2006-01-13 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PROVIDE THE AIC RATING FOR THE |
| SERVICE EQUIPMENT PER 110.9. |
| |
| 2} SUBMIT A PANEL SCHEDULE SO THAT |
| BRANCH CIRCUIT COMPLIANCE CAN BE |
| REVIEWED. |
| |
| 3} THE REFERENCE IN THE ELECTRICAL NOTES |
| TO THE 2001 NEC ARE INCORRECT, WE ARE |
| CURRENTLY UNDER THE 2002 EDITION. |
| |
| 4} THE 3 SMALL APPLIANCE CIRCUITS IN THE |
| LOAD CALCULATION MUST BE 1500 VA EACH |
| PER 220.16(A). |
| |
| 5} A RECEPTACLE MUST BE ADDED IN BEDROOM |
| #3 TO COMPLY WITH 210.52(A)(1). |
| |
| 6} A SMOKE DETECTOR IS REQUIRED OUTSIDE |
| BEDROOM #3 PER 313.1 FBC(RES). BECAUSE |
| THIS WOULD PLACE IT IN THE KITCHEN SEE |
| NFPA-72 ARTICLE 11.8.3.5(4) FOR |
| REQUIREMENTS. |
| |
| 7} LOCATE A RECEPTACLE IN BEDROOM #1 TO |
| COMPLY WITH 210.52(A)(2) AT ENTRANCE. |
| SEE REVIEWED SET OF PLANS. |
| |
| 8} A RECEPTACLE MUST BE ADDED IN THE |
| DINING ROOM PER 210.52(A)(1), ALSO SEE |
| 210.52(B)(1). |
| |
| 9} THE LOAD CALC INDICATES TWO A/C |
| SYSTEMS, THERE IS ONLY ONE SHOWN ON THE |
| DRAWINGS. PLEASE CORRELATE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |