Plan Review Notes
Plan Review Notes For Permit 06010290
Permit Number 06010290
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-11 00:00:00 
 PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
  
 1) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOUCMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICAL. CONSTRUCTION
 DOUCMENTS SHALL BE OF SUFFICENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT ITWILL CONFORM TOTHE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS
 AS DETERMINED BY THE BUILDING OFFICAL (
 SEE ALSO SECTION 106.3.5)
 2) SHT LS0-0 REQUIRED MINIMUM FACILITIES
 SHOW THE LOCATION OF THE REQUIRED D/F
 AND S/S, REFERENCED ON CODE SUMMARY.
 3) SHT A1-1.0 ROOM #108,109 DARK ROOM.
 SEC 803.2 NEUTRALIZING DEVICE REQUIRED
 FOR CORROSIVE WASTE.
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISORINDUSTRIAL COORDINATOR,
 LYNN MASSON
 OFFICE 561-822-2271
 E-MAIL [email protected]
 4)SHT A1-1.0 SEC 415 GROUP H-5
 OCCUPANCY. ROOM #110,111 JEWELRY MFG.
 STUDIO. PROVIDE IN DETAIL ALL
 INFORMATION REQUIRED FOR GROUP H-5 USE.
 5) SHT A1-1.0 CONFERENCE RM SINK.
 11-4.24 SINKS.
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
 11-4.24.2 HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER
 OR RIM NO HIGHER THAN 34 INCHES (865 MM)
 ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM)
 WIDE, AND 19 INCHES (485 MM) DEEP SHALL
 BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6?
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
 6)SEC 106.3.5.1.3 (3,4.)COMMERICAL
 BUILDINGS: PLUMBING, SANITARY; WATER.
 ISOMETRIC REQUIRED.
 7) SEC 106.3.5.2 GAS: ISOMETRIC
 REQUIRED.
 8)PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  