 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE THE AIC RATING FOR THE
 SERVICE EQUIPMENT PER 110.9.
  
 2} SUBMIT A PANEL SCHEDULE SO THAT
 BRANCH CIRCUIT COMPLIANCE CAN BE
 REVIEWED.
  
 3} THE REFERENCE IN THE ELECTRICAL NOTES
 TO THE 2001 NEC ARE INCORRECT, WE ARE
 CURRENTLY UNDER THE 2002 EDITION.
  
 4} THE 3 SMALL APPLIANCE CIRCUITS IN THE
 LOAD CALCULATION MUST BE 1500 VA EACH
 PER 220.16(A).
  
 5} A RECEPTACLE MUST BE ADDED IN BEDROOM
 #3 TO COMPLY WITH 210.52(A)(1).
  
 6} A SMOKE DETECTOR IS REQUIRED OUTSIDE
 BEDROOM #3 PER 313.1 FBC(RES). BECAUSE
 THIS WOULD PLACE IT IN THE KITCHEN SEE
 NFPA-72 ARTICLE 11.8.3.5(4) FOR
 REQUIREMENTS.
  
 7} LOCATE A RECEPTACLE IN BEDROOM #1 TO
 COMPLY WITH 210.52(A)(2) AT ENTRANCE.
 SEE REVIEWED SET OF PLANS.
  
 8} A RECEPTACLE MUST BE ADDED IN THE
 DINING ROOM PER 210.52(A)(1), ALSO SEE
 210.52(B)(1).
  
 9} THE LOAD CALC INDICATES TWO A/C
 SYSTEMS, THERE IS ONLY ONE SHOWN ON THE
 DRAWINGS. PLEASE CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  