2006-05-05 00:00:00 | |
| |
| DENIED |
| |
| NOTES 1 AND 4 WHERE ADDRESSED BUT MORE |
| INFORMATION IS NEED, NOTE 3 WAS NOT |
| ADDRESSED. |
| |
| 1) HANDRAIL EXTENTION IS SHOWN ON A2-1.0 |
| BUT SIZE IS NOT SHOWN. PLEASE SHOW THAT |
| MIN REQUIREMENT IS MET PER 11-4.8.5(2) |
| FBC |
| A2-1.0 SHOWS FOOTING UNDER CMU.THERE ARE |
| NO DETAILS FOR FOOTING ONTHIS DETAIL OR |
| 03/A0-0 |
| LANDINGS ON RAMPS ARE REQUIRED TO BE NO |
| LESS THAN 72" PER 11-4.8.4(2) FBC |
| |
| 3) PLEASE SEE A1-1.0 AT DOOR 114 AND |
| RAMP MANUVERING REQUIRES A MINIMUM 24" |
| OF LEVEL AREA ON THE LATCH SIDE ALSO |
| APPROCH FROM THE PUSH SIDE REQUIRES A |
| MINIMUM 12" AT THE LATCH SIDE OF DOOR |
| (SEE FIG. 25 (A)AND(B) IN CHAPTER 11) |
| FBC |
| |
| 4) IN BUILDINGS WITH MULTIPLE ACCESSIBLE |
| ENTRANCES, ACCESSIBLE PARKING SPACES |
| SHALL BE DISPERSED AND LOCATED CLOSEST |
| TO THE ACCESSABLE ENTRANCES PER 11-4.6.2 |
| FBC |
| |
| NEW NOTES: |
| |
| 1) DOOR 114 IS AN INTERIOR DOOR THAT |
| WILL BE USED AS AN EXTERIOR DOORAS |
| SUCH PLEASE PROVIDE PRODUCT APPROVALS |
| PER 9B-72 F.A.C. ALSO STATE WIND DESIGN |
| CRITERIA AND COMPONENT AND CLADING PSF"S |
| FOR DOOR ON DRAWING PER 1603.1.4 FBC |
| |
| 2) APPLICABLE CODES SECTION OF PAGE T1 |
| AND LS0-0 DO NOT MATCH SHOULD READ FBC |
| 2004 PLEASE CLARIFY |
| |
| 3) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED. ALTHOUGH IT IS |
| GOOD FOR 1 YEAR FROM DATE OF ISSUE WORK |
| MUST COMMENCE WITHIN 90 DAYS. PLEASE |
| RE-RECORD |
| |
| 4) PLEASE NOTE THAT NO FURTHER PLAN |
| REVIEWS WILL BE DONE UNTIL FALSE ALARM |
| FEES ARE PAID AND FINANCE DEPT HOLD IS |
| REMOVED CONTACT EFRAIM GARCED @ 805-1320 |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |