2006-01-13 00:00:00 | *** DENIED *** |
| 1) NEED TO SUBMIT ENERGY CALCULATIONS. |
| ENERGY CALCULATIONS NEED TO BE ON FORM |
| 600A-04 (2004) PER FBC 13-600.3.A . |
| |
| 2) NEED TO PROVIDE RETURN AIR IN |
| BEDROOMS, SEE NOTE #3. |
| |
| 3)BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| 4) AFTER GETTING YOUR ENERGY CAL'S. |
| PLEASE CHECK THE MANUAL 'J' SECTION AND |
| AJUST THE SIZE OF THE SUPPLY AIR DUCTS |
| (FLEX) ACCORDINGLY, THEY APPEAR TO LARGE |
| AT THIS TIME. |
| |
| 5) PLEASE SHOW BATHROOM AND KITCHEN |
| EXHUST DUCTS ON MECHANICAL PLANS. |
| |
| 6) PLEASE SHOW A/C SYSTEM'S TOTAL AND |
| SENSIBLE BTU'S ON MECHANICAL PLANS. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |