| THE SUPPORTING STRUCTURE. |
| (5)GRAB BARS SHALL NOT ROTATE |
| WITHIN THEIR FITTINGS. |
| ALL HANDRAILS, GRAB BARS, AND TUB AND |
| SHOWER SEATS REQUIRED TO BE ACCESSIBLE |
| BY SECTION 11-4.1 , 11-4.8 , 11-4.9 , |
| 11-4.16 , 11-4.17 , 11-4.20 OR 11-4.21 |
| SHALL COMPLY WITH SECTION 11-4.26 . |
| |
| 51) A6.6.2 MASTER BEDROOM: 11-9.2.2 |
| MINIMUM REQUIREMENTS. |
| AN ACCESSIBLE UNIT, SLEEPING ROOM OR |
| SUITE SHALL BE ON AN ACCESSIBLE ROUTE |
| COMPLYING WITH SECTION 11-4.3 AND HAVE |
| THE FOLLOWING ACCESSIBLE ELEMENTS AND |
| SPACES. |
| (1)ACCESSIBLE SLEEPING ROOMS SHALL |
| HAVE A 36 INCH (915 MM) CLEAR WIDTH |
| MANEUVERING SPACE LOCATED ALONG BOTH |
| SIDES OF A BED, EXCEPT THAT WHERE TWO |
| BEDS ARE PROVIDED, THIS REQUIREMENT CAN |
| BE MET BY PROVIDING A 36 INCHES (915 MM) |
| WIDE MANEUVERING SPACE LOCATED BETWEEN |
| THE TWO BEDS. CHECK ALL UNITS! |
| |
| 51) A6.10.1A6.1.1 DOOR P01E TO BE A |
| MINIMUM OF 32" CLEAR, FAIR HOUSING ANSI |
| A117.1- 404.2.3.SMALL CLOSETS SUCH AS |
| LINEN CLOSETS NOT COVERED, SHELVES |
| WITHIN REACH, THIS CLOSEET IS 3'-0" |
| DEEP. |
| |
| 52)A6.13.1 MASTER BEDROOM MASTER |
| BEDROOM: 11-9.2.2 MINIMUM REQUIREMENTS. |
| AN ACCESSIBLE UNIT, SLEEPING ROOM OR |
| SUITE SHALL BE ON AN ACCESSIBLE ROUTE |
| COMPLYING WITH SECTION 11-4.3 AND HAVE |
| THE FOLLOWING ACCESSIBLE ELEMENTS AND |
| SPACES. |
| (1)ACCESSIBLE SLEEPING ROOMS SHALL |
| HAVE A 36 INCH (915 MM) CLEAR WIDTH |
| MANEUVERING SPACE LOCATED ALONG BOTH |
| SIDES OF A BED, EXCEPT THAT WHERE TWO |
| BEDS ARE PROVIDED, THIS REQUIREMENT CAN |
| BE MET BY PROVIDING A 36 INCHES (915 MM) |
| WIDE MANEUVERING SPACE LOCATED BETWEEN |
| THE TWO BEDS. CHECK ALL UNITS! |
| |
| 53) A8.1.1 FINISH SCHEDULE NOT COMPLETE |
| PAGE IS BLANK. |
| |
| 54) A9.1 DETAILS 3& 4 ARE MISSING THE |
| SOUND TRANSMITION RATING.1207.2 |
| AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING |
| ASSEMBLIES SEPARATING DWELLING UNITS |
| FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND |
| TRANSMISSION CLASS (STC) OF NOT LESS |
| THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN |
| ACCORDANCE WITH ASTM E 90. PENETRATIONS |
| OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| VENTILATING OR EXHAUST DUCTS SHALL BE |
| SEALED, LINED, INSULATED OR OTHERWISE |
| TREATED TO MAINTAIN THE REQUIRED |
| RATINGS. THIS REQUIREMENT SHALL NOT |
| APPLY TO DWELLING UNIT ENTRANCE DOORS; |
| HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 55) SHEET A9.1 REFERS BACK TO 0/A8.00 |
| FOR LIMITING HEIGHT AND GAUGE TABLE. |
| THERE IS NO SUCH SHEET. |
| |
| 56) SHEET A9.2 PROVIDE UL LISTING OR |
| GYPSUM ASSOCIATION NUMBER FOR EACH |
| ASSEMBLY.FIRE PARTITION. A VERTICAL |
| ASSEMBLY OF MATERIALS DESIGNED TO |
| RESTRICT THE SPREAD OF FIRE IN WHICH |
| OPENINGS ARE PROTECTED. |
| SHAFT ENCLOSURE. THE WALLS OR |
| CONSTRUCTION FORMING THE BOUNDARIES OF A |
| SHAFT. |
| |
| 57) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 58)FL BLD CODE 1609.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) CURTAIN WALL |
| B) STOREFRONT WINDOW AND DOOR |
| C) LOUVERED DOORS -REQUIRES STORM |
| SHUTTERS SEE REPORT (NOA) |
| D) EXTERIOR DOOR AT AUTO ELEVATOR |
| E) SOFFITS(EFIS) |
| F) ROOF HATCH |
| G) PRE-ENGINEERED A/C STANDS |
| H) MULLIONS |
| |
| 58) CONTRACTOR TO HIGHLIGHT WHICH |
| ROOFING APPLICATION FLAT DECK SBS SYSTEM |
| DECK TYPE APPLICATION TYPE 31 OR DECK |
| TYPE 3. |
| |
| 59) PLANS DO NOT ADEQUATELY PROVIDE |
| WHAT TYPE OF WINDOWS ARE TO BE USED , |
| EXAMPLE UNITS 1707- 2107 WINDOW (00) |
| DEPENDING ON TYPE OF WINDOW EAST |
| ELEVATION REPORT FOR WIND TUNNEL TEST |
| INDICATES A NEGATIVE PEAK PRESSURE OF |
| 105. |
| PROVIDE MORE DETAIL OF WINDOW TYPES AND |
| LOCATION. (WINDOW SCHEDULE) |
| |
| 60) SHEET A5.8 PLANS INDICATE DROPPED |
| CEILINGS BUT NO DETAILS INDICATING THE |
| TYPE OF CEILING THICKNESS, TYPE OF |
| FRAMING, THICKNESS SIZE, MATERIAL |
| THICKNESS NOR FLANGE SIZE. PLANS ALSO DO |
| NOT PROVIDE THE ALLOWABLE CEILING |
| DEFLECTIONS. PLANS DO NOT INDICATE IF |
| STIFF BACKS ARE USED.THIS SAME |
| INFORMATION WILL BE REQUIRED FOR DROPPED |
| SOFFITS INTERIOR AND EXTERIOR. |
| |
| 61) (A5.6) EXTERIOR DETAILS THERE IS NO |
| DETAILS INDICATING HOW TO FASATEN TO |
| DECK ABOVE, FREQUENCY OF FASTENERS NOR |
| SPACING. NO MENTION OF SUBSHEATHING OR |
| FINISH. |
| |
| 62) S-1 NOTE: 8'-0" THICK MAT FOUNDATION |
| SEE DWG S-16 FOR DETAILS, NO DETAILS |
| |
| 63) A6.1.1 HEARING IMPAIRED UNITS, |
| SHOW COMPLIANCE WITH 11-9.3/ 11-4.28.4. |
| PROVIDE MANUFACTURER SPEC SHEET. |
| |
| 64) A6.11 TYPICAL BALCONY RAILING NOTE |
| NOT COMPLETE.XXX |
| |
| ADDITIONAL COMMENTS MAY APPEAR ON THE |
| NEXT REVIEW DUE TO THE RESPONCE TO THESE |
| COMMENTS OR LACK THERE OFF. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| |
| |