2006-03-30 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: |
| |
| 1- THIS IS THE THIRD TIME REQUESTING |
| PEDESTRIAN WALKWAYACCESSIBILITY |
| INFORMATION TO REVIEW COMPLIANCE WITH |
| CHAPTER 11 FBC 2004. |
| |
| FIRST TWO TIMES THIS ITEM WAS NOT |
| ADDRESSED AT ALL. THIS TIME THE ONLY |
| INFORMATION SUBMITTED WAS NOTE #19 |
| SAYING "BRIDGE SHALL BE INSTALLED TO |
| MEET ADA ACCESSIBILITY REQUIREMENTS, |
| RISE SHALL NOT EXCEED 5%. GUIDERAILS |
| SHALL BE INSTALLED TO BOCA STANDARDS". |
| THIS IS NOT ENOUGH INFORMATION FOR |
| REVIEW AND SPECIFIED REFERENCES DON'T |
| APPLY TO FLORIDA. |
| (ENGINEER TO READ ATTACHED COPY OF |
| FLORIDA STATUTE 553.80(2)(B) REGARDING |
| DESIGN PROFESSI0NAL DOCUMENTS AND |
| MULTIPLE REVIEWS) |
| |
| 2- DESIGNER OF RECORD NEED TO REVIEW |
| CHAPTER 11 OF FLORIDA BUILDING CODE 2004 |
| AND PROVIDE THE SPECIFIC INFORMATION |
| THAT APPLIES TO THE PEDESTRIAN WALKWAY. |
| |
| 3- DRAWING # 203145-00 THAT HAS |
| ADDITIONAL NOTE #19 IS PART OF THE |
| CONSTRUCTION DOCUMENTS AND IS MISSING |
| THE ENGINEER'S TITLE BLOCK, SEAL AND |
| SIGNATURE. |
| |
| 4- FROM PREVIOUS CHECKLISTS ENGINEER WAS |
| ASKED TO SUBMIT ALL DOCUMENTS WITH HIS |
| ORIGINAL SEAL, SIGNATURE AS REQUIRED BY |
| CHAPTER 471 FLORIDA STATUTE AND FLORIDA |
| ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| LAST PACKAGE SUBMITTED ADDRESSING THE |
| FLORIDA PRODUCT APPROVALS REVIEW DOESN'T |
| HAVE ORIGINAL SEAL AND SIGNATURE. |
| |
| 5- ENGINEER USES THE UZMAN ENGINEERING |
| NAME ON WIND LOAD CALCULATIONS. SEE |
| SHEET NUMBER 203145-01 OF LARGE SET OF |
| DRAWINGS 24"X36" SHEETS. THAT'S WHY |
| CERTIFICATE OF AUTHORIZATION WAS |
| REQUESTED ON PREVIOUS CHECKLISTS. |
| |
| 6- THERE ARE TOO MANY SETS OF PLANS |
| SUBMITTED. PLEASE SUBMIT ONLY TWO MOST |
| RECENT SETS WITH ALL REQ'D INFORMATION |
| (REVISIONS, TITLE BLOCK AND ORIGINAL |
| SEAL AND SIGNATURE). |
| PROVIDE LARGE SETS (24"X36" SHEETS) OR |
| SMALL SETS (8 1/2"X11" SHEETS) NOT BOTH |
| TO AVOID CONFUSIONS. THERE IS SOME |
| INFORMATION THAT IS IN ONE SET BUT IS |
| NOT IN THE OTHER. CHECK IT OUT. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |
| |