Plan Review Notes For Permit 06010260 |
Permit Number |
06010260 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-06 00:00:00 | DENIED | | REFERENCE:FBC-2004 424.2 SWIMMING POOLS | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING | | INFORMATION REQUIRED FOR PLAN REVIEW: | | | | 1.) FBC-2004 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON | | WATER SERVICE.(ADD TO NOTES) | | 2) FBC-2004 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 3) FBC-2004 JOINTS AND CONNECTIONS, FBC | | PLBG. SEC. 605.21, PURPLE PRIMER | | REQUIRED ON PVC PIPING.(ADD TO NOTES) | | 4) FBC-2004 424.2.14.4 CONNECTIONS, ALL | | WATER HEATING EQUIPMENT SHALL BE | | INSTALLED WITH FLANGES OR UNION | | CONNECTIONS ADJACENT TO THE HEATER.(ADD | | TO NOTES) | | 5) FBC-2004 424.2.15 GAS PIPING SHALL | | COMPLY WITH FBC-2004 FUEL GAS. SEPERATE | | PLANS AND PERMIT REQUIRED.(ADD TO NOTES, | | AND SPECIFY WHAT MODEL GAS POOL HEATER | | IS BEING USED) | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561)805-6730 | | FAX (561)805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561)805-6721 | | |
|