2006-02-28 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- PRODUCT APPROVAL FOR POLYGLASS USA
 MODIFIED BITUMEN ROOF SYSTEM IS LIMITED
 BY GENERAL LIMITATION #7, WHICH REQUIRES
 REQUIRES ENHANCED UPLIFT CALCULATIONS
 FOR ROOF SYSTEM AT PERIMETER AND CORNER
 AREAS TO BE PREPARED, SIGNED AND SEALED
 BY A PROFESSIONAL AS LISTED IN
 LIMITATION #7.
 SUCH CALCULATIONS NEED TO BE DONE IN
 COMPLIANCE WITH ROOFING APPLICATION
 STANDARD RAS 117. CALCULATIONS SUBMITTED
 BY THE PROFESSIONAL ENGINEER RICHARD
 BOYETTE DON'T ADDRESS THE STANDARD CITED
 ON LIMITATION #7. NEED CALCULATIONS FOR
 THE ENHANCING OF THE FLAT ROOF SYSTEM TO
 BE INSTALLED, NOT THE ROOF SHEATHING.
 ENGINEER TO READ LIMITATION #7 AND
 PROVIDE REQUESTED CALCULATIONS.
  