Plan Review Notes For Permit 06010282 |
Permit Number |
06010282 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-03-28 00:00:00 | BUILDING REVIEW 4TH CHECKLIST: | | 1- ON THIRD PLAN REVIEW CHECKLIST, | | ENGINEER WAS ASKED TO REVIEW GENERAL | | LIMITATION #7 AND TO PROVIDE | | CALCULATIONS BASED ON THE STANDARD RAS | | 117. INFORMATION SUBMITTED DOESN'T | | ADDRESS THIS COMMENT. | | | | 2- ENGINEER TO SEE SPECIFIC ROOF PRODUCT | | APPROVAL SUBMITTED TO SEE APPROVED | | FASTENER TYPE AND SPACING AND MAXIMUM | | DESIGN PRESSURES ALLOWED FOR THE SYSTEM. | | INFORMATION SUBMITTED HAS NOT | | COORDINATION WITH PRODUCT APPROVAL. | | PRODUCT APPROVAL SYSTEM DESIGN PRESSURE | | OF -52.5PSF IS ASSUMED TO BE FOR ZONE | | ONE. ENGINEER NEEDS TO PROVIDE FASTENER | | ENHANCING TO RESIST DESIGN PRESSURES AT | | ZONES 2 AND 3. | | | | 3- ENGINEER TO SEE ATTACHED COPY OF | | FLORIDA STATUTE 553.80(2)(B) REGARDING | | DESIGN PROFESSIONAL DOCUMENTS. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|