2006-04-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06010310
 ADD: 720 S. DIXIE HWY.
 CONT: THE WEITZ CO
 TEL: (561)719-0317
  
 ----- THE HARRICK-----
  
 ARCH FIRM:OLIVER GLIDEN SPINA & PARTNERS
  
 KEITH M SPINA
 ENGFIRM: ONMJ O'DONNELL, NACCARAATO,
 MIGNOGNA& JOHNSON STRUCTURAL
  
 ENGINEERS
 PHILLIP J. RIZZO
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 6) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 7) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
  
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
  
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
  
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
  
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
  
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
  
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF UNITS
 H) NUMBER OF FLOORS
 I) NUMBER OF BEDROOMS
 J) NUMBER OF ROOMS
 K) NUMBER OF BEDROOMS
 L) SQ. FT. LIV SPACE/ FL
 M) SQ. FT. FOOTPRINT
 N) SQ. FT. UNDER ROOF (TOTAL)
 O) OCCUPANT LOAD
 P) FLOOD ZONE
  
 8) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 9) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 11) PLANS DO NOT HAVE AN INDEX PAGE
 MAKING IT DIFICULT TO LOCATE ITEMS FOR
 PLAN REVIEW.
  
 12) SHEET A2.1.1 INDICATES A FIRE
 CONTROL ROOM, IF THIS IS THE SAME AS A
 FIRE COMMAND CENTER THERE ARE MINIMUM
 ROOM DIMENSIONS, SHOW COMPLIANCE:
 911.1 FEATURES.
 WHERE REQUIRED BY OTHER SECTIONS OF THIS
 CODE, A FIRE COMMAND CENTER FOR FIRE
 DEPARTMENT OPERATIONS SHALL BE PROVIDED.
 THE LOCATION AND ACCESSIBILITY OF THE
 FIRE COMMAND CENTER SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY
 NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE-RATED FIRE BARRIER. THE
 ROOM SHALL BE A MINIMUM OF 96 SQUARE
 FEET (9 M 2 ) WITH A MINIMUM DIMENSION
 OF 8 FEET (2438 MM). A LAYOUT OF THE
 FIRE COMMAND CENTER AND ALL FEATURES
 REQUIRED BY THE SECTION TO BE CONTAINED
 THEREIN SHALL BE SUBMITTED FOR APPROVAL
 PRIOR TO INSTALLATION. THE FIRE COMMAND
 CENTER SHALL COMPLY WITH NFPA 72 AND
 SHALL CONTAIN THE FOLLOWING FEATURES.
 1.THE EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM UNIT.
 2.THE FIRE DEPARTMENT
 COMMUNICATIONS UNIT.
 3.FIRE DETECTION AND ALARM SYSTEM
 ANNUNCIATOR UNIT.
 4.ANNUNCIATOR UNIT VISUALLY
 INDICATING THE LOCATION OF THE ELEVATORS
 AND WHETHER THEY ARE OPERATIONAL.
 5.STATUS INDICATORS AND CONTROLS
 FOR AIR-HANDLING SYSTEMS.
 6.THE FIRE-FIGHTER?S CONTROL PANEL
 REQUIRED BY SECTION 909.16 FOR SMOKE
 CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
 7.CONTROLS FOR UNLOCKING STAIRWAY
 DOORS SIMULTANEOUSLY.
 8.SPRINKLER VALVE AND WATER-FLOW
 DETECTOR DISPLAY PANELS.
 9.EMERGENCY AND STANDBY POWER
 STATUS INDICATORS.
 10.A TELEPHONE FOR FIRE DEPARTMENT
 USE WITH CONTROLLED ACCESS TO THE PUBLIC
 TELEPHONE SYSTEM.
 11.FIRE PUMP STATUS INDICATORS.
 12.SCHEMATIC BUILDING PLANS
 INDICATING THE TYPICAL FLOOR PLAN AND
 DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS,
 FIRE-FIGHTING EQUIPMENT AND FIRE
 DEPARTMENT ACCESS.
 13.WORKTABLE.
 14.GENERATOR SUPERVISION DEVICES,
 MANUAL START AND TRANSFER FEATURES.
 15.PUBLIC ADDRESS SYSTEM, WHERE
 SPECIFICALLY REQUIRED BY OTHER SECTIONS
 OF THIS CODE.
  
 13A) A2.1.1 SHOW COMPLIANCE AT THE ENTRY
 DROP OFF ZONE/ VALET PARKING/ LOADING
 ZONE.
 11-4.6.6 PASSENGER LOADING ZONES.
 PASSENGER LOADING ZONES SHALL PROVIDE AN
 ACCESS AISLE AT LEAST 60 INCHES (1525
 MM) WIDE AND 20 FEET (6096 MM) LONG
 ADJACENT AND PARALLEL TO THE VEHICLE
 PULL-UP SPACE (SEE FIGURE 11-10 ). IF
 THERE ARE CURBS BETWEEN THE ACCESS AISLE
 AND THE VEHICLE PULL-UP SPACE, THEN A
 CURB RAMP COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED. VEHICLE STANDING
 SPACES AND ACCESS AISLES SHALL BE LEVEL
 WITH SURFACE SLOPES NOT EXCEEDING 1:50
 (2 PERCENT) IN ALL DIRECTIONS.
 FL S S 553.5041(1)
  
 13B) A2.1.1 SHOW COMPLIANCE WITH "VAN
 ACCESSIBLE PARKING" 11-4.6.4.
  
 14) A2.1.1, EXIT CORRIDOR# 112 INDICATES
 A RAMP WITH 12" RISE NO HANDRAILS,
 1010.8 HANDRAILS.
 HANDRAILS SHALL BE PROVIDED ALONG BOTH
 SIDES OF A RAMP RUN WITH A RISE GREATER
 THAN 6 INCHES (152 MM) AND SHALL CONFORM
 TO THE REQUIREMENTS IN SECTIONS 1009.11
 . IF HANDRAILS ARE NOT CONTINUOUS, THEY
 SHALL EXTEND AT LEAST 18 INCHES (305 MM)
 BEYOND THE TOP AND BOTTOM OF THE RAMP
 SEGMENT AND SHALL BE PARALLEL WITH THE
 FLOOR OR GROUND SURFACE. ENDS OF
 HANDRAILS SHALL BE EITHER ROUNDED OR
 RETURNED SMOOTHLY TO FLOOR, WALL OR
 POST. HANDRAILS SHALL NOT ROTATE WITHIN
 THEIR FITTINGS. TOP OF THE HANDRAIL
 GRIPPING SURFACE SHALL BE NOT LESS THAN
 34 INCHES (864 MM) NOR MORE THAN 38
 INCHES (965 MM) ABOVE THE RAMP SURFACE.
 11-4.8.5 HANDRAILS.
 IF A RAMP RUN HAS A RISE GREATER THAN 6
 INCHES (150 MM) OR A HORIZONTAL
 PROJECTION GREATER THAN 72 INCHES (1830
 MM), THEN IT SHALL HAVE HANDRAILS ON
 BOTH SIDES. HANDRAILS ARE NOT REQUIRED
 ON CURB RAMPS OR ADJACENT TO SEATING IN
 ASSEMBLY AREAS. HANDRAILS SHALL COMPLY
 WITH SECTION 11-4.26 AND SHALL HAVE THE
 FOLLOWING FEATURES:
 (1)HANDRAILS SHALL BE PROVIDED
 ALONG BOTH SIDES OF RAMP SEGMENTS. THE
 INSIDE HANDRAIL ON SWITCHBACK OR DOGLEG
 RAMPS SHALL ALWAYS BE CONTINUOUS.
 (2)HANDRAILS ON RAMPS WHICH ARE NOT
 CONTINUOUS SHALL EXTEND NOT LESS THAN 18
 INCHES (457 MM) BEYOND THE SLOPED
 SEGMENT AT BOTH THE TOP AND BOTTOM, AND
 SHALL BE PARALLEL TO THE FLOOR OR GROUND
 SURFACE.
 (3)THE CLEAR SPACE BETWEEN THE
 HANDRAIL AND THE WALL SHALL BE 1? INCHES
 (38 MM).
 (4)GRIPPING SURFACES SHALL BE
 CONTINUOUS.
 (5)TOP OF HANDRAIL GRIPPING
 SURFACES SHALL BE MOUNTED BETWEEN 34
 INCHES AND 38 INCHES (865 MM AND 965 MM)
 ABOVE RAMP SURFACES.
 (6)ENDS OF HANDRAILS SHALL BE
 EITHER ROUNDED OR RETURNED SMOOTHLY TO
 FLOOR, WALL, OR POST.
 (7)HANDRAILS SHALL NOT ROTATE
 WITHIN THEIR FITTINGS.
  
 15) COMMON TO ALL FLOORS, THE PLANS DO
 NOT INDICATE FIRE RESISTANCE RATING TO
 ANY WALLS, TENANT SEPERATION, CORRIDOR
 WALLS, ETC.707.2/TABLE 1016.1.
  
 16) A2.2.1 PLANS ARE MISSING DOORS AT
 231B.
  
 17) A2.2.1. ELEVATOR LOBBY PLANS
 INDICATE 45 MIN DOORS WITH THE EXCEPTION
 OF 201A AND 231B. 707.14.1.
  
 18) PLEASE PROVIDE SINK DETAILS FOR
 STAFF BREAK ROOM.
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 19) A2.2.1 RESTROOM DETAIL INDICATES A
 SECTION )/ A6.00 FOR ENLARGED PLAN AND
 DIMENSIONS. NO SUCH SHEET.
  
 20) A2.2.1 DETAIL 1/ A5.5 THIS DETAIL IS
 A 2ND FLOOR BALCONY GAURD RAIL DETAIL
 BUT DETAIL IS FOR THE 14TH -21ST FLOORS.
 PLEASE CORECT.
  
 21)A2.3.1 ROOM 302 (EXIT ACCESS
 CORRIDOR) THIS IS NOT A EXIT ACCESS
 CORRIDOR BUT A EXIT PASSAGE.DEFINITION:
 EXIT PASSAGEWAY. AN EXIT COMPONENT THAT
 IS SEPARATED FROM ALL OTHER INTERIOR
 SPACES OF A BUILDING OR STRUCTURE BY
 FIRE-RESISTANCE-RATED CONSTRUCTION AND
 OPENING PROTECTIVES, AND PROVIDES FOR A
 PROTECTED PATH OF EGRESS TRAVEL IN A
 HORIZONTAL DIRECTION TO THE EXIT
 DISCHARGE OR THE PUBLIC WAY. EXTENTION
 OF EXIT.SEE SECTION A0.0.
  
 22)A2.3.1 NORTH WALL INDICATES LOUVERS
 ON THE NORTH WALL, PLANS DO NOT PROVIDE
 THE DIMENSION FROM THE BUILING LINE TO
 THE NORTH NOR EAST PROPERTY LINE. TABLE
 503, TABL4 601, TABLE 602 & TABLE 704.8.
  
 23) THE FREIGHT ELEVATOR FOR VEHICLES
 FLOORS 1-4.
 3002.1 HOISTWAY ENCLOSURE PROTECTION.
 ELEVATOR , DUMBWAITER AND OTHER HOISTWAY
 ENCLOSURES SHALL HAVE A FIRE-RESISTANCE
 RATING NOT LESS THAN THAT SPECIFIED IN
 CHAPTER 6 AND SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH CHAPTER 7 . 707.2 SHAFT
 ENCLOSURE REQUIRED.
  
 OPENINGS THROUGH A FLOOR/CEILING
 ASSEMBLY SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE COMPLYING WITH THIS SECTION
  
 3002.1.1 OPENING PROTECTIVES.
 OPENINGS IN HOISTWAY ENCLOSURES SHALL BE
 PROTECTED AS REQUIRED IN CHAPTER 7 .
  
 24) PROVIDE INFORMATION ON VEHICLE
 STORAGE SYSTEM.
  
 25) THIRD & FOURTH FLOOR PARKING GARAGE.
  
 25A)110.4.2* STORAGE & FACTORY-
 INDUSTRIAL OCCUPANCIES.
 IT SHALL BE THE RESPONSIBILITY OF THE
 OWNER, AGENT, PROPIETOR OR OCCUPANT OF
 GROUP S AND GROUP F OCCUPANCIES, OR ANY
 OCCUPANCY WHERE EXCESSIVE FLOOR LOADING
 IS LIKELY TO OCCUR, TO EMPLOY A
 COMPETENT ARCHI- TECT OR ENGINEER IN
 COMPUTING THE SAFE FLOOR LOAD CAPACITY.
 ALL SUCH COMPUTA- TIONS SHALL BE
 ACCOMPANIED BY AN AFFA- DAVIT FROM THE
 ARCHITECT OR ENGINEER STATING THE SAFE
 ALLOWABLE FLOOR LOADS ON EACH FLOOR IN
 POUNDS PER SQ FT.THE COMPUTATIONS &
 AFFADAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
 25B) 110.4.3* SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 25C)1607.9.1.1 HEAVY LIVE LOADS.
 LIVE LOADS THAT EXCEED 100 PSF (4.79
 KN/M 2 ) SHALL NOT BE REDUCED EXCEPT THE
 LIVE LOADS FOR MEMBERS SUPPORTING TWO OR
 MORE FLOORS ARE PERMITTED TO BE REDUCED
 BY A MAXIMUM OF 20 PERCENT, BUT THE LIVE
 LOAD SHALL NOT BE LESS THAN L AS
 CALCULATED IN SECTION 1607.9.1 .
  
 25D) 1607.9.1.2 PASSENGER VEHICLE
 GARAGES. THE LIVE LOADS SHALL NOT BE
 REDUCED IN PASSENGER VEHICLE GARAGES
 EXCEPT THE LIVE LOADS FOR MEMBERS
 SUPPORTING TWO OR MORE FLOORS ARE
 PERMITTED TO BE REDUCED BY A MAXIMUM OF
 20 PERCENT, BUT THE LIVE LOAD SHALL NOT
 BE LESS THAN L AS CALCULATED IN SECTION
 1607.9.1 .
  
