Plan Review Notes
Plan Review Notes For Permit 06010269
Permit Number 06010269
Review Stop E
Sequence Number 2
Notes
Date Text
2006-01-31 00:00:00 
 NO COMMENTS FROM THE PREVIOUS REVIEW
 WERE ADDRESSED.
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE THE AIC RATING FOR THE
 SERVICE EQUIPMENT PER 110.9.
  
 2} SUBMIT A PANEL SCHEDULE SO THAT
 BRANCH CIRCUIT COMPLIANCE CAN BE
 REVIEWED.
  
 3} THE REFERENCE IN THE ELECTRICAL NOTES
 TO THE 2001 NEC ARE INCORRECT, WE ARE
 CURRENTLY UNDER THE 2002 EDITION.
  
 4} THE 3 SMALL APPLIANCE CIRCUITS IN THE
 LOAD CALCULATION MUST BE 1500 VA EACH
 PER 220.16(A).
  
 5} A RECEPTACLE MUST BE ADDED IN BEDROOM
 #3 TO COMPLY WITH 210.52(A)(1).
  
 6} A SMOKE DETECTOR IS REQUIRED OUTSIDE
 BEDROOM #3 PER 313.1 FBC(RES). BECAUSE
 THIS WOULD PLACE IT IN THE KITCHEN SEE
 NFPA-72 ARTICLE 11.8.3.5(4) FOR
 REQUIREMENTS.
  
 7} LOCATE A RECEPTACLE IN BEDROOM #1 TO
 COMPLY WITH 210.52(A)(2) AT ENTRANCE.
 SEE REVIEWED SET OF PLANS.
  
 8} A RECEPTACLE MUST BE ADDED IN THE
 DINING ROOM PER 210.52(A)(1), ALSO SEE
 210.52(B)(1).
  
 9} THE LOAD CALC INDICATES TWO A/C
 SYSTEMS, THERE IS ONLY ONE SHOWN ON THE
 DRAWINGS. PLEASE CORRELATE.
  
  
 ATTACHED IS THE REQUIRED VIOLATION
 NOTICE ADDRESSED TO THE DESIGN
 PROFESSIONAL PER 553.80(2)(B)FLORIDA
 STATUTES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  