| FBC 2004 PLUMBING CODE PLAN REVIEW |
| FBC2004 FUEL GAS CODEPLAN REVIEW |
| FBC 2004 CH 11, FL ACESSIBILITY CODE |
| DENIED |
| |
| 1) 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE |
| MATERIAL. ELECTRONIC MEDIA DOUCMENTS ARE |
| PERMITTED TO BE SUBMITTED WHEN APPROVED |
| BY THE BUILDING OFFICAL. CONSTRUCTION |
| DOUCMENTS SHALL BE OF SUFFICENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT ITWILL CONFORM TOTHE |
| PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS |
| AS DETERMINED BY THE BUILDING OFFICAL ( |
| SEE ALSO SECTION 106.3.5) |
| 2) SHT LS0-0 REQUIRED MINIMUM FACILITIES |
| SHOW THE LOCATION OF THE REQUIRED D/F |
| AND S/S, REFERENCED ON CODE SUMMARY. |
| 3) SHT A1-1.0 ROOM #108,109 DARK ROOM. |
| SEC 803.2 NEUTRALIZING DEVICE REQUIRED |
| FOR CORROSIVE WASTE. |
| CONTACT W P BEACHWATERPLANT LAB |
| SUPERVISORINDUSTRIAL COORDINATOR, |
| LYNN MASSON |
| OFFICE 561-822-2271 |
| E-MAIL [email protected] |
| 4)SHT A1-1.0 SEC 415 GROUP H-5 |
| OCCUPANCY. ROOM #110,111 JEWELRY MFG. |
| STUDIO. PROVIDE IN DETAIL ALL |
| INFORMATION REQUIRED FOR GROUP H-5 USE. |
| 5) SHT A1-1.0 CONFERENCE RM SINK. |
| 11-4.24 SINKS. |
| 11-4.24.1 GENERAL. |
| SINKS REQUIRED TO BE ACCESSIBLE BY |
| SECTION 11-4.1 SHALL COMPLY WITH SECTION |
| 11-4.24. |
| 11-4.24.2 HEIGHT. |
| SINKS SHALL BE MOUNTED WITH THE COUNTER |
| OR RIM NO HIGHER THAN 34 INCHES (865 MM) |
| ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE. |
| KNEE CLEARANCE THAT IS AT LEAST 27 |
| INCHES (685 MM) HIGH, 30 INCHES (760 MM) |
| WIDE, AND 19 INCHES (485 MM) DEEP SHALL |
| BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.4 DEPTH. |
| EACH SINK SHALL BE A MAXIMUM OF 6? |
| INCHES (165 MM) DEEP. |
| 11-4.24.5 CLEAR FLOOR SPACE. |
| A CLEAR FLOOR SPACE AT LEAST 30 INCHES |
| BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE |
| PROVIDED IN FRONT OF A SINK TO ALLOW |
| FORWARD APPROACH. THE CLEAR FLOOR SPACE |
| SHALL BE ON AN ACCESSIBLE ROUTE AND |
| SHALL EXTEND A MAXIMUM OF 19 INCHES (485 |
| MM) UNDERNEATH THE SINK (SEE FIGURE |
| 11-32). |
| 11-4.24.6 EXPOSED PIPES AND SURFACES. |
| HOT WATER AND DRAIN PIPES EXPOSED UNDER |
| SINKS SHALL BE INSULATED OR OTHERWISE |
| CONFIGURED SO AS TO PROTECT AGAINST |
| CONTACT. THERE SHALL BE NO SHARP OR |
| ABRASIVE SURFACES UNDER SINKS. |
| 11-4.24.7 FAUCETS. |
| FAUCETS SHALL COMPLY WITH SECTION |
| 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, |
| TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED |
| MECHANISMS ARE ACCEPTABLE DESIGNS. |
| 6)SEC 106.3.5.1.3 (3,4.)COMMERICAL |
| BUILDINGS: PLUMBING, SANITARY; WATER. |
| ISOMETRIC REQUIRED. |
| 7) SEC 106.3.5.2 GAS: ISOMETRIC |
| REQUIRED. |
| 8)PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT PLUMBING |
| PLANS. |
| END OF COMMENTS, QUESTIONS 561-805-6692 |
| |
| |