 26) MECH M2.3/ M2.4 BOTH INDICATE
 MECHANICAL EQUIPMENT IN THE EXIT
 PASSAGEWAY THAT DO NOT HAVE ANY BEARING
 ON THE STAIR PRESSURIZATION FOR THE EXIT
 1020.5 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION AND ELECTRICAL
 RACEWAY SERVING THE EXIT PASSAGEWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M 2 ). SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712 . THERE
 SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT
 PASSAGEWAYS.
  
 27) MECH M2.3/ M2.4 BOTH STAIRWELLS
 INDICATE THE USE OF LOUVER GRAVITY
 DAMPERS, PROVIDE ADDITIONAL INFORMATION
 WHERE THEY HAVE A 1 1/2 HR FIRE RATING.
  
 28) SHEET A2.5.1 DETAIL OF ELEVATOR
 LOBBY 0/ A6.0.0 MISSING DETAIL
  
 29) A2.5.1 ELEVATOR LOBBY DOORS T04A &
 T04B, BOTH DOORS AND ELEVATOR LOBBY
 DOORS 5TH FLOOR AND ABOVEARE MISSING
 THE FIRE RATING OF 3/4 HR SEE 707.14.1./
 TABLE 1016.1.
  
 30) SHEET A2.5.1 EAST WEST CUT SECTION,
 DETAIL1/ A4.2 NO SUCH SECTION.
  
 31) SHEET A2.1.1- A2.10.1 ALL INDICATE
 PARTITION LEGEND, PROVIDE THE EQUIVALENT
 THICKNESS AND ASSOCIATED FIRE RESISTANCE
 RATING FOR BOTH CONCRETE MASONARY WALLS
 AND CAST IN PLACE CONCRETE.
 721.3.2 CONCRETE MASONRY WALLS.
 THE FIRE-RESISTANCE RATING OF WALLS AND
 PARTITIONS CONSTRUCTED OF CONCRETE
 MASONRY UNITS SHALL BE DETERMINED FROM
 TABLE 721.3.2 . THE RATING SHALL BE
 BASED ON THE EQUIVALENT THICKNESS OF THE
 MASONRY AND TYPE OF AGGREGATE USED.
 REPORT FROM THE BLOCK MANUFACTURER FOR
 RATING OF BLOCK.NOT U. L. LISTING.
 721.2.1.1 CAST-IN-PLACE OR PRECAST
 WALLS.
 THE MINIMUM EQUIVALENT THICKNESSES OF
 CAST-IN-PLACE OR PRECAST CONCRETE WALLS
 FOR FIRE-RESISTANCE RATINGS OF 1 HOUR TO
 4 HOURS ARE SHOWN IN TABLE 721.2.1.1 .
 FOR SOLID WALLS WITH FLAT VERTICAL
 SURFACES, THE EQUIVALENT THICKNESS IS
 THE SAME AS THE ACTUAL THICKNESS. THE
 VALUES IN TABLE 721.2.1.1 APPLY TO
 PLAIN, REINFORCED OR PRESTRESSED
 CONCRETE WALLS.
  
 32) A2.5.1 DETAIL 1/A5.4INDICATES A CUT
 SECTION THROUGH A BALCONY BUT NO DETAILS
 GIVEN FOR BALCONY RAILING. GLASS IN
 HANDRAILS AND GUARDS.2407.1 MATERIALS.
 GLASS USED AS STRUCTURAL BALUSTRADE
 PANELS IN RAILINGS SHALL BE CONSTRUCTED
 OF EITHER SINGLE FULLY TEMPERED GLASS,
 LAMINATED FULLY TEMPERED GLASS OR
 LAMINATED HEAT-STRENGTHENED GLASS.
 GLAZING IN RAILING IN-FILL PANELS SHALL
 BE OF AN APPROVED SAFETY GLAZING
 MATERIAL THAT CONFORMS TO THE PROVISIONS
 OF SECTION 2406.1.1 . FOR ALL GLAZING
 TYPES, THE MINIMUM NOMINAL THICKNESS
 SHALL BE ? INCH (6.4 MM). FULLY TEMPERED
 GLASS AND LAMINATED GLASS SHALL COMPLY
 WITH CATEGORY II OF CPSC 16 CFR 1201,
 LISTED IN CHAPTER 35 .
  
 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM
 SHALL BE DESIGNED TO WITHSTAND THE LOADS
 SPECIFIED IN SECTION 1607.7 . A SAFETY
 FACTOR OF FOUR SHALL BE USED.
  
