Plan Review Notes For Permit 06010290 |
Permit Number |
06010290 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-03 00:00:00 | | | | | DENIED | | | | 1) PROVIDE DETAILS ON RAMP CONSTRUCTION | | FOOTING DETAILS, DECK CONSTRUCTION, TIE | | DOWNS, HANDRAIL ETC. | | | | 2) RAMPS SHALL HAVE HANDRAIL ON BOTH | | SIDE PER 11-4.8.5 FBC | | | | 3) COMPLY WITH MANUVERING DISTANCE | | REQUIREMENTS AT RAMP LANDING PER | | 11-4.13.6 FBC | | | | 4) SHOW LOCATION OF ACCESSABLE PARKING | | SPACE AND ROUTE TO NEW ACCESSABLE RAMP | | AND ENTRANCE | | | | 5) DOOR HARDWARE SHALL COMPLY WITH | | 11-4.13.9 | | | | 6) DOOR SCHEDULE SHOWS #104 AND #114 AS | | PAIRS PLEASE CLARIFY | | | | 7) PROVIDE DETAILS OF RECEPTION COUNTER | | FOR COMPLIANCE WITH ACCESSABILITY PER | | 11-7.2 | | | | 8) PROVIDE ACCESSABILITY REQUIREMENTS | | FOR KITCHEN SINK PER 11-4.24 | | | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | | | | | | | |
|