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE
 SUPPORTED BY A MINIMUM OF THREE GLASS
 BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE
 BALUSTER PANEL FAIL. GLASS BALUSTERS
 SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD .
  
 33)A2.5.1 LAUNDRY CHUTE REQUIRES A 2HR
 RATED WALL PROVIDE THE EQUIVALENT
 THICKNESS AND TYPE OF BLOCK TO BE USED,
 FROM BLOCK MANUFACTURER.
  
  
 34) SERVICE ELEVATOR MISSING ELEVATOR
 LOBBY,707.14.1 ELEVATOR LOBBY.
 ELEVATORS OPENING INTO A
 FIRE-RESISTANCE-RATED CORRIDOR AS
 REQUIRED BY SECTION 1016.1 SHALL BE
 PROVIDED WITH AN ELEVATOR LOBBY AT EACH
 FLOOR CONTAINING SUCH A CORRIDOR. THE
 LOBBY SHALL SEPARATE THE ELEVATORS FROM
 THE CORRIDOR BY FIRE PARTITIONS AND THE
 REQUIRED OPENING PROTECTION. ELEVATOR
 LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND
 OTHER PROVISIONS WITHIN THIS CODE.
  
 35) A2.9.1 COOLING TOWERS ONCE DOOR IS
 OPENED TO THIS AREA THERE IS NO 36"
 MEANS OF EGRESS AROUND THE COOLING
 TOWERS.
  
 36) 1509.7 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE
 MOUNTED ON CURBS RAISED A MINIMUM OF 8
 INCHES (203 MM) ABOVE THE ROOF SURFACE,
 OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARANCE
 HEIGHT IN ACCORDANCE WITH TABLE 1509.7 .
  
  
 37) A2.9.1 PLAN INDICATES FOR ENLARGED
 STAIR PLAN AND DIMENSIONS SEE A0.0.0.
  
 38) A2.9.1 MECHANICAL ROOM/ COOLING
 TOWERS PLANS DO NOT INDICATE THERE IS TO
 BE A GENERATOR LOCATED IN THIS AREA ,SEE
 M2.22. PROVIDE DETAILS FOR GENERATOR,
 FOR COMPLIANCE WITH:
 403.10.1 SPECIAL REQUIREMENTS FOR
 STANDBY POWER SYSTEMS.
 IF THE STANDBY SYSTEM IS A GENERATOR SET
 INSIDE A BUILDING, THE SYSTEM SHALL BE
 LOCATED IN A SEPARATE ROOM ENCLOSED WITH
 2-HOUR FIRE-RESISTANCE-RATED FIRE
 BARRIER ASSEMBLIES. SYSTEM SUPERVISION
 WITH MANUAL START AND TRANSFER FEATURES
 SHALL BE PROVIDED AT THE FIRE COMMAND
 CENTER. SURROUNDING WALL 2HR WITH
 1 1/2HR OPENING PROTECTIVES, DOOR M04A.
  
 39) A2.10.1 AT SECTION 1/ A5.1JUST TO
 THE RIGHT OF THIS SECTION THE HEIGHT OF
 THE PLANTER WALL 3'-2" AND THE HEIGHT OF
 THE GLASS RAIL AS 3'-2". SEE DETAIL
 1/A5.1 THE GLASS RAILING SITS ATOP OF
 THE PLANTER WALL AN ADDITIONAL 3'-71/2".
  
 40) A2.10.1 THE ELEVATOR DOORS AND
 WINDOWS ON EITHER SIDE OF THE ELEVATOR
 LOBBY ARE MISSING THE 1 1/2 HR RATING.
 707.14.1 ELEVATOR LOBBY.
 ELEVATORS OPENING INTO A
 FIRE-RESISTANCE-RATED CORRIDOR AS
 REQUIRED BY SECTION 1016.1 SHALL BE
 PROVIDED WITH AN ELEVATOR LOBBY AT EACH
 FLOOR CONTAINING SUCH A CORRIDOR. THE
 LOBBY SHALL SEPARATE THE ELEVATORS FROM
 THE CORRIDOR BY FIRE PARTITIONS AND THE
 REQUIRED OPENING PROTECTION. ELEVATOR
 LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND
 OTHER PROVISIONS WITHIN THIS CODE.
  
 41) A2.10.1 THE MENS AND WOMENS
 HANDICAPPED TOILET STALL DOORS ARE NOT
 DIMENSIONED PLEASE SEE FIGURE 30, THE
 STALL DOOR TO BE 32" CLEAR.
  
 42) NOTE: 424.1 PUBLIC SWIMMING POOLS
 AND BATHING PLACES.
 PUBLIC SWIMMING POOLS AND BATHING PLACES
 SHALL COMPLY WITH THE DESIGN AND
 CONSTRUCTION STANDARDS OF THIS SECTION.
 NOTE: OTHER ADMINISTRATIVE AND
 PROGRAMMATIC PROVISIONS MAY APPLY. SEE
 DEPARTMENT OF HEALTH (DOH) RULE 64E-9,
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER
 514, FLORIDA STATUTES.FAC 514 PUBLIC
 SWIMMING AND BATHING FACILITIES.
  
 43) A2.10.1 BAR D11 NO CUT SECTION
 INDICATING COMPLIANCE WITH, FAIR HOUSING
 REACH RANGES, ACCESSIBLE OUTE BEHIND
 BAR.
  
 44)A2.11.1 PLANS DO NOT INDICATE
 ELEVATOR VENTS OR NOTES WHERE TO FIND
 VENTS.
 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR
 OR FLOORS AT THE TOP OF THE HOISTWAY,
 AND SHALL OPEN EITHER DIRECTLY TO THE
 OUTER AIR OR THROUGH NONCOMBUSTIBLE
 DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE
 DUCTS SHALL BE PERMITTED TO PASS THROUGH
 THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE
 THE HOISTWAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS
 THAN THE FIRE PROTECTION RATING REQUIRED
 FOR THE HOISTWAY. HOLES IN THE MACHINE
 ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR
 EQUIPMENT SHALL BE LIMITED SO AS NOT TO
 PROVIDE GREATER THAN 2 INCHES (51 MM) OF
 CLEARANCE ON ALL SIDES.
  
 3004.3 AREA OF VENTS.
 EXCEPT AS PROVIDED FOR IN SECTION
 3004.3.1 , THE AREA OF THE VENTS SHALL
 NOT BE LESS THAN 3? PERCENT OF THE AREA
 OF THE HOISTWAY NOR LESS THAN 3 SQUARE
 FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR,
 AND NOT LESS THAN 3? PERCENT NOR LESS
 THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY,
 WHICHEVER IS GREATER. OF THE TOTAL
 REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE OF THE PERMANENTLY
 OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON
 DETECTION OF SMOKE FROM ANY OF THE
 ELEVATOR LOBBY SMOKE DETECTORS.
  
 45) A3.1.1 & A3.1.3 NORTH AND EAST
 ELEVATIONS, THE DISTANCE TO THE PROPERTY
 LINE IS NOT PROVIDED, THE ALLOWABLE AREA
 OF OPENINGS PER FLOOR CAN'T BE COMPUTED.
 704.8 ALLOWABLE AREA OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED OR
 PROTECTED OPENINGS PERMITTED IN AN
 EXTERIOR WALL IN ANY STORY SHALL NOT
 EXCEED THE VALUES SET FORTH IN TABLE
 704.8 . WHERE BOTH UNPROTECTED AND
 PROTECTED OPENINGS ARE LOCATED IN THE
 EXTERIOR WALL IN ANY STORY, THE TOTAL
 AREA OF THE OPENINGS SHALL COMPLY WITH
 THE FOLLOWING FORMULA:
  
 A/A+AU/AU<1.0
  
 46) A6.1.1- A6.14.2 1207.2 AIR-BORNE
 SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 47) A6.1.1- A6.14.1 1207.3
 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492.
  
 48) A6.1.1 DOOR T01E TO BE A MINIMUM OF
 32" CLEAR, FAIR HOUSING ANSI A117.1-
 404.2.3.SMALL CLOSETS SUCH AS LINEN
 CLOSETS NOT COVERED, SHELVES WITHIN
 REACH, THIS CLOSEET IS 3'-0" DEEP.
  
 49) A6.2.1 DOOR T02C1 SEE DOOR CHART FOR
 WIDTH.
  
 50) A6.3.2 NOTE: REFER TO INTERIOR
 DESIGNERS DRAWINGS FOR ALL BATH
 ACCESSORY SPECIFICATIONS AND MOUNTING
 HEIGHT. THERE IS NO INDEX NOR NOTE
 INDICATING WHERE THIS INFORMATION CAN BE
 LOCATED. 11-4.26.2 SIZE AND SPACING OF
 GRAB BARS AND HANDRAILS.
 THE DIAMETER OR WIDTH OF THE GRIPPING
 SURFACES OF A HANDRAIL OR GRAB BAR SHALL
 BE 1? INCHES TO 1? INCHES (32 MM TO 38
 MM), OR THE SHAPE SHALL PROVIDE AN
 EQUIVALENT GRIPPING SURFACE. IF
 HANDRAILS OR GRAB BARS ARE MOUNTED
 ADJACENT TO A WALL, THE SPACE BETWEEN
 THE WALL AND THE GRAB BAR SHALL BE 1?
 INCHES (38 MM) [SEE FIGURE 11-39 (A),
 FIGURE 11-39 (B), FIGURE 11-39 (C), AND
 FIGURE 11-39 (E)]. HANDRAILS MAY BE
 LOCATED IN A RECESS IF THE RECESS IS A
 MAXIMUM OF 3 INCHES (76 MM) DEEP AND
 EXTENDS AT LEAST 18 INCHES (455 MM)
 ABOVE THE TOP OF THE RAIL [SEE FIGURE
 11-39 (D)].
 11-4.26.3
 11-4.26.3 STRUCTURAL STRENGTH.
 THE STRUCTURAL STRENGTH OF GRAB BARS,
 TUB AND SHOWER SEATS, FASTENERS AND
 MOUNTING DEVICES SHALL MEET THE
 FOLLOWING SPECIFICATION:
 (1)BENDING STRESS IN A GRAB BAR OR
 SEAT INDUCED BY THE MAXIMUM BENDING
 MOMENT FROM THE APPLICATION OF 250 LBF
 (1112 N) SHALL BE LESS THAN THE
 ALLOWABLE STRESS FOR THE MATERIAL OF THE
 GRAB BAR OR SEAT.
 (2)SHEAR STRESS INDUCED IN A GRAB
 BAR OR SEAT BY THE APPLICATION OF 250
 LBF (1112 N) SHALL BE LESS THAN THE
 ALLOWABLE SHEAR STRESS FOR THE MATERIAL
 OF THE GRAB BAR OR SEAT. IF THE
 CONNECTION BETWEEN THE GRAB BAR OR SEAT
 AND ITS MOUNTING BRACKET OR OTHER
 SUPPORT IS CONSIDERED TO BE FULLY
 RESTRAINED, THEN DIRECT AND TORSIONAL
 SHEAR STRESSES SHALL BE TOTALED FOR THE
 COMBINED SHEAR STRESS, WHICH SHALL NOT
 EXCEED THE ALLOWABLE SHEAR STRESS.
 (3)SHEAR FORCE INDUCED IN A
 FASTENER OR MOUNTING DEVICE FROM THE
 APPLICATION OF 250 LBF (1112 N) SHALL BE
 LESS THAN THE ALLOWABLE LATERAL LOAD OF
 EITHER THE FASTENER OR MOUNTING DEVICE
 OR THE SUPPORTING STRUCTURE, WHICHEVER
 IS THE SMALLER ALLOWABLE LOAD.
 (4)TENSILE FORCE INDUCED IN A
 FASTENER BY A DIRECT TENSION FORCE OF
 250 LBF (1112 N) PLUS THE MAXIMUM MOMENT
 FROM THE APPLICATION OF 250 LBF (1112N)
 SHALL BE LESS THAN THE ALLOWABLE
 WITHDRAWAL LOAD BETWEEN THE FASTENER AND
 THE SUPPORTING STRUCTURE.
 (5)GRAB BARS SHALL NOT ROTATE
 WITHIN THEIR FITTINGS.
 ALL HANDRAILS, GRAB BARS, AND TUB AND
 SHOWER SEATS REQUIRED TO BE ACCESSIBLE
 BY SECTION 11-4.1 , 11-4.8 , 11-4.9 ,
 11-4.16 , 11-4.17 , 11-4.20 OR 11-4.21
 SHALL COMPLY WITH SECTION 11-4.26 .
  
 51) A6.6.2 MASTER BEDROOM: 11-9.2.2
 MINIMUM REQUIREMENTS.
 AN ACCESSIBLE UNIT, SLEEPING ROOM OR
 SUITE SHALL BE ON AN ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 AND HAVE
 THE FOLLOWING ACCESSIBLE ELEMENTS AND
 SPACES.
 (1)ACCESSIBLE SLEEPING ROOMS SHALL
 HAVE A 36 INCH (915 MM) CLEAR WIDTH
 MANEUVERING SPACE LOCATED ALONG BOTH
 SIDES OF A BED, EXCEPT THAT WHERE TWO
 BEDS ARE PROVIDED, THIS REQUIREMENT CAN
 BE MET BY PROVIDING A 36 INCHES (915 MM)
 WIDE MANEUVERING SPACE LOCATED BETWEEN
 THE TWO BEDS. CHECK ALL UNITS!
  
 51) A6.10.1A6.1.1 DOOR P01E TO BE A
 MINIMUM OF 32" CLEAR, FAIR HOUSING ANSI
 A117.1- 404.2.3.SMALL CLOSETS SUCH AS
 LINEN CLOSETS NOT COVERED, SHELVES
 WITHIN REACH, THIS CLOSEET IS 3'-0"
 DEEP.
  
 52)A6.13.1 MASTER BEDROOM MASTER
 BEDROOM: 11-9.2.2 MINIMUM REQUIREMENTS.
 AN ACCESSIBLE UNIT, SLEEPING ROOM OR
 SUITE SHALL BE ON AN ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 AND HAVE
 THE FOLLOWING ACCESSIBLE ELEMENTS AND
 SPACES.
 (1)ACCESSIBLE SLEEPING ROOMS SHALL
 HAVE A 36 INCH (915 MM) CLEAR WIDTH
 MANEUVERING SPACE LOCATED ALONG BOTH
 SIDES OF A BED, EXCEPT THAT WHERE TWO
 BEDS ARE PROVIDED, THIS REQUIREMENT CAN
 BE MET BY PROVIDING A 36 INCHES (915 MM)
 WIDE MANEUVERING SPACE LOCATED BETWEEN
 THE TWO BEDS. CHECK ALL UNITS!
  
 53) A8.1.1 FINISH SCHEDULE NOT COMPLETE
 PAGE IS BLANK.
  
 54) A9.1 DETAILS 3& 4 ARE MISSING THE
 SOUND TRANSMITION RATING.1207.2
 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 55) SHEET A9.1 REFERS BACK TO 0/A8.00
 FOR LIMITING HEIGHT AND GAUGE TABLE.
 THERE IS NO SUCH SHEET.
  
 56) SHEET A9.2 PROVIDE UL LISTING OR
 GYPSUM ASSOCIATION NUMBER FOR EACH
 ASSEMBLY.FIRE PARTITION. A VERTICAL
 ASSEMBLY OF MATERIALS DESIGNED TO
 RESTRICT THE SPREAD OF FIRE IN WHICH
 OPENINGS ARE PROTECTED.
 SHAFT ENCLOSURE. THE WALLS OR
 CONSTRUCTION FORMING THE BOUNDARIES OF A
 SHAFT.
  
 57) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 58)FL BLD CODE 1609.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) CURTAIN WALL
 B) STOREFRONT WINDOW AND DOOR
 C) LOUVERED DOORS -REQUIRES STORM
 SHUTTERS SEE REPORT (NOA)
 D) EXTERIOR DOOR AT AUTO ELEVATOR
 E) SOFFITS(EFIS)
 F) ROOF HATCH
 G) PRE-ENGINEERED A/C STANDS
 H) MULLIONS
  
 58) CONTRACTOR TO HIGHLIGHT WHICH
 ROOFING APPLICATION FLAT DECK SBS SYSTEM
 DECK TYPE APPLICATION TYPE 31 OR DECK
 TYPE 3.
  
 59) PLANS DO NOT ADEQUATELY PROVIDE
 WHAT TYPE OF WINDOWS ARE TO BE USED ,
 EXAMPLE UNITS 1707- 2107 WINDOW (00)
 DEPENDING ON TYPE OF WINDOW EAST
 ELEVATION REPORT FOR WIND TUNNEL TEST
 INDICATES A NEGATIVE PEAK PRESSURE OF
 105.
 PROVIDE MORE DETAIL OF WINDOW TYPES AND
 LOCATION. (WINDOW SCHEDULE)
  
 60) SHEET A5.8 PLANS INDICATE DROPPED
 CEILINGS BUT NO DETAILS INDICATING THE
 TYPE OF CEILING THICKNESS, TYPE OF
 FRAMING, THICKNESS SIZE, MATERIAL
 THICKNESS NOR FLANGE SIZE. PLANS ALSO DO
 NOT PROVIDE THE ALLOWABLE CEILING
 DEFLECTIONS. PLANS DO NOT INDICATE IF
 STIFF BACKS ARE USED.THIS SAME
 INFORMATION WILL BE REQUIRED FOR DROPPED
 SOFFITS INTERIOR AND EXTERIOR.
  
 61) (A5.6) EXTERIOR DETAILS THERE IS NO
 DETAILS INDICATING HOW TO FASATEN TO
 DECK ABOVE, FREQUENCY OF FASTENERS NOR
 SPACING. NO MENTION OF SUBSHEATHING OR
 FINISH.
  
 62) S-1 NOTE: 8'-0" THICK MAT FOUNDATION
 SEE DWG S-16 FOR DETAILS, NO DETAILS
  
 63) A6.1.1 HEARING IMPAIRED UNITS,
 SHOW COMPLIANCE WITH 11-9.3/ 11-4.28.4.
 PROVIDE MANUFACTURER SPEC SHEET.
  
 64) A6.11 TYPICAL BALCONY RAILING NOTE
 NOT COMPLETE.XXX
  
 ADDITIONAL COMMENTS MAY APPEAR ON THE
 NEXT REVIEW DUE TO THE RESPONCE TO THESE
 COMMENTS OR LACK THERE OFF.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)805-6731
  